Data Sheet For Chilled Water Pump (Primary) For Air Cooled Chiller
Data Sheet For Chilled Water Pump (Primary) For Air Cooled Chiller
Data Sheet For Chilled Water Pump (Primary) For Air Cooled Chiller
1
Delhi Metro Contract Mott MacDonaldAir Cooled Chiller Station ECS
CEDD 3, Phase-IIIContract CE 10 Pumps, common for all stations Data Sheet
and CE-11
Motor
Type TEFC Induction Motor ( IP – 55 ), EFF-1
Design As Per IEC 34 – 1, IEC 72 – 1, BS – 4999
RPM 1450 (Max)
Power Supply Three Phase, 415 V, 50 Hz, AC Power Supply
Vibration Isolation Inertia Base, Spring Isolation
Mounting Arrangement Suitable Base Frame For Floor Mounting
Lifting Arrangement Lifting Eye At Suitable Location And Number
Paint Epoxy Paint, After Surface Treatment For Corrosion
Notes
1. Pumps shall be provided with common base frame, inertia base, spring vibration isolation pads,
suction & discharge pressure gauges with isolation valves, test and / or air vent cocks, gland drain
& other accessories as required.
2. Pumps starters shall be star delta air break type
3. Pump head given is approximate and vendor shall do their own calculations and offer the pumps
accordingly.
4. Pump motor shall be EFF-1, non overloading up to out off conditions riding over complete curve.