Chapter 2 CAPS PDF
Chapter 2 CAPS PDF
Chapter 2 CAPS PDF
CHAPTER-2
LOAD FLOW ANALYSIS
2.1 Introduction:
Load Flow or Power Flow is the solution for the Power System under static conditions of
operation. Load Flow studies are undertaken to determine:
1. The line flows
2. The bus voltages and system voltage profile
3. The effect of changes in circuit configuration, and incorporating new circuits on system
loading
4. The effect of temporary loss of transmission capacity and (or) generation on system loading
and accompanied effects
5. The effect of in-phase and quadrature boost voltages on system loading.
6. Economic system operation
7. system transmission loss minimization
8. Transformer tap settings for economic operation and
9. Possible improvements to an existing system by change of conductor sizes and system
voltages.
For the purpose of load flow studies, a single phase representation of the power network is used
since the system is generally balanced. When systems had not grown to the present size,
networks were simulated on network analyzers for power flow studies. These analyzers are of
analogue type, scaled down miniature models of power systems with resistances, reactance’s,
capacitances, autotransformers, transformers, loads, and generators. The generators are just
supply sources operating at a much higher frequency than 50Hz to limit the size of the
components. The loads are represented by constant impedances. Meters are provided on the
panel board for measuring voltages, currents, and powers. The load flow solution is obtained
directly from measurements for any system simulated on the analyzer.
With the advent of the modern digital computer possessing large storage and high speed, the
mode of load flow studies have changed from analog to digital simulation. A large number of
algorithms are developed for digital power flow solutions. Some of the generally used methods
are described in this chapter. The methods basically distinguish between themselves in the rate of
convergence, storage requirement and time of computation. The loads are generally represented
by constant power.
In the network at each bus or node there are four variables viz.
(i) Voltage magnitude
1
Prepared by Dr. c v v pavani
Computer Applications in power systems
2
Prepared by Dr. c v v pavani
Computer Applications in power systems
• Node voltages are available directly from the solution, and branch currents are easily calculated.
• Off-nominal transformer taps can easily be represented.
The power system will be considered as a balanced system in which the transmission lines and
loads are balanced (the impedances are equal in all the three phases) and the generator produces
balanced three phase voltages (magnitudes are equal in all the 3 phases while the angular
difference between any two phases is 120 degree). For the purpose of load flow studies, a single
phase representation of the power network is used since the system is generally balanced
Basically, an AC transmission system consists of
i) Synchronous generator
ii) Transformers
iii) Transmission lines and
iv) Loads
We will look into the network models of synchronous generators, Transformers, Transmission
lines and loads.
Interconnection of two or more power system components (Generators, Transformers,
Transmission lines and loads) is called bus.
Transformer Model
For power system steady-state and fault studies, generally the exciting current of the transformer
is neglected as it is quite low compared to the normal load current flowing through the
transformer. Therefore, a two winding transformer connected between buses ‘i’ and ']' is
represented by its per unit leakage impedance as shown in figure below
Loads
Loads can be classified into three categories; i) constant power, ii) constant impedance and iii)
constant current. However, within the normal operating range of the voltage almost all the loads
behave as constant power loads.
As the objective of the AC power flow analysis is to compute the normal steady-state values of
the bus voltages, the loads are always represented as constant power loads. Hence, at any bus 'k'
(say), the real and reactive power loads are specified as 100 MW and 50 MVAR (say)
respectively.
3
Prepared by Dr. c v v pavani
Computer Applications in power systems
4
Prepared by Dr. c v v pavani
Computer Applications in power systems
Let the nodes in the network be numbered 0,1,...,«, where 0 designates the reference node
(ground). By Kirchhoff's current law, the injected current /k must be equal to the sum of the
currents leaving node k, hence
If this equation is written for all the nodes except the reference, i.e. for all bus bar in the case of a
power system network, then a complete set of equations defining the network is obtained in
matrix form as
5
Prepared by Dr. c v v pavani
Computer Applications in power systems
The nodal admittance matrix in equations (2.3.4) or (2.3.5) has a well-defined structure, which
makes it easy to construct automatically. Its properties are as follows.
• Square of order n x n.
• Symmetrical, since Yki = Yik.
• Complex.
• Each off-diagonal element Yki is the negative of the branch admittance between nodes k and i,
and is frequently of value zero.
• Each diagonal element Ykk is the sum of the admittance of the branches which terminate on
node k, including branches to ground.
• Because in all but the smallest practical networks very few nonzero mutual admittances exist,
matrix Y is highly sparse.
6
Prepared by Dr. c v v pavani
Computer Applications in power systems
It is observed here, that the generators are specified in 3-phase MVA, L-L voltage and per phase
Y-equivalent impedance, transformers are specified in 3-phase MVA, L-L voltage
7
Prepared by Dr. c v v pavani
Computer Applications in power systems
transformation ratio and per phase Y-equivalent impedance on any one side and the loads are
specified in 3-phase MW, L-L voltage and power factor.
2.5 Impedance Diagram:
The impedance diagram on single-phase basis for use under balanced conditions can be easily
drawn from the SLD. The following assumptions are made in obtaining the impedance diagrams.
Assumptions:
1. The single phase transformer equivalents are shown as ideals with impedances on appropriate
side (LV/HV).
2. The magnetizing reactance’s of transformers are negligible.
3. The generators are represented as constant voltage sources win! series resistance or reactance,
4. The transmission lines are approximated by their equivalent ^-Models,
5. The loads are assumed to be passive and are represented by a series branch of resistance or
reactance and
6. Since the balanced conditions are assumed, the neutral grounding impedances do not appear
in the impedance diagram.
Example system
As per the list of assumptions as above and with reference to the system, of figure 2, the
impedance diagram can be obtained as shown in figure 3.
8
Prepared by Dr. c v v pavani
Computer Applications in power systems
> The resistance is often omitted during the fault analysis. This causes a very* negligible error
since, resistances are negligible
> Loads are Omitted
> Transmission line capacitances are ineffective &
> Magnetizing currents of transformers are neglected.
Example system
As per the assumptions given above and with reference to the system of figure 2 and figure 3, the
reactance diagram can be obtained as shown in figure 4.
9
Prepared by Dr. c v v pavani
Computer Applications in power systems
presence of the transformers! are then related to the chosen one by the turns-ratio of the
connecting transformer.
If Ib is the base current in kilo amperes and Vb. the base voltage in kilovolts, then the base MVA
is, Sb = (VbIb). Then the base values of current & impedance are given by
On the other hand die change of base can also be done by first converting the given pu
impedance to its ohmic value and then calculating its pu value on the new set of base values.
Merits and Demerits of pu System
Following are the advantages and disadvantages of adopting the pu system of computations in
electric power systems:
Merits:
> The pu value is the same for both 1 -phase and & 3-phase systems
> The pu value once expressed on a proper base, will be the same when refereed to either side
of the transformer. Thus the presence of transformer is totally eliminated.
> The variation of values is in a smaller range 9nearby unity)- Hence the errors involved in pu
computations are very less.
> Usually the nameplate ratings will be marked in pu on the base of the name plate ratings, etc.
De Merits:
> If proper bases are not chosen, then the resulting pu values may be highly absurd (such as 5.8
pu. -18.9 pu. etc.). This may cause confusion to the user. However, this problem can be avoided
10
Prepared by Dr. c v v pavani
Computer Applications in power systems
by selecting the base MVA near the high-rated equipment and a convenient base KV in any
section of the system.
Per Unit Impedance/ Reactance Diagram:
For a given power system with all its data with regard to the generators, transformers,
transmission lines, loads, etc.. it is possible to obtain the corresponding impedance or reactance
diagram as explained above. If the parametric values are shown in pu on the properly selected
base values of the system, then the diagram is referred as the per unit impedance or reactance
diagram. In forming a pu diagram, the following are the procedural steps involved:
1. Obtain the one line diagram based on the given data
2. Choose a common base MVA for the system
3. Choose a base KV in any one section (Sections formed by transformers)
4. Find the base KV of all the sections present
5. Find pu values of all the parameters: R.X, Z, E, etc.
6. Draw the pu impedance reactance diagram.
2.8 Formation of YBUS and ZBUS
The performance equations of a given power system can be considered in three different frames
of reference as discussed below:
Frames of Reference:
Bus Frame of Reference: There are b independent equations (b = no. of buses) relating the bus
vectors of currents and voltages through the bus impedance matrix and bus admittance matrix:
Loop Frame of Reference: There are b independent equations (b = no. of branches of a selected
Tree sub-graph of the system Graph) relating the branch vectors of currents and voltages through
the branch impedance matrix and branch admittance matrix:
11
Prepared by Dr. c v v pavani
Computer Applications in power systems
These are the performance equations of the given network in admittance form and they can be
represented in matrix form as:
12
Prepared by Dr. c v v pavani
Computer Applications in power systems
13
Prepared by Dr. c v v pavani
Computer Applications in power systems
Equations (18) and (19) are known as the basic load flow equations. It can be seen that for any ith
bus, there are two equations. Therefore, for a 'n'-bus power system, there are altogether '2n' load-
flow equations.
Now, from equations (18) and (19) it can be seen that there are four unknown variables (Vi, δi, Pi,
and Qi) associated with the ith bus. Thus for the 'n'-bus system, there are a total of '4n' variables.
As there are only '2n' equations available, out of these '4n' variables, '2n' quantities need to be
specified and remaining '2n' quantities are solved from the '2n' load-flow equations. As '2n'
variables are to be specified in a 'n' bus system, for each bus, two quantities need to be specified.
For this purpose, the buses in a system are classified into three categories and in each category;
two different quantities are specified as described below.
14
Prepared by Dr. c v v pavani
Computer Applications in power systems
PQ Bus: At these buses loads are connected and therefore, these buses are also termed as load
buses. Generally the values of loads (real and reactive) connected at these buses are known and
hence, at these buses Pi and Qi are specified (or known). Consequently, Vi and θi need to be
calculated for these buses
PV Bus: Physically, these buses are the generator buses. Generally, the real power supplied by
the generator is known (as we say that the generation is supplying 100 MW) and also, the
magnitude of the terminal voltage of the generator is maintained constant at a pre-specified value
by the exciter (provided that the reactive power supplied or absorbed by the generator is within
the limits). Thus, at a PV bus, Pi and Vi are specified and consequently, Qi and θi need to be
calculated, these buses are also termed as voltage controlled buses
Slack Bus: To calculate the angles θi (as discussed above), a reference angle (θi = 0) needs to be
specified so that all the other bus voltage angles are calculated with respect to this reference
angle. For this generator, Vi and θi(= 0) are specified and the quantities Pi and Qi are calculated.
Basic Power flow Equations (18) and (19) represent a set of simultaneous, non-linear, algebraic
equations. As the set of equations is non-linear, no closed form, analytical solution for these
equations exist. Hence, these equations can only be solved by using suitable numerical iterative
techniques. For solving the load flow problem, various iterative methods exist. These are:
1. Gauss-Seidel method
2. Newton Raphson (polar coordinate) technique
3. Newton Raphson (rectangular coordinate) technique
4. Fast-decoupled load flow
2.10 Newton Raphson (polar coordinate) technique
Newton Raphson method is more efficient and practical for large power system. Main advantage
of this method is that the number of iterations required to obtain the solution is Independent of
the size of the system and computationally is very fast
The above basic load flow equations constitute a set of Non-linear algebraic equations. In terms
of independent variables, voltage magnitude in per unit and phase angle in radians. There will be
two equations (Pi and Qi equation) for each load bus(PQ Bus) and one equation for PV bus.
Initially we assume a flat voltage profile i.e magnitude of Vi=1 and δi=0 for all PQ buses
15
Prepared by Dr. c v v pavani
Computer Applications in power systems
16
Prepared by Dr. c v v pavani
Computer Applications in power systems
17
Prepared by Dr. c v v pavani
Computer Applications in power systems
18
Prepared by Dr. c v v pavani
Computer Applications in power systems
• Real power changes are less sensitive to voltage magnitude changes and are most sensitive to
changes in phase angle Δδ.
•Similarly, reactive power changes are less sensitive to changes in angle and are mainly
dependent on changes in voltage magnitude.
•Therefore the Jacobian matrix in Eqn.(21) can be written as
19
Prepared by Dr. c v v pavani
Computer Applications in power systems
20
Prepared by Dr. c v v pavani
Computer Applications in power systems
21
Prepared by Dr. c v v pavani