Data Sheet

RISH EM 1340 / 30 / 20
(Programmable)

Compact True RMS Energy Meter


for Energy Monitoring
RISH EM series is specially designed for Active,
Reactive and Apparent Energy Measurement
including per phase THD, Powers and others
parameters as per different models.

True RMS Measurement Energy as per IEC 62053 Onsite Programmable Low Back Depth
Phase Reversal Indication LCD Display with Back-lit RS485, Limit or Pulse Output

Measure Control Record Analyze


Data Sheet
RISH EM 1340 / 30 / 20

RISH EM series measures important electrical parameters in 3


phase and single phase Network & replaces the multiple
analog panel meters. It measures electrical parameters like
Active / Reactive / Apparent energy , power as per models. The
instrument has 2 configurable optional outputs as pulse output
for energy measurement or limit output.

Applications:
Internal Energy billing
Electrical load monitoring
Sub-metering
Genset, Test Benches and Laboratories

Product Features:
True RMS measurement: User Configurable Features:
Measures distorted waveform up to 15th Harmonic. User can select any five or ten measurement
screens which will be shown on display. Also backlit
Energy as per IEC 62053: can be programmed to switched on or off.
Independent Import and Export Energy counter.
Active energy (kWh), Reactive energy (kVArh), LCD Display with Backlit:
Apparent energy (kVAh) measurement. LCD shows 3 Parameters at a glance.
Accuracy as per IEC 62053-21,IEC62053-23.
Parameter Screen recall:
THD Measurement: In case of power failure, the instrument memorizes
The instrument measures THD per phase voltage & the last displayed screen.
current up to 15th Harmonic.
Run Hour, ON Hour, Number of Interruptions:
Onsite programmable: Run Hour records the number of hours load is
Onsite Programmable System Configuration 3PH4W connected. ON Hour is the period for which the
/ 3PH3W / 1PH2W. auxiliary supply is ON. Number of Interruptions
Onsite Programmable CT ratios and PT ratios indicates the number of times the Auxiliary Supply
was interrupted.
Direct remote access(Optional):
Remote configuration of the Instrument via Onsite selection of Auto scroll / Fixed Screen
MODBUS. User can set the display in auto scrolling mode or
Remote access of measured parameters. fixed screen mode locally via front panel keys by
Programmable baud rates up to 38.4kbps. entering into Programming mode or remotely via
MODBUS (Rs485).
Limit (Alarm) or Pulse Relay Output(Optional):
Potential free, very fast acting relay contact. Enclosure Protection for dust and water:
Configurable as pulse output which can be used to Conforms to IP 50 (front face) as per IEC60529
drive an external counter for energy measurement.
Configurable as limit (alarm) switch. Compliance to International Safety standards
Compliance to International Safety standard
Low back depth: IEC 61010-1- 2010
The instrument has very low back depth (behind the EMC Compatibility
panel) of less than 35 mm. Compliance to International standard IEC 61326

Measure Control Record Analyze

Page No.: 1 Version No.: B 06/2020


Data Sheet
RISH EM 1340 / 30 / 20

Technical Specifications:
Dimensions Details: Input Voltage:
Nominal input voltage (AC RMS) 100 VL-L to 500 VL-L (57.7 VL-N to 290 VL-N)
96 mm
System PT primary values 100VLL to 1200kVLL programmable on site.
Max continuous input voltage 120% of nominal value
Input Current:
Nominal input current 1A/5A AC RMS
System CT primary values From 1A to 9999A
96mm

Display Area Max continuous input current 120% of nominal value


Overload Indication “-OL-” >121% of Nominal value
(for voltage and current)
Auxiliary Supply:
External Higher Aux 60 V – 300V AC/DC (± 5% approx)
Front View Higher Aux Nominal Value 230 V AC/DC 50/60 Hz for AC Aux
OR
External Lower Aux 20V – 60 V DC / 20V – 40 V AC
Lower Aux Nominal Value 48 V DC / 24 V AC 50/60 Hz for AC Aux
Aux Supply frequency 45 to 65 Hz range
VA Burden:
27 mm
Nominal input voltage burden < 0.3 VA approx. per phase
Nominal input current burden < 0.3 VA approx. per phase
Auxiliary Supply burden
With Addon card < 6VA approx.
Without Addon card < 4VA approx.
Operating Measuring Ranges:
Current (Energy Measurement) Starting current : 2mA for 1A & 10mA for 5A
(As per IEC 62053-21) Range: 20mA to 1.2A for 1A
100mA to 6A for 5A
Voltage 50... 120% of nominal value
6 mm Power Factor 0.5 Lag ... 1... 0.8 Lead
35 mm Frequency 50Hz / 60Hz
Total Harmonic Distortion 0......50%
Side View
Accuracy :
Reference Conditions 23°C +/- 2°C
(As per IEC 62053 - 21)
Active Energy Class 1 as per IEC 62053 - 21
92mm+0.8
Reactive Energy Class 2 as per IEC 62053 - 23
Apparent Energy Class 1
Active Power ±0.5% of nominal value at cos ø = 1
Re-Active Power ±1.0% of nominal value at sin ø = 1
92mm+0.8

Apparent Power ±0.5% of nominal value


Power Factor/Phase Angle ±3°
Voltage ±0.5% of nominal value
Current ±0.5% of nominal value
Frequency ± 0.2% of mid frequency
THD (Voltage / Current) ± 2.0%
Panel Cutout

Measure Control Record Analyze

Page No.: 2 Version No.: B 06/2020


Data Sheet
RISH EM 1340 / 30 / 20

Technical Specifications:
Installation:
Overload Withstand:
Voltage 2 x rated value for 1 second, repeated 10 times
at 10 second intervals
Current 20x Imax for 0.5sec
Display update rate:
Easy Clip - in
mounting
Response time to step input 1 sec approx.
Applicable Standards:
EMC IEC 61326 - 1 : 2005
Immunity IEC 61000-4-3. 10V/m min – Level 3 industrial
Swivel screw
Low level
Safety IEC 61010-1-2010 , Permanently connected use
IP for water & dust IEC60529
Pollution degree: 2
Installation category: III
Isolation:
Protective Class 2
High Voltage Test
Input+Aux Vs Surface 4kV RMS, 50Hz,1min
Input Vs Remaining Circuit 2kV RMS,50Hz,1min
Environmental:
Operating temperature -10 to +55°C
Optional Modbus/Pulse output pluggable module.
Storage temperature -20 to +65°C
Relative humidity 0... 90%RH (non condensing)
Electrical Connection: Warm up time Minimum 3 minute
Shock (As per IEC60068-2-27) Half sine wave,Peak acceleration
2 5 8 11 1 3 4 6 7 9 13 14
30gn (300 m/s^2),duration 18ms.
Vibration 10... 150...10 Hz, 0.15mm amplitude
L N Number of Sweep cycles 10 per axis
S1

L1
P1 S1
AUX SUPPLY
L Enclosure IP 50 (front face only)
L2 O
L3
P1 S1
P1
A Interfaces:
N D
Impulse Led For Energy Calibration at front
3 Phase 4 wire Unbalanced load
Relay(Optional) 240 VAC ,5 A(Configured as limit or pulse output)
2 5 8 1 3 7 9 13 14 Modbus (Optional) RS485,max.1200m
Baud rate : 4.8k,9.6k,19.2k,38.4k bps
NOTE: Variation due to influence Quantity is 100% of class index for all other
S1
L N parameters except Energy.
AUX SUPPLY
L1 L
L2
P1
S1
O Input connections are made directly to screw-type terminals with indirect wire pressure.
L3 A Numbering is clearly marked on the connector . Choice of cable should meet local regulations.
P1 D
Terminal for both Current and Voltage inputs will accept up to 4mm2 (12AWG) solid or 2.5 mm2
3 Phase 3 wire Unbalanced load standard cable.

2 11 1 3 13 14 Note: It is recommended to use wire with lug for connection with meter.

S1 L N
P1 AUX SUPPLY L
L1
O
A
N D
1 Phase 2 Wire

Measure Control Record Analyze

Page No.: 3 Version No.: B 06/2020


Data Sheet
RISH EM 1340 / 30 / 20

Measured Parameter System wise:  : Available  : Not Available

Sr No Displayed Parameters 3 Phase 4Wire 3Phase 3Wire 1Phase 2Wire


1. Import Active Energy ( kWh)   
2. Export Active Energy ( kWh)   
3. Inductive Reactive Energy (kVArh)   
4. Capacitive Reactive Energy (kVArh)   
5. Apparent Energy (kVAh)   
 6. System Active Power (kW)   
7. Active Power L1 (kW)   
8. Active Power L2 (kW)   
9. Active Power L3 (kW)   
10. System Re-active Power (kVAr)   
11. Re-active Power L1 (kVAr)   
12. Re-active Power L2 (kVAr)   
13. Re-active Power L3 (kVAr)   
14. System Apparent Power (kVA) 
15. Apparent Power L1 (kVA)   
16. Apparent Power L2 (kVA)   
17. Apparent Power L3 (kVA)   
18. System Power Factor   
19. Power Factor L1   
20. Power Factor L2   
21. Power Factor L3   
22. System Phase Angle   
23. Phase Angle L1   
24. Phase Angle L2   
25. Phase Angle L3   
26. Current Demand   
27. kVA Demand   
28. Import kW Demand   
29. Export kW Demand   
30. Max Current Demand   
31. Max kVA Demand   
32. Max Import kW Demand   
33. Max Export kW Demand   
34. Run Hour   
35. On Hour   
36. Number of Interruptions   
37. System Voltage   
38. Voltage L1   
39. Voltage L2   
40. Voltage L3   
41. Voltage L12   
42. Voltage L23   
43. Voltage L31   
44. System Voltage THD   
45. Voltage L1 THD   
46. Voltage L2 THD   
47. Voltage L3 THD   

Measure Control Record Analyze

Page No.: 4 Version No.: B 06/2020


Data Sheet
RISH EM 1340 / 30 / 20

Measured Parameter System wise:  : Available  : Not Available

Sr No Displayed Parameters 3 Phase 4Wire 3Phase 3Wire 1Phase 2Wire


48. System Current   
49. Current L1   
50. Current L2   
51. Current L3   
52. System Current THD   
53. Current L1 THD   
54. Current L2 THD   
55. Current L3 THD   
56. Neutral Current   
57. Frequency   
58. RPM   
59. Phase Reversal Indication   
60. Current Reversal Indication   
61. Phase Absent Indication   
62. Old Import Active Energy ( kWh)   
63. Old Export Active Energy ( kWh)   
64. Old Inductive Reactive Energy (kVArh)   
65. Old Capacitive Reactive Energy (kVArh)   
66. Old Apparent Energy (kVAh)   
67. Old Run Hour   
68. Old On Hour   
69. Old Number of Interruptions   

Measured Parameter Model wise:


Sr. No Parameters EM 1320 EM 1330 EM 1340
On 
Display On Modbus On 
Display On 
Modbus On 
Display On Modbus

1. Import Active Energy ( kWh)      
2. Export Active Energy ( kWh)      
3. Inductive Reactive Energy (kVArh)      
4. Capacitive Reactive Energy (kVArh)      
5. Apparent Energy (kVAh)      
 6. System Active Power (kW)      
7. Active Power L1 (kW)      
8. Active Power L2 (kW)      
9. Active Power L3 (kW)      
10. System Re-active Power (kVAr)      
11. Re-active Power L1 (kVAr)      
12. Re-active Power L2 (kVAr)      
13. Re-active Power L3 (kVAr)      
14. System Apparent Power (kVA)      
15. Apparent Power L1 (kVA)      
16. Apparent Power L2 (kVA)      
17. Apparent Power L3 (kVA)      
18. System Power Factor      
19. Power Factor L1      
20. Power Factor L2      
21. Power Factor L3      

Measure Control Record Analyze

Page No.: 5 Version No.: B 06/2020


Data Sheet
RISH EM 1340 / 30 / 20

Measured Parameter Model wise:  : Available  : Not Available

Sr. No Parameters EM 1320 EM 1330 EM 1340


On 
Display On Modbus
 On Display
 On Modbus
 On Display
 On Modbus

22. System Phase Angle      
23. Phase Angle L1      
24. Phase Angle L2      
25. Phase Angle L3      
26. Current Demand      
27. kVA Demand      
28. Import kW Demand      
29. Export kW Demand      
30. Max Current Demand      
31. Max kVA Demand      
32. Max Import kW Demand      
33. Max Export kW Demand      
34. Run Hour      
35. On Hour      
36. Number of Interruptions      
37. System Voltage      
38. Voltage L1      
39. Voltage L2      
40. Voltage L3      
41. Voltage L12      
42. Voltage L23      
43. Voltage L31      
44. System Voltage THD      
45. Voltage L1 THD      
46. Voltage L2 THD      
47. Voltage L3 THD      
48. System Current      
49. Current L1      
50. Current L2      
51. Current L3      
52. System Current THD      
53. Current L1 THD      
54. Current L2 THD      
55. Current L3 THD      
56. Neutral Current      
57. Frequency      
58. RPM      
59. Phase Reversal Indication      
60. Current Reversal Indication      
61. Phase Absent Indication      
62. Old Import Active Energy ( kWh)      
63. Old Export Active Energy ( kWh)      
64. Old Inductive Reactive Energy (kVArh)      
65. Old Capacitive Reactive Energy (kVArh)      
66. Old Apparent Energy (kVAh)      
67. Old Run Hour      
68. Old On Hour      
69. Old Number of Interruptions      

Measure Control Record Analyze

Page No.: 6 Version No.: B 06/2020


Data Sheet
RISH EM 1340 / 30 / 20

Ordering Information:
Ordering Code
Ordering information RISH EM 1320/30/40
Model
EM 1320 1320
EM 1330 1330
EM 1340 1340

System Type (Connection network)


3 Phase (onsite programmable to 3PH4W,3PH3W and 1PH2W) 3
1 Phase 1

Auxiliary Supply Voltage


60 - 300 V AC DC EA
20 - 60 V DC / 20 - 40 V AC LA

Optional:
MODBUS (RS485) output R
MODBUS Option not used Z
GSM (No Pulse/Limit Output) G

Optional: Pulse/Limit Output


With 1 Pulse/Limit output P1
With 2 Pulse/Limit output P2
Without Pulse/Limit output NP

Note:- 1.For Three Phase, input voltage is 100- 500 VLL (Onsite programmable) and For Single Phase, input voltage is
57.7- 290 VLN (Onsite programmable)
2.Input Current is 5 Amps / 1 Amps (Onsite Programmable)

Order Code Examples:


1.RISH EM 1340 – 3 - EA - R - P2
RISH Energy Meter 1340, three Phase, 100- 500 VLL input voltage, 5 Amps / 1 Amps, external aux (60V – 300V AC/DC),
with MODBUS output, with two Pulse/Limit Outputs.

2.RISH EM 1330 – 1 – LA - Z - P1
RISH Energy Meter 1330, Single Phase, 57.7 - 290 VLN input voltage, 5 Amps / 1 Amps, external aux (20V – 60V DC /
20V – 40V AC ), with Pulse/Limit Output.

Measure Control Record Analyze

Page No.: 7 Version No.: B 06/2020


Measure Control Record Analyze