Oxidation Stability of Insulating Fluids
Oxidation Stability of Insulating Fluids
Oxidation Stability of Insulating Fluids
Working Group
D1.30
February 2013
OXIDATION
STABILITY OF
INSULATING FLUIDS
WG D1.30
Members
“Ownership of a CIGRE publication, whether on paper or in an electronic format only infers right of
use for personal purposes. Prohibited, except if explicitly agreed by CIGRE, is the total or partial
reproduction of the publication for use other than personal and transfer to a third party; hence
publication on any intranet or other company network is forbidden”.
Disclaimer notice
“CIGRE gives no warranty or assurance about the contents of this publication, nor does it accept
any responsibility, as to the accuracy or completeness of the information. All implied warranties and
conditions are excluded to the maximum extent permitted by law”.
ISBN : 978-2-85873-219-7
Oxidation Stability of Insulating Fluids
Page 2
Oxidation Stability of Insulating Fluids
Page 3
Oxidation Stability of Insulating Fluids
It is well known that any insulating liquid serves four main functions:
The long term stability of insulating fluids is a result of their thermal endurance, hydrolytic and oxidation stability, as
well as compatibility with other transformer materials (e. g. copper, cellulose, insulating varnish, etc.). A low intrinsic
gassing behavior is usually desired to guarantee a low background level for reliable detection of failures through
dissolved gas analysis (DGA). Last but not least there are growing interests for requirements for challenging
applications, such as fire resistance or environmental risks.
Material specifications for transformers are designed to reflect the transformer operating environment. Often,
however, there is a need for simplifying testing procedures to get quick results. In such cases attention should be
paid to whether such methods are still able to reliably reflect the transformers operating environment and stresses.
For high operational stresses, the strictest requirements for insulating fluids, especially mineral oils and esters can
hardly be achieved without the addition of additive packages. It is unrealistic to compare the oxidation stability of an
uninhibited with that of an inhibited oil.
The present test methods for oxidation stability take the different oxidation behavior of uninhibited and of inhibited
oils into consideration by differences in the testing time. A disadvantage of some of these methods is that the
ageing is carried out to the breakdown stage – with development of acidity and sludge.
An alternative approach is to identify the sludge-free and acid-free time for an oil, also in consideration of different
temperatures and major transformer materials. It seems likely that in the future one must also consider preventive
measures that help to maintain the safety margins and protect the solid-liquid insulation in transformers.
Combination of both methods could help fulfill specific requirements for challenging operational conditions.
Page 4
Oxidation Stability of Insulating Fluids
However, not all applications ultimately need the strictest requirement for oxidation stability. The existing practices
and experience using either free-breathing equipment or alternatively equipment with a reduced oxygen content
must be reviewed.
Oxidation stability is an important characteristic of an insulation fluid. In the case of mineral oils uncontrolled
oxidation may lead to the formation of polar oxidation products, depositing on paper and changing its dielectric
properties (Fig. 1). Sludge formation can lead to plugging up of cooling channels and changing the thermal design.
The functionality of mechanical components like Buchholz relays may be jeopardized (Fig. 2). Oxidation may be
accompanied with a strong increase of the dissipation factor and a decrease of resistivity, which can be critical in
the case of electrical equipment with a small oil volume, such as instrument transformers or bushings. Dielectric
instability of oil in current transformers has been reported [1]. Strongly oxidized oil with a high conductivity may also
have an influence on the diagnostic criteria of a transformer as a whole, e.g. on the measured insulation resistance.
A certain oxidation stability is necessary even in “closed type” transformers, since air is always present, even in low
amounts. Furthermore, there is never a life long guarantee that hermetic conservation systems, membranes or
rubber bags will perform properly. Advanced oxidation of a natural ester liquid change the viscosity characteristics
and in extreme cases may lead to sticky insoluble deposits.
Oxidation stability is one of the most important characteristics of insulation fluids. It is a part of the requirements for
consistency and stability.
The first publication in 1923 of BS148, which was the standard for unused insulating oils for use in transformers in
the United Kingdom for many years, includes an oxidation test. By today’s standard it was not onerous because it
only considered sludge production; the level of acidity during the test was not included until a later revision (in
1951) and the new oil itself had very relaxed requirement for acidity at 2.0mg KOH/g. The second revision of the
same standard in 1933 used the sludge test to differentiate different grades of oils. Other specifications of the time
also had requirements of oxidation stability, for instance VDE 0370 in Germany talks about oxidation stability as a
tendency for ageing (Fig. 3).
Page 5
Oxidation Stability of Insulating Fluids
Advertising for transformer oils is reflected in the world literature, emphasizing, that the requirement for consistency
has always been primary for the user:
„What really counts, more than anything else, is the consistency of specifications in every grade, the characteristics
that indicate the merit of a given oil….Always the same! Always! Identical, any time and any place: from one
shipment to the next. The world can come to an end, the phoenix can rise from its ashes, the Coliseum can catch
fire, but…..transformer oil is what it is, and remains what it is!“
Carlo Emilio Gadda from "That Awful Mess on the Via Merulana", 1957
1.2 The Impact of Oxidation Stability on Transformer Insulation System and Functionality
The insulating fluid in a transformer has an insulating as well as a heat transfer function. Changes in dissipation
factor or viscosity will inevitably influence these characteristics. The influence of oxidation on insulating oil is
summarized in Fig. 4 [2, 3, 4, 5, 6]
Page 6
Oxidation Stability of Insulating Fluids
CAUSE EFFECT
OIL
OXIDATION Soluble organic acids, plus Oil thickening REDUCED
Soluble polymeric material OIL LIFE
Insoluble
Insolubleproducts
productsof
ofoil
oiloxidation
oxidationare are
aaprimary
primary cause of reducedoil
cause of reduced oillife
life
Example: 200 MVA transformer, after 30 years of service exhibited a neutralization value of 0.22 mgKOH/g oil,
interfacial tension of 14 mN/m and dissipation factor of 0.113 at 90°C. Heavy sludge deposits have been found on
the internal tank walls and on insulation parts (Fig. 5). The cooling ducts have been clogged with thick chloroform
insoluble material. Transformer operation has been jeopardized because of overheating, caused by accelerated oil
degradation.
Fig. 5 Insulation parts covered by thick sludge deposits caused by accelerated oil degradation
Page 7
Oxidation Stability of Insulating Fluids
The use of insulating fluid is based to a great extent on historical experience and on existing standards. In
many cases low oxidation stability has been experienced, but the problems do not seem to be very severe,
leading to an equipment failure.
Oil performance seems to be regarded as a whole and oxidation stability is only a part of it.
It seems to be a trend toward higher loading of transformers in the future (better utilization of existing
networks), as well as from non-inhibited to inhibited mineral oils.
1.4.1 PARTICIPANTS
25 utilities, 13 manufacturers, 4 consultants took part in the survey. The geographical distribution of the participants
is shown on Fig. 6.
Fig. 6 Geographical distribution of the participants in the survey (the points are related
symbolically to a country, but do not indicate a city).
Page 8
Oxidation Stability of Insulating Fluids
core type 29
shell type 10
no answer 14
generator transformers 21
shunt reactors 23
network transformers 28
industrial transformers 8
distribution transformers 21
traction transformers 5
Tap Changer 2
instrument transformers 17
Yes 12
No 12
Rarely 3
Sometimes 3
No answer 11
Page 9
Oxidation Stability of Insulating Fluids
Customer requirements, historical price considerations play an important role. Health and safety requirement, e.g.
lack of polychlorinated biphenyls (PCB) is also important.
inhibited 15
uninhibited 17
No answer 4
The application seems to play an important role for choosing an insulating liquid (15 answers). A large majority
uses naphthenic oils (21 answers), some users use both (napthenic and paraffinic) (8 answers). Some participants
answered that they use paraffinic at lower voltages and naphthenics at higher voltages. Concerns in case of
paraffinics are wax and availability.
IEC 60296 10
Brazilian 3
CSA Std 1
BS, IEC 1
Doble TOPs 1
IEC, Doble 1
Existing spec. 1
No answer 23
Page 10
Oxidation Stability of Insulating Fluids
Presumably the question has not only been referred to oil bulk, but also to max. allowed hot-spots.
The answers on the max. electrical stress also vary. There are mainly 2 groups of answers:
1:1–4
1.4.9 CONCLUSION
The use of insulating fluid is based to a great extent on historical experience and on existing standards. In many
cases low oxidation stability has been experienced, but the problems do not seem to be very severe, i.e., leading to
an equipment failure.
Oil performance seems to be regarded as a whole and oxidation stability is only a part of it.
There seems to be a trend toward higher loading of transformers in the future (better utilization of existing
networks) as well as to inhibited insulating oils. Alternative fluids are being regarded, but are still used only for
special applications.
Page 11
Oxidation Stability of Insulating Fluids
In order to understand the principles of insulating oil classification, a brief introduction in the refining methods is
necessary.
This process starts with fractionated distillation of the crude oil to separate fractions of different boiling range from
one another. Out of the different fractions (with different viscosities) a suitable one is selected (widely referred to as
light spindle oil). Sometimes the distillation residue is distilled under vacuum and the lightest of the vacuum
fractions is selected as a component for the production of insulating oil.
Depending on the source of crude oil, these distillates may be neutral or have a certain acidity and a high content
of aromatic compounds and heterogenic molecules.
In the early times of refining the first step of refining was a treatment with sulfuric acid to sulphonize the
polyaromatics respectively to reduce total aromatics as well as most heterogenes that normally bond to aromatic
molecules. All these extracted materials together with the acid employed form the so called acid goudron and were
separated by so called “agiteurs” (by difference of spec. gravity) or by centrifuges. The amount of separated
goudrons (acid + production losses) was waste material to be treated or disposed of, both of which is very
expensive.
The remaining low acidity of the refined oil was to be neutralized with lime or soda and the resulting product filtered
using clay. The decrease of total aromatics by this treatment was approx. 4-6%, the resulting final product (if
naphthenic) had a CA of 15-18%. Although this seems to be a high value, these oils had an acceptable oxidation
stability and met the standard requirements at the time (1930-1950)
Today acid/clay treatment is an obsolete refining process mainly due to the environmental impact of the waste
products and its disposal costs.
In the early 1950s the extraction technology (developed for lubricating oils) was introduced for the production of
insulating oils. The most used solvents were phenol and 2-furfural, which has a strongly selective solvent power to
aromatic molecules. Aromatics, but not with paraffinic or naphthenic structures are very soluble in 2-furfural and the
reduction of the aromatic content of the feedstock was remarkable, between 10 - 15%, depending on the 2-furfural-
ratio.
Combined with a final acid/clay treatment this refining procedure resulted in quite good insulating oils with high
oxidation stability and excellent electrical properties.
But a disadvantage of this process was expense, as the extracted by product, the so called “extract” had a low
economic value. For a time it was used as softeners in the rubber industry or for tire production.
Page 12
Oxidation Stability of Insulating Fluids
To avoid “acid goudrons” in the 1960s the hydrogenation technology was introduced for refining of insulating oils, in
the early days as a final treatment in combination with solvent extraction (so called “hydrofinishing” with hydrogen
pressure up to 40-50 bar).
With the development of specific catalysts and increasing pressure this technology has more and more replaced
the extraction process, especially in the use of naphthenic distillates (since the early 1980s). Many refiners have
completely changed to this high pressure hydrogenation, but there are still extracted/hydrofinished insulating oils
on the market.
The intensity of refining (and therefore quality of the final product) depends on hydrogen pressure, type of catalyst,
temperature and speed of the process. The higher the intensity (“degree of refining”) the stronger the reduction of
unwanted polyaromatics, aromatics and heterogenes and the higher therefore the thermal and oxidation stability of
the final product. But there is a certain point of intensity where the result of refining (seen as oxidation stability) is
an optimum. A further increase of refining intensity would reduce the aromatic content too much and reduce the
oxidation stability of an oil without synthetic axitioxidant (see Fig. 7)
Page 13
Oxidation Stability of Insulating Fluids
Some significant differences in physical and chemical properties are listed below:
Paraffinic structures have a high viscosity index, meaning the decrease of viscosity with increasing
temperature is low (important for engine/motor oils)
Paraffinic oils have a lower density than naphthenic oils (more volume for the same mass, this is an
advantage for the purchaser).
Paraffinic oils have a lower solubility for oxidation products and precipitate them earlier as sludge during
service life in a transformer.
Finally, they have a higher pour point than naphthenic structures/insulating oil (e.g. –10 to –20°C
depending on the degree of dewaxing) and sometimes need a pour point depressant additive.
According to IEC 60296 Ed.3/2003 they may be used in countries with mild/hot climates down to LCSET of –10°C
(therefore Pour Point –20°C) without use of PPD (Pour Point Depressants).
Some experiments show, that paraffinic oils exhibit higher acidity and sludge formation than naphthenics under
ageing conditions [4]. The classification into naphthenic or paraffinic may be misleading for the new hydrocracked
oil. In these oils, branched non-cyclic saturated hydrocarbons are dominant, and based on, for example carbon
distribution analysis, they would obviously be classified as paraffinic. They have the high viscosity index typical of
paraffinic oils, but the low temperature flow properties are more like those of naphthenic oils.
When formulating mineral insulating oil, there are two basic types (at least in theory). Either you are allowed to
make use of synthetic phenolic radical scavengers, or you are not. The former type of oil is referred to as
“inhibited”, the other “uninhibited”. Inhibited and uninhibited oils may behave in quite different ways. This is
because the inherent oxidation stability of the oil depends very much on the degree of refining, as was also
discussed above under the heading “Refining Methods” and chemistry of oil oxidation. This section contains some
repetition, but it is important to understand why the different types of oil behave in very different ways.
The more highly refined the oil, the less aromatics, polyaromatics and hetero-compounds (molecules containing
other atoms than carbon or hydrogen) that will be left. Some of these removable components are easily oxidized,
while others provide some protection against the normal oxidation process. Typically there is some kind of optimal
degree of refining with respect to oxidation stability that will yield an oil with fair oxidation stability without any
synthetic additives. The uninhibited oil starts to oxidize more or less from day one, albeit at a moderate rate, since
it contains a certain amount of so called natural antioxidants, some of them present from the beginning (mostly
sulfur-containing peroxide scavengers); others being formed by the oxidative processes (mostly radical scavengers
formed by oxidation of aromatic compounds).
However, if we look at how the oil behaves after the addition of synthetic radical scavengers, a totally different
picture will emerge. Typically the oxidation stability of oil with a phenolic antioxidant will improve as long as the
degree of refining increases. In an optimally formulated inhibited oil, based on highly or very highly refined base
oils, the oxidation rate is extremely slow as long as there is still some phenolic antioxidant left. Usually 0.25-0.40 %
of DBPC (di-tert-butyl-paracresol) is added at the refinery or blending plant. This is normally sufficient to suppress
the oxidation processes for many years. However, when such an oil runs out of antioxidant, the oxidation will
proceed at a significantly higher rate. Obviously one tries to avoid this situation by maintaining an appropriate
content of antioxidant.
Page 14
Oxidation Stability of Insulating Fluids
Real life is of course more complicated than the clear cut cases that we have in theory. A real product can be a
blend of oils with different degrees of refining. Synthetic antioxidants can be added also to originally “uninhibited”
oil, although the response to the inhibitor, in terms of the time during which the antioxidant efficiently suppresses
the oxidation, is normally poorer than for the oil that was from the beginning designed for use with inhibitor. Many
oils sold as inhibited are in fact basically of the uninhibited type, but with inhibitor added. This may be for logistic
reasons (it is simpler for a supplier to deal with very few base oils) or it is in some cases a kind of “belt-and-braces”
philosophy, where you want some of the benefits of both types of oil (the longer life of the inhibited oil, and the
more predictable ageing of the uninhibited oil). There is also an intermediate type, usually called “trace inhibited”,
with a small addition of synthetic antioxidant (up to 0.08%). Such oils can be of either basic type.
Normally the oxidation stability requirements put on the different types of oil differ significantly. Test times are
generally much shorter for uninhibited oil compared to inhibited, when the same test is used [IEC 60296].
In modern transformers strong partial discharges and therefore large quantities of gas formations should not occur,
as calculation of electrical fields, design and assembly processes have improved significantly and if there is a
partial discharge problem in a transformer in service, it is detected normally early enough by DGA to avoid a failure.
However some equipment design concepts may need compensation by gas-absorbing oils.
In extremely cold countries (Canada, Scandinavian countries, Russia) a very low LCSET of –40°C is required. To
ensure the lowest possible viscosity at –40°C, such oil generally has a lower viscosity than “standard grades”, e.g.
approximately 7 mm²/s at 40°C. A limit of viscosity is given by the required minimum flash point (135°C).
Page 15
Oxidation Stability of Insulating Fluids
Page 16
Oxidation Stability of Insulating Fluids
Mineral insulating oil consists mainly of a complex mixture of different types of hydrocarbon molecules (paraffins,
naphthenes and aromatics), i.e. molecules that are built from only two types of atoms; carbon and hydrogen.
Insulating fluids of the ester type (natural or synthetic) also contain oxygen functionalities, but the basic
mechanisms of hydrocarbon oxidation still holds (although kinetics may differ). Non-carbon based liquids like
silicone fluid does not behave according to these mechanisms.
The heart of the radical chain mechanism of oxidation of hydrocarbons is shown above (Fig. 8). The process starts
·
by (thermal) generation of a hydrocarbon radical R from a hydrocarbon molecule RH, by loss of a hydrogen atom
from the carbon backbone of the molecule. The dot symbolizes an unpaired valence electron, i.e. a radical.
Initiation (reaction I) is a rare event which only has to happen once to initiate the chain reaction. If oxygen is
·
present it will quickly react with the hydrocarbon radical to form a peroxy radical ROO . This is an example of a
propagation reaction as it generates a new radical species (P1). The peroxy radical can then go through two
different routes.
3.2.1 Route 1 (Fig. 9): A peroxy radical can abstract a hydrogen atom from another hydrocarbon molecule to
generate yet another hydrocarbon radical (reaction P2) and a hydroperoxide ROOH. This closes the cycle of the
chain reaction. In principle the reaction will continue in this manner as long as there is oxygen available. It is
therefore often referred to as autooxidation. The hydroperoxides that are generated in this process can react
further in a type of propagation reaction that generates two radical species per molecule. This is called branching,
and explains why the oxidation of hydrocarbons often accelerates (exponential growth of the number of active
radical species) after a period of induction.
Page 17
Oxidation Stability of Insulating Fluids
· ·
Through these reactions alkoxy radicals RO and hydroxyl radicals OH can be generated from hydroperoxides.
Both of these new radicals can react with hydrocarbon molecules to form new hydrocarbon radicals that will react
with oxygen according to the mechanism above and thus further increase the total reaction rate (consumption of
oxygen). In this process alkoxy radicals form alcohols (ROH) and hydroxyl radicals form water. This route to
oxidation products is catalyzed by metal cations such as those of iron and copper. They do so through a
mechanism where a metal cation of a lower oxidation state is oxidized by a hydroperoxide under formation of
radical species.
3.2.2 Route 2 (Fig. 10): The other route to oxidation products goes through termination (Reaction T) of the chain
reaction when two peroxy radicals react with each other. This type of reaction yields an alcohol, oxygen and an
aldehyde (or ketone depending on substitution pattern).
H
O
2 R O R
OH + O2 + R Aldehyde
O
Alcohol
O2
O
R Peracid
O OH
R + CO2 R
O RH
R
O
+ R
O OH
Carboxylate Carboxylic
radical acid
Aldehydes which have come about by this reaction of peroxy radicals can in turn be oxidized further to peracids
(via acyl radicals). Peracids in turn can form carboxylate radicals, which upon abstraction of hydrogen atoms give
carboxylic acids (and new hydrocarbon radicals which will partake in the oxidation chain reaction). This chemistry is
utilized industrially to produce formic acid from formaldehyde. Ketones behave in a similar fashion and can also
Page 18
Oxidation Stability of Insulating Fluids
give rise to esters when they react with peracids. Esters and water can also be formed by the (acid catalyzed)
reaction of alcohols and carboxylic acids.
Carboxylate radicals can alternatively form carbon dioxide (and new radicals) through a β-elimination process.
Carbon dioxide can also be formed by decarboxylation of carboxylic acids and carbon monoxide through radical
decarbonylation of aldehydes.
It is a well known fact that the viscosity of oils tend to increase on oxidation. There are at least two explanations for
this effect. The first is that physical interaction between molecules increase as a consequence of the molecules
becoming more polar as more and more oxygen functionalities and unsaturation are incorporated (hydrogen
bonding and polarization). The second explanation is that hydrocarbon radicals can react with other radicals (a
form of termination) to form larger molecules which generally give higher viscosity. Sludge (material not soluble in
oil) can be formed through various paths including acid catalyzed condensation reactions of keto compounds,
(radical) polymerization and salt formation. Under extreme conditions polyaromatics and pure carbon (soot) can
form as a result of oxidative processes and contribute to the non-soluble sludge content.
In the context of insulating oils it is also of course well known that oxidation gives rise to smaller molecules such as
water soluble acids and carbon dioxide. These smaller molecules come about by various elimination and
fragmentation reactions (not covered here). Since such molecules generally evaporate they do not compensate the
average molecular size, and thus viscosity increases.
So called hydroperoxide decomposers act by reducing hydroperoxides to alcohols, i.e. they inhibit Route 1 (above).
These types of compounds include various non-heterocyclic sulfur containing compounds that can be found in
mineral oils. Uninhibited insulating oils depend on such compounds for their oxidation stability. The illustration
(Fig. 11) shows how an organic sulfide is successively oxidized by hydroperoxides (which is reduced to the
corresponding alcohol) to first a sulfoxide and then a sulfone.
O O O
ROOH ROOH S
S S
R R -ROH R R -ROH R R
There are also so called chain breaking antioxidants which react with formed radicals and stabilize the resulting
radicals, i.e. they inhibit both Route 1 and 2 (above). The result is a much slower, or totally inhibited, oxidation
Page 19
Oxidation Stability of Insulating Fluids
process. This group of compounds include hindered phenols such as di-t-Butyl-p-Cresol (DBPC a.k.a. BHT), a
synthetic inhibitor that is commonly added to inhibited grades of insulating oils (Fig. 12).
Y
. .
X Y
OH O O
-XH
The hydrogen atom of the hydroxyl functionality of the phenol is first abstracted by a radical X. (which is then
terminated). This yields a highly stabilized phenolic radical which is much less prone to take part in any propagation
of the chain reactions of oxidation. A second radical Y. can subsequently be terminated by the phenolic radical.
Thus one molecule of DBPC can terminate (at least) two radicals, which can be of any type that occurs in the
overall oxidation chain mechanism. This explains the great efficiency of phenolic type inhibitors.
Both types of antioxidants are eventually consumed, but the time this takes depend on temperature and oxygen
availability as well as on chemical composition of the oil. It should also be noted that the efficiency of antioxidants is
temperature dependant. Since the antioxidant effect is a kinetic effect there is a temperature window in which each
type of antioxidant is active. In a broader context than insulating oils chain breaking antioxidants are often referred
to as primary antioxidants, whereas peroxide decomposers are referred to as secondary antioxidants. Intensive
studies on the byproducts of oxidation and their influence has been carried out [17] For ultimate oxidation stability
in products like engine oils and other lubricants it is customary to combine several specific antioxidant additives of
the two different types.
- High temperature
- Prooxidants
Chain Breaking Inhibitors (radical catchers) are mainly phenolic and aminic type anti-oxidants
Page 20
Oxidation Stability of Insulating Fluids
Examples are :
NH
R H
R'
N
2. Hydroperoxide decomposers
Compounds that react with hydroperoxides giving non-radical products. How? By being oxidized. They
are reducing agents. Most common are S or P species, e.g. DBDS (Dibenzyldisulfide)
The rate of oxidation of fatty compounds depends on the number of double bonds per molecule and their relative
location. The bis-allylic position in linoleic acid (Fig. 14) (double bonds at C-9 and C-12, giving one bisallylic
position at C-11) and linolenic acid (Fig. 15) (double bonds at C-9, C-12 and C-15, giving two bis-allylic positions at
C-11 and C-14) are even more prone to oxidation than allylic positions like in oleic acid (Fig. 13). Indeed the
relative rates of oxidation given in the literature are 1 for oleates (methyl, ethy esters) (18:1), 41 for linoleates (18:2)
and 98 for linolenates (18:3).
Small amounts of more highly unsaturated fatty compounds containing bis-allylic carbons have a disproportionately
strong effect on oxidative stability.
OH
Page 21
Oxidation Stability of Insulating Fluids
OH
O
Fig. 14 Linoleic acid (cis, cis-9,12-octadecadienoic acid)
OH
The Oil Stability Index (OSI) can be used for the assessment of oxidation stability of vegetable fluids. OSI is based
on determining the time (usually termed "induction time") before the maximum rate change of oxidation by
measuring the increase in conductivity of deionized water caused by dry air bubbled through a heated sample that
carries the resulting volatile acids into a separate container with the deionized water. The method is believed to
give semiquantitative predictions. It is similar to EN 14213, EN 14214.
Elemental copper, iron and nickel have a catalytic effect on the oxidation stability of fatty acids methyl esters,
where the catalytic activity of copper is the greatest, measured by the OSI method [19].
Fatty acids, that contain more poly-unsaturation, are more prone to oxidation. As linolic and linolenic acid content in
fatty oils or esters increases, the oxidation stability decreases and as fatty oils oxidize the hydroperoxide (ROOH)
levels also increase. Studies have indicated that the development of ROOH over time exhibits one of the two
behaviors: (i) ROOH levels can increase, achieve a plateau, and then be held at that level in a steady state and
alternatively (ii) ROOH can increase, achieve a peak level and then decrease, but no explanation is available on
such behavior. However, the factors like oxygen availability, temperature, extent of preexisting oxidation and the
presence of metals catalyzing the decomposition of hydroperoxides are likely involved in causing the primary
oxidation.
Page 22
Oxidation Stability of Insulating Fluids
Several parameters [20] are known to provide information on stability of vegetable fluids, such as:
Iodine value (IV): This is one of the oldest and most common methods to determine the magnitude of
unsaturation in fatty oil or ester. D1541 and D1959 are two available ASTM methods along ISO 3961 to
measure IV though it is not necessarily a good method for assessing the stability as the stability depends on the
position of the double bonds available for oxidation.
Peroxide value (ISO 3960): Peroxide value tends to increase and then decrease upon further oxidation due to
formation of secondary oxidation products.
Viscosity (ISO 3104): Viscosity has been found to increase with chain length and with increasing degree of
saturation. Free fatty acids also contribute to higher viscosity. Furthermore, double bond configuration also
influences the viscosity, i. e. cis doble bond configuration giving a lower viscosity than trans. Since oxidation
processes lead to the formation of free fatty acids, cis-trans isomerization, and the formation of high molecular
weight products, the viscosity increases with oxidation.
Steric hindered phenols like DBPC have an antioxidant activity on soybean oil [21].
In recent times [5] natural esters have been successfully adopted in power transformers up to 200 MVA and 242
kV. Applications at higher ratings are envisaged in the future.
Some further investigations [23, 24, 25] show that natural ester oils are less stable with respect to oxidation than
mineral oil. However, depending on the type and the presence or lack of inhibitor, the oxidation behavior of
vegetable oils can be very different.
Oxidation of certain natural esters influence diagnostic parameters of DGA, e. g. gassing. Ongoing oxidation
accelerates stray gassing, especially ethane production (Fig. 16), produced from poly unsaturated acids, e.g. -3
fatty acids [26, 27, 28, 29, 30, 31, 32] Hydrogen evolution may also be connected with the formation and
degradation of peroxides [32].
Page 23
Oxidation Stability of Insulating Fluids
700
600
500
[Ethane], ppm
400
200
100
Fig. 16 Development of Ethane under Thermal Stress (150°C) in Mineral Oil and in a Certain
Natural ester [31]
3.9.1 TEMPERATURE
As a rough approximation, the rate of reaction doubles for every 7 – 10 °C rise in temperature, because every
chemical reaction is thermally dependent on the Arhenius law.
From a recent study of power transformers (Australian experience) just under twenty years old the following
comparison can be made [33]:
- Free breathing (desiccant) conservator: 17180 ppm O2 (average of 14 units 110&132 kV)
Since any insulating oil will be more or less exposed to oxygen and heat it is obvious that oxidation stability will
have to remain a basic requirement of insulating oils.
Page 24
Oxidation Stability of Insulating Fluids
Generally speaking, the aromatic content of extracted oils is also higher than in hydrotreated oils due to saturation
of aromatics by hydrogen [35].
The fact that higher aromatic content generally increases inherent oxidation stability in mineral oils has been known
for a long time [36] and it is also generally known that in uninhibited oils there has to be a balance between
aromatics and sulfur compounds [37]. Especially the larger aromatic molecules affect the oxidation stability
because they form phenols on oxidation. There are however health and safety limitations to possible formulations
because of the demand for low content of polycyclic aromatic hydrocarbons (PCA).
Additives to reduce gassing tendency contain aromatic molecules, but it is hard to say anything general about the
effect on oxidation stability of such additives because it varies depending on type of molecule and on the
composition of the oil. Gas absorption is an important issue for cable and capacitor liquids.
In inhibited oils the story is very different. The more highly refined the oil is (lower sulfur and aromatic content), the
better the response to the added antioxidant [38]. This means that the oxidation stability of a more highly refined oil
will be better than that of a less highly refined oil given the same type and amount of antioxidant. Oxidation stability
expressed as induction time will also increase (up to a point) if the initial amount of antioxidant is increased in the
same oil. It is sometimes argued that since the intrinsic oxidation stability of a highly refined oil (suitable for
formulation of an inhibited oil) is much lower than that of an oil which is less highly refined (commonly used to make
uninhibited oil), it is safer to utilize uninhibited oils which possess an intrinsic oxidation stability. However, in any
case uninhibited oils do develop acidic compounds much earlier and faster than does an inhibited oil. This means
that the acid catalyzed breakdown of solid cellulose insulation will start earlier and shorten the lifetime of the
transformer.
Ester-based oils depend on added antioxidants for oxidation stability. Natural esters derived from plants usually
contain some amount of residues of unsaturated fatty acids (containing carbon-carbon double bonds). Although
these are beneficial to our health when ingested as food, it makes natural esters more prone to oxidation. In
synthetic esters this problem can be avoided as the constituent fatty acids chosen can be completely saturated.
Standards for laminated wood (IEC 61061) and laminated board (IEC 60763) describe compatibility procedures for
insulating oil.
3.9.5 METALS
Investigations on the influence of metals on the oxidation stability have been performed since the 1950s at different
transformer manufacturers [39]. In the transformer factory in Nuremberg, Germany, Baader ageing has been used
and as parameters the saponification value and the loss factor have been used. It has been found that the rate of
catalytic activity of the metals is:
Al:Fe:galvanized Fe:Zn:Cu
1:1:3:4:13
Paper insulation decreases the catalytic influence of copper. Copper varnishing eliminates completely its catalytic
activity (Fig. 17).
Page 25
Oxidation Stability of Insulating Fluids
Fig. 17
Oil appearance after Oil appearance after
ageing with varnished ageing with blank
copper (150°C, 48h) copper(150°C, 48h)
There is a fundamental connection between oil oxidation and metal corrosion. Products of oil oxidation such as
peroxides, acids and water, can corrode metals such as the copper (in windings) [40], iron (in the steel tank walls)
and silver (on tap changers). The metals that are dissolved in this fashion can then catalyze further oxidation,
leading to even more corrosion, and so on. For this reason metal passivators (such as BTA, TTA and similar
compounds) have a positive effect on the oxidation stability of insulating oils in the presence of metal surfaces [41].
It has been shown, that the addition of passivators enhances the oxidation stability of uninhibited mineral oils
significantly [42].
The mechanism of the catalytic effect of metals on oxidation has been discussed at length [43, 44]. The prevailing
theory seems to be catalytic decomposition of hydroperoxides to peroxy radicals by disproportioning of copper ions
[44].
Page 26
Oxidation Stability of Insulating Fluids
Some vegetable fluids show similar tendency of formation of hydrogen and ethane in service – see Chapter 2.
Oxidation affects gas-in-oil analysis. Oxygen depression is a result of oxidation processes and is always to be seen
in loaded transformers, especially with non-inhibited oils.
N2 – 66000 ppm
O2 – 33000 ppm
Actually dissolved oxygen is often very low, although the transformer is free breathing (Fig. 18) .
H2 Hydrogen 13
C2H6 Ethane 80
C2H4 Ethylene 14
C3H6 Propylene 60
O2 Oxygen 2825
N2 Nitrogen 76520
Page 27
Oxidation Stability of Insulating Fluids
4.2.1 COLOR
For unused new oils, color is generally considered as a rough estimation of the degree of refining and for oils in
service as a roughly index of its deterioration (oxidation). Color is not a defined characteristic, but reveals a lot
about the transformer oil condition. Inhibited oils in service have usually a lighter color than non-inhibited for the
same service time and transformer load (Fig. 19).
Transformer 1 Transformer 2
Non-inhibited oil Inhibited oil
Rating (kV) 420 425
Power (MVA) 780 970
Year of manufacture 1985 1973
Colour 4,5 2,5
Acidity(mg KOH/g oil) 0,12 <0,01
Lossfactor (90°C) 0,035 0,014
Interfacial tension 18 37
(mN/m)
Inhibitor content (%) - 0,17
Fig. 19 Transformers with similar rating and load, filled with uninhibited and inhibited oil.
4.2.2 SLUDGE
Strongly oxidized oil also deteriorates the solid insulation, since the major polar products absorb in paper (Fig. 20,
Fig. 21).
Page 28
Oxidation Stability of Insulating Fluids
Inhibited and non-inhibited mineral oils behave differently in respect of the loss factor increase with service time
(Fig. 22).
0.12
0.1
0.08
Lossfactor
non-inhibited
0.06
inhibited
0.04
0.02
0
0 5 10 15 20 25 30 35
Service Time (Years)
Fig. 22 Behavior of the loss factor increase with service time for non-inhibited and inhibited
mineral oils
Table 5 Results of oxidation stability tests acc. IEC 61125C for a mineral insulating oil
Requirement
Property Unit of IEC 60296
Value for standard grade
Page 29
Oxidation Stability of Insulating Fluids
There is no clear evidence on the relationship between oil behavior in service and the performance in the oxidation
stability tests. It has been demonstrated, however, that insulating oils which failed the test in IEC 61125C because
of high loss factor showed after short time of service (5 years) in free breathing distribution transformers an unusual
high loss factor and low interfacial tension (Table 5, Table 6).
On the other hand, it is known that high grade inhibited oils acc. to IEC 60296 perform well even after long years of
service.
There is a definitive correlation of loss factor with resistivity (Fig. 23) [48, 49] well known from Cigre publications;
therefore it is a question of analytical philosophy as to which parameter is to be determined.
Log[IRES] vs Log[DDF]
4
3.5
3
2.5
1.5
1 improving resistivity
0.5
0
-4 -3.5 -3 -2.5 -2 -1.5 -1 -0.5 -0.5 0 0.5
-1
Page 30
Oxidation Stability of Insulating Fluids
0.25
0.2
Acidity (mg KOH/g oil)
0.15
non inhibited
inhibited
0.1
0.05
0
0 5 10 15 20 25 30 35
Service Time (Years)
Fig. 24 Neutralization value increase with service time for non-inhibited and inhibited mineral
oils
High acidity will inevitably have an impact on paper degradation, therefore oil and paper ageing are closely related
[50, 51, 52]
The HV winding of this transformer was wrapped in 8 layers of paper and samples were taken from different points
of the transformer and the tensile index was measured. The results show that the chemical degradation of the outer
layer of paper, especially at the lower part of the HV winding, have as much effect on the tensile index as the
thermal degradation of the inner layer of paper at the top of the winding (Fig. 25, Fig. 26). The chemical
degradation is also confirmed by the presence of higher quantities of low molecular weight acids (LMAs) in the
outer layers of paper [52].
Page 31
Oxidation Stability of Insulating Fluids
A general scheme of behavior of uninhibited and inhibited insulating oils is shown in Fig. 27.
Page 32
Oxidation Stability of Insulating Fluids
45
40
35
Interfacial Tension mN/m
30
25
non-inhibited
inhibited
20
15
10
0
0 5 10 15 20 25 30 35
Service Time (Years)
There is also an interdependence between the different ageing parameters like interfacial tension (IFT) and acidity
(NN) (Fig. 28) [53].
50 0.5
40 0.4
NN (mg KOH/g)
IFT (mN/m)
30 0.3
NN
IFT
20 0.2
10 0.1
0 0
0 5 10 15 20
age (years)
Fig. 28 Interdependence between interfacial tension (IFT) and acidity (NN) [53]
Page 33
Oxidation Stability of Insulating Fluids
100
Breakdown voltage
80
60
40
20
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Acidity mgKOH/g
120
100
Breakdown voltage
80
60
40
20
0
0.1 1 10 100 1000 10000
Resisitvity Gohm‐1
Considering the above, it is evident how strategic and important the design of an efficient oil protection system is
that is able to stop or at least delay the negative effects of the direct contact with external atmosphere (oxygen and
moisture). The development of the oil protection system took place over a period of more than 50 years, at the
same time with research on the ageing of the insulating materials and ended around 1970 [54, 55]. Many different
technical solutions are today available, with all of them being fully investigated in experiments, with specific values
Page 34
Oxidation Stability of Insulating Fluids
and limits. The detailed description of the different oil preservation systems goes beyond the scope of this paper,
but the following can be cited as a historical background:
Many other parameters should be taken in account: such as oil type (uninhibited or inhibited), cooling system
(natural, forced, etc.), desiccant type (salts driers, Peltier effect), maintenance practices; with regard to oil oxidation
expectations, all the above systems can be categorized into two simple classes:
Free-Breathing Transformers
Closed Type Transformers.
60 1.5 500
Neutralisation
50 Value
1.2 400
LOAD
OIL TEMP
40
AIR TEMP
0.9 300
LOAD
30
°C
NV
0.6 200
20
10 0.3 100
0 0 0
1940 1942 1944 1946 1948 1950 1940 1942 1944 1946 1948 1950
Fig. 31 Variation of acidity, max temperature (air and oil) and load of a typical 500-kVA
transformer installed in 1938
It is evident that the purpose of the sealing systems is to prevent air and moisture from contacting liquid and solid
insulation. A combination of oxygen and water will greatly reduce the service life of the transformers by oxidizing
and ageing of oil and paper.
Worldwide experience mainly reflects consolidated local traditions and is sometimes dependent upon user polices
for fault prevention, environmental protection and fire safety. Economical aspects are less critical because the extra
cost of oil preservation systems is quite negligible for large power transformers (high value) and in any case it is
fully amortized in the long run.
Despite the availability of a large number of different test methods for measuring oxidation stability in new or
unused insulating oils, none of them is specifically devoted to evaluation of the residual life of in-service oils. It is
therefore common practice to control oil ageing by the direct titration of its by-products (acidity , referred to as NN)
and by the measuring of electrical parameters (DDF, resistivity) or physical (IFT) sensitive to by-products. IEC
60422 provides detailed and profound descriptions for basic rules on oil surveillance; in doing this the key
parameter is the oil acidity, which in this context must be considered as a global measure of oil ageing sufficient to
promote the proper maintenance action in order to prevent sludge and asphalt generation.
The following Table 7 and Fig. 32 report long-time experience in oil oxidation monitoring for the two transformer
classes [33].
Page 35
Oxidation Stability of Insulating Fluids
Table 7 Acidity (neutralization value (average and maximum value) as function of age for open
(free breathing) and closed type transformers
0.50
Neutralisation Value (mg KOH/g oil
0.40
CLOSE_av
OPEN_av
0.30
CLOSE_max
OPEN_max
0.20
IEC 60422 Limit
for type O and A
0.00
<10 10-15 15-20 20-25 25-30 30-35 35-40 > 40
age (years)
Fig. 32 Acidity (neutralization value) (average and maximum value) as function of age for open
(free breathing) and closed transformers
Looking at the above data it can be perceived how the IEC 60422 given limit for acidy is practically never reached
in close equipment and even for open type equipment acidity was adequate for roughly 20 years.
This data reflects the experience gained in Italy (from a large fleet of generation and transmission transformers for
half a century) with the use of membrane conservator. After some negative experience with the flat membrane
(revealed to be too fragile at the perimetrical fastening, excellent performance was obtained with the nitrylic rubber
Page 36
Oxidation Stability of Insulating Fluids
bag reinforced with nylon tissue. This solution has shown, apart from good mechanical reliability, excellent
effectiveness in preventing ingress of atmospheric air and moisture. The periodic DGA show oxygen concentration
below 500 ppm and water content below 10 ppm: as a consequence the acidity increase rate is very low.
Also worth mentioning is the interfacial tension (IFT) test; many of oil soluble by-products are hydrophilic and
hydrophobic and having tensioactive behavior may reduce the IFT value. This value (expressed as mN/m) quickly
drops from approximately 45 for new oils to 20 for used oils with only 0.1 mg KOH/g oil of acidity. Consequently,
the IFT test is extremely sensitive in first stage of oil oxidation, but then becomes ineffective for detection of further
levels of degradation.
The following Fig. 33 shows the relationship between interfacial tension (IFT) and acidity (NN).
60
50
40
IFT (mN/m)
30
20
10
0
0 0.1 0.2 0.3 0.4 0.5
NN (mg KOH/g)
It is further acknowledged that tradition and allegations rather than peremptory needs are the reasons for the
widespread preference accorded to uninhibited oils. The fear of collapse of oxidation resistance observed with
inhibited oils in accelerated laboratory tests was never supported by field evidence. Of greater substance may be
the issue of miscibility that is explicitly granted at any time and in all ratios only in the absence of additives. Yet,
complete miscibility is specified for other petroleum products, such as transportation fuels and engine lubricants
that depend on a complex package of additives for their performance [56]. It is further perceived that the aftermath
of the current landmark case will lead to greater use of metal-deactivator additives, even with deeply desulfurized
base oils. In addition to protecting against corrosion, they also enhance oxidation stability by counteracting the
catalytic effect of copper [57].
Page 37
Oxidation Stability of Insulating Fluids
Relatively low average values for acidity (TAN) and dielectric lossfactor (DDF) reflect efficient inhibitor protection of
oil and slow ageing rates (Table 8) . Also, oil change and reclamation procedures have impacted improved oil
quality of transformers in service, and have influenced lower TAN and DDF values (Fig. 34). Taking this into
account (approx. 10 % reclaimed oils) average TAN values are max. up to 0.15 – 0.20 mgKOH/g .
Table 8 Average values of acidity (in mg KOH/g oil), interfacial tension (IFT in mN/m) and
dielectric loss factor (DDF in*10-3) of inhibited oils in service
Y. in service Acidity av. Acidity max. IFT av. DDFav.
0.15
TAN, mgKOH/g
0.14
0.13 IFT, N/m
0.12 DDF
0.11
0.1
TAN, IFT, DDF
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
0-10 10 to 20 20 to 30 30 to 40 40 to 50 50 to 55 55 to 60
Years of Service
Fig. 34 Average values of acidity (TAN), interfacial tension (IFT) and dielectric loss factor (DDF)
based on years of service
Page 38
Oxidation Stability of Insulating Fluids
Fig. 35 Average in service acidity ( TAN values) at different voltage level and years
Maximum TAN values for both voltage levels were for 30 years service up to 0.20 mgKOH/g, and for up to 50 years
of service up to 0.47 mgKOH/g (Fig. 35).
Acidity increase correlates with increase in the loss factor (DDF). This correlation is more pronounced for older
units (Fig. 37).
TAN vs IFT
60
50
40
IFT. mN/m
30
20
10
0
0 0.05 0.1 0.15 0.2 0.25
TAN, mgKOH/g
Page 39
Oxidation Stability of Insulating Fluids
300
DDF, ‰ TAN vs DDF
Units 30 -49 years old
250
200
150
100
50
TAN, mgKOH/g
0
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
Page 40
Oxidation Stability of Insulating Fluids
0.40
0.35
0.30
0.25
DBPC, %m
TAN, mgKOH/g
0.20
IFT, mN/m
DDF
0.15
0.10
0.05
0.00
72
74
75
77
78
79
94
96
00
02
04
04
07
09
19
19
19
19
19
19
19
19
20
20
20
20
20
20
6/
5/
9/
5/
9/
3/
7/
0/
0/
7/
1.
9/
8.
9.
/0
/0
/0
/0
/0
/0
/0
/1
/1
/0
.1
/0
.0
.0
16
03
29
08
24
Fig. 38 Change of Acidity (TAN), IFT and DDF related to DBPC consumption
Page 41
Oxidation Stability of Insulating Fluids
0.35
0.30
0.25
0.20 DBPC, %m
TAN, mgKOH/g
IFT, mN/m
0.15 DDF
0.10
0.05
0.00
/03/1981 /03/1982 /12/1983 /06/1984 /02/1987 /01/1988 /02/1997 /08/2005 /03/2008
Fig. 39 Change of Acidity (TAN), IFT and DDF related to DBPC consumption
Page 42
Oxidation Stability of Insulating Fluids
0.35
0.30
0.25
DBPC, %m
0.20
TAN, mgKOH/g
IFT, N/m
0.15 DDF
0.10
0.05
0.00
86
90
76
80
04
97
99
02
05
07
09
19
19
19
19
20
19
19
20
20
20
20
9/
5/
9/
0/
5.
3/
1/
3/
0/
9/
4/
/0
/0
/0
/1
.0
/0
/1
/0
/1
/0
/0
23
27
15
26
16
13
10
21
14
Fig. 40 Change of Acidity ( TAN), IFT and DDF related to DBPC consumption
Page 43
Oxidation Stability of Insulating Fluids
0,25
DBPC (%)
0,20
0,15
0,10
0,05
1994 1995 1996 1997 1998 1999 2000 2001 2002 2003
Fig. 41 The oil was originally inhibited. DBPC to a final concentration of 0.3% (reinhibition) was
added to a transformer in 1995. The transformer was taken out of service in 1999.
0,30
Acidity (m g KOH/g)
DBPC (%)
0,25
0,20
0,15
0,10
0,05
0,00
1998 1999 2000 2001 2002 2003 2004 2005 2006 2007
Fig. 42 DBPC was added to an end concentration of 0.3% to a transformer in 1997. This
transformer was taken out of service in 2005.
Page 44
Oxidation Stability of Insulating Fluids
Adding an inhibitor to differently aged samples and ageing under the conditions of IEC 61125C it has been shown,
that inhibition is effective when done at early stages of ageing with the conclusion that "younger" transformers are
to be prioritized rather than "older" ones [58].
A certain decrease in resistivity, however, has also been noticed and should be monitored.
Oil reclaiming can take place in the equipment itself (on-line or off-line), as well as in bulk outside the electrical
equipment.
A direct comparison of the oxidation stability of insulating oils prior to and after reclaiming is difficult, since all
established procedures for oxidation stability are designed for new oils. [Seeking of a correlation between oil
properties and oxidation stability in the case of reclaiming is not straightforward. Some conclusions based on test
series are [60]:
- No clear correlation between oil oxidation stability of reclaimed oils and any relevant oil property
parameters
- The amount of DBPC in purified oil is not the only factor in influencing oil oxidation stability, at least under
ASTM D2112 test conditions
- Additional improvement of oxidation stability is dependent on the type of adsorbent used in the treatment
Several oil characteristics can be monitored during reclaiming, e. g. IFT, neutralization value, loss factor, color
(Fig. 43).
Recently additional properties have been reported to be susceptible to the degree of reclamation like density and
refractive index [61].
Page 45
Oxidation Stability of Insulating Fluids
Fig. 43 Oil color change in the course of a reclaiming (from left to right)
Some examples of reclaiming and reinhibiting of inhibited oils with stability data over years are given below –
Fig. 44 [62] and Fig. 45, Fig. 46 [63].
Page 46
Oxidation Stability of Insulating Fluids
prior reclamation
after reclamation
prior reclamation
after reclamation
Fig. 44 Development of oil characteristics with time after reclamation. In both cases natural
adsorbent was used, based on Alumosilicates, with some amount of MgO, particle size from
800 – 1000 µm. Percolation process was applied in three cycles with re-inhibition afterwards,
up to 0.30-0.35% of DBPC [62]
Page 47
Oxidation Stability of Insulating Fluids
mg KOH/g oil, % m
adding inhibitor
30
2000
mN/m
0.2
*10^3
1500 Before regenetarion
25 0.15
1998. May
September
2002. June
2002. August
November
September
Oktober
23.03.2009
1996. May
1998. May
September
2002. June
2002. August
November
September
Oktober
23.03.2009
2008.
2008.
1996. May
1998. May
September
2002. June
2002. August
November
September
2008. Oktober
23.03.2009
2003.
2000.
2004.
2003.
2000.
2004.
2003.
2000.
2004.
Fig. 45 Free breathing transmission transformer 220 kV, year of manufacture: 1974 (filled
originally with uninhibited oil) year of regeneration: 2001, still in service [63].
38 3000
Interfacial tension DDF 0.36 Acidity Inhibitor content
Before regenetarion
After regenetarion 2500 0.31
33
mg KOH/g oil, % m
2000 0.26
adding inhibitor
*10^3
0.21
mN/m
28 1500 Before regenetarion
0.16
1000 After regenetarion
After regenetarion 0.11
23
Before regenetarion 500 0.06
18 0 0.01
1996. July
1998. March
2000. September
2001. July
2001. November
2002. January
2002. Oktober
2003. March
2004. June
2005. April
2007. May
1996. July
1998. March
2000. September
2001. July
2001. November
2002. January
2002. Oktober
2003. March
2004. June
2005. April
2007. May
1996. July
1998. March
2000. September
2001. July
2001. November
2002. January
2002. Oktober
2003. March
2004. June
2005. April
2007. May
Fig. 46 Free breathing transmission transformer 120 kV year of manufacture: 1960 ( filled
originally with uninhibited oil) year of regeneration: 1981 [63].
It is obvious, that the long-term stability of reclamation is dependent on many factors such as :
For the estimation of long-term stability of regenerated oils a 170h oxidation test under the conditions of IEC
61125C was used. The consumption of the inhibitor after the oxidation test seems to correlate with the
performance in service [64] .
Usual practice after reclaiming is inhibiting with DBPC. Some studies have shown that the induction period of
reclaimed oils with addition of DBPC is much longer than without [65]. As a test method a setup similar to EN
14112 has been used, but temperature, copper surface area/oil volume, oxygen flow etc. was modified to get as
close to IEC 61125B conditions as possible.
As seen from the graphs in the following reinhibiting on its own has very poor effect on oil that contains significant
amounts of oxidation products (Fig. 48). On the other hand, Fuller's earth treatment only gives very short induction
times, since the oil is nearly totally depleted of inhibitor (Fig. 47 and Fig. 49). However, the combination of earth
treatment and reinhibiting gives excellent results (Fig. 50).
Page 48
Oxidation Stability of Insulating Fluids
Fig. 48 Oxidation stability test of oxidized oil with the inhibitor content restored to 0.3%.
Fig. 49 Oxidation stability test of reclaimed oil before the addition of new inhibitor.
Page 49
Oxidation Stability of Insulating Fluids
Oil reclaiming without inhibiting may lead to a strongly deteriorated oil state in a very short time, therefore the
inhibition after reclamation is strongly recommended [66]. Two examples from real life are shown below.
Example – Fig. 51 [67]. The oil was reclaimed in 2002, without an addition of inhibitor. After only 30 months
the acidity was at the same level. The oil was finally replaced in 2006
Fig. 51 Acidity development (mg KOH/ g oil) in a reclaimed oil without addition of inhibitor.
Page 50
Oxidation Stability of Insulating Fluids
Fig. 52 Sludge precipitation on a Buchholz relay from a reclaimed oil without inhibitor
addition[68]
- 1992 – commissioning
- Regularly monitored maximum operation temperature between 64 and 70°C, in short periods several
ON/OFF every day
Treatment of insulating oils with alumosilicates such as molecular sieves extract passivators, which may have an
impact on their properties, e.g. corrosivity [69].
Experience in the UK in using reclaimed oil is summarized in the following section [70].
Page 51
Oxidation Stability of Insulating Fluids
Reclaimed oils are defined by BS148 (2009) as mineral insulating oil used in electrical equipment which has been
subjected to chemical and/or physical processing to eliminate soluble and insoluble contaminants. The quality of
the used oil that is reclaimed is key to the product being able to achieve the requirements of BS148:2009 and
reclaimers are careful not to choose oils that are unsuitable because they were originally of poor quality or because
they are contaminated with PCBs. It is generally assumed that oil that is supplied as reclaimed will have been
originally supplied to BS148 (1998) or an earlier version of this standard. These oils rarely present problems to
users and the practice remains common. However, oil supplied to IEC 60296 (2003) only may not be suitable for
reclaiming and then re-use as uninhibited reclaimed oil and it is likely that inhibitors will need to be used to meet
BS148.
Until the early 1990s it was relatively common for uninhibited reclaimed oil to be purchased for first fill of a new
transformer or other oil-filled equipment. Some oil supplied to BS148 between 1988 and 1992 exhibited an
abnormal and severe degree of sludging in certain makes of switchgear, including tapchangers; the cause of the
sludging was not clear. The supplier recommended that equipment containing this oil was inspected and replaced
in the event that sludging was occurring. Unusually, the sludging was not always accompanied by high acidity
values or especially a darkening in color.
The oil of concern was fingerprinted by means of GC-MS analysis of the polyaromatic fraction and the oil was
found to be readily identifiable. Other tests such as carbon typing and furan analysis were used to identify where
the oil had been used so that it could be replaced before sludging occurred. The furan analysis was useful in some
cases as it was at very high levels, up to 36ppm of 2-FAL were recorded; it is believed that the oil or an oil used in
the blend had been produced by solvent extraction . By the mid-2000s the oil had largely been removed from
equipment by UK utilities but where it had been stored on site and used later than 1994 during maintenance of tap
changers it may still cause sludging that is then apparent many years later. Tap changer oil is sometimes stored in
a conservator during maintenance and sludging here may also be found. Any migration of the sludge into the main
tank through this route can accelerate oxidation of the main tank oil even if it is originally from a different source.
For this reason, use of the conservator for holding selector oil during maintenance is not recommended. Whenever
contamination has occurred the main tank oil should be replaced or reclaimed and inhibited.
In some cases transformer main tank oil has been found to contain large amounts of sludge where the particular oil
was used from new (Fig. 53, Fig. 54). In these cases it is necessary to flush the main tank with as much 50% of the
main tank oil volume in order to remove enough sludge before it is refilled.
Fig. 53 Heavy deposition found in two different types of selector filled with reclaimed oil known
to produce sludge
Page 52
Oxidation Stability of Insulating Fluids
Fig. 54 Evidence of sludging in a conservator tank from a transformer filled from new with
reclaimed oil known to produce sludge
This particular experience of reclaimed oil, and possibly unused oil from the same source, should not detract from
the practice of using reclaimed oil any more than use of on-site reclamation which is becoming more common.
Reclamation of oil through either route is important in preserving a valuable and finite natural resource, this is
especially true for naphthenic-based transformer oils which continue to be the preferred choice of most utilities.
Fig. 55
Paper and copper for a non corrosive Paper and copper for the same oil after
but aged oil after the test acc. IEC 62535 reclaiming after the test acc. IEC 62535
Page 53
Oxidation Stability of Insulating Fluids
Based on the type of reclaiming (regeneration rigs) and/or type of Fuller's earth some additional corrosion
phenomena, not existing in the oil prior regeneration may arise [71, 72, 73]. This may be due to reactions with
existing sulfur compounds and/or extraction of natural passivators from the insulating oil. Mitigation of the process
can be achieved with a prolonged regeneration.
Addition of passivators to strongly oxidized oils may have some side effects like gassing or increasing of the loss
factor. This may be due to the fact, that passivators like Irgamet 39 or TTA are destroyed by [74, 75, 76]. The
addition of passivators to unoxidized new oils containing inhibitors is not known to produce side effects.
Nitrogen blanketing or hermetical sealing excludes atmospheric gases as well and prolongs life of oil.
Page 54
Oxidation Stability of Insulating Fluids
Page 55
No SPECIFICATION OXIDATION STABILITY GASSING TENDENCY ROTATING BOMB TEST INHIBITOR CONTENT Ca / Cp / Cn
%sludge
Method Duration Temp Flowrate Acid max Method Max Method Spec Method Spec Method Spec
max
SMS 430.10.1
2 National Grid Type II D2440 72 hrs 0.1 0.3
Version 1.1 D2112 220min
oils(Naphthenic)
Date 05/23/2007 164 hrs 0.2 0.4
Page 56
INSULATING OILS (UNINHIBITED AND
(UNINHIBITED AND INHIBITED) INHIBITED) PART 1:
PART 1: PURCHASE,
MANAGEMENT, MAINTENANCE
PURCHASE, MANAGEMENT,
(Type U) Uninhibited ASTM D2440-2004 164 hrs 110 0.3 0.6 ≤+5 IEC 60666 Not detectable
AND TESTING MAINTENANCE AND TESTING
11 JAPAN OEM IEC 61125C, Uninhibited 164 hrs 120 0.15 Lit/hr 1.2 0.8 IEC 60666 Not detectable
IEC 61125 C Trace Inhibited 332hrs 120 0.15 Lit/hr 1.2 0.8 0.08
72 Hrs 110 1 Lit/hr 0.15 0.5 D2300 Negative Not Applicable D 4768 or D2668 0
D2112
164 hrs 110 1 Lit/hr 0.3 0.6
Type 1
72 Hrs 110 1 Lit/hr 0.15 0.5 D2300 Negative 195 D 4768 or D2668 0.08
D2112
164 hrs 110 1 Lit/hr 0.3 0.6
Type 11
72 Hrs 110 1 Lit/hr 0.1 0.3 D2300 Negative 220 D 4768 or D2668 0.3
D2112
164 hrs 110 1 Lit/hr 0.2 0.4
Oxidation Stability of Insulating Fluids
No SPECIFICATION OXIDATION STABILITY GASSING TENDENCY ROTATING BOMB TEST INHIBITOR CONTENT Ca / Cp / Cn
%sludge
Method Duration Temp Flowrate Acid max Method Max Method Spec Method Spec Method Spec
max
Inhibited , Special
15 EUROPEAN OEM-1 IEC 61125 Method C
application
120 ± 0.5
500 hrs 0.15 Lit/hr 0.3 0.05 IEC 60666 0.3(-0.05+0.10)
°C
Inhibited
120 ± 0.5
IEC 61125 Method C 500 hrs 0.15 Lit/hr 1.2 0.8 IEC 60666 0.3(-0.05+0.10)
°C
120 ± 0.5
IEC 61125 Method C 164 hrs 0.15 Lit/hr 1.2 0.8 IEC 60666 Not detectable
°C
D2440 164 hrs 110 1 Lit/hr 0.6 0.3 D 4768 or D2668 0.01-0.08
D2440 164 hrs 110 1 Lit/hr 0.4 0.2 D 4768 or D2668 0.08-0.30
120 ± 0.5 IEC 60628: 1985 , Method
16 Malaysia OEM IEC 61125 Method C 164 hrs 0.15 Lit/hr 1.2 0.8 5 IEC 60666 Not detectable ASTM D 2140 9.0 / 49.0 / 42.0
°C A
19 EUROPEAN OEM-2 IEC61125C Inhibited 500hrs 120 0.15 Lit/hr 1.2 0.8 D 2300 +30 IEC 60666 0.3
IEC61125C Uninhibited 164 hrs 120 0.15 Lit/hr 1.2 0.8 Not detectable
Page 57
for transformers and switchgear
BS EN 61125: 1993 Inhibited 164 hrs 120 0.15 Lit/hr 0.01 0.25 BS 5797:1994 for 120mins 8 No requirement
23 IRAN OEM IEC 61125C, Uninhibited 164 hrs 120 0.15 Lit/hr 1.2 0.8 IEC 60628 Method A eneral requirement IEC 60666 Not detectable
IEC 61125 C Trace Inhibited 332hrs 120 0.15 Lit/hr 1.2 0.8 0.08
IEC61125C Inhibited 500hrs 120 0.15 Lit/hr 1.2 0.8 0.4
24 EUROPEAN OEM-3 Mineral insulating oils IEC 61125C, Uninhibited<362 KV 164 hrs 120 0.15 Lit/hr 0.1 0.2 IEC 60628 Method A IEC 60666 Not detectable
IEC 61125C, Uninhibited362KVto 420KV 164 hrs 121 0.15 Lit/hr 0.1 0.15 or Not detectable
IEC 61125C, Uninhibited ≥420KV 164 hrs 122 0.15 Lit/hr 0.1 0.1 ASTM D 2300B Not detectable
IEC 61125 C Trace Inhibited<362 KV 332hrs 120 0.15 Lit/hr 0.1 0.2 0.08
IEC 61125 C Trace Inhibited362KVto 420KV 332hrs 121 0.15 Lit/hr 0.1 0.15 0.08
IEC 61125 C Trace Inhibited≥420KV 332hrs 122 0.15 Lit/hr 0.1 0.1 0.08
IEC61125C Inhibited<362 K 500hrs 120 0.15 Lit/hr 0.1 0.2 0.4
IEC61125C Inhibited362KVto 420KV 500hrs 121 0.15 Lit/hr 0.1 0.15 0.4
IEC61125C Inhibited≥420KV 500hrs 122 0.15 Lit/hr 0.1 0.1 0.4
Oxidation Stability of Insulating Fluids
Oxidation Stability of Insulating Fluids
6.2 Methods for Evaluating Oxidation Stability - Different Methods, Different Results
The methods used for oxidation stability were historically developed for lubricants and differ considerably in
conditions, time and temperature (Table 12), therefore it is not astonishing, that the results they deliver also differ.
Plus steel
ASTM D943 (TOST) (Induction) 95 1137 oxygen 6 and water,
Sol acids
DIN 51554 (Ba) 140 110 360 air (1500lifts/h) No air flow
No catalyst,
ISO 6886 (Induction) 110 (3g Sample) air 10 vol ox.
Products
Results of oxidation stability, achieved by different methods are the basis of evaluation in standards and guidelines
for unused insulation fluids. A brief overview is presented in Table 13.
Page 58
Oxidation Stability of Insulating Fluids
Table 13 Some existing determination and evaluation standards for oxidation stability.
Mineral oil Mineral oil Mineral oil Fatty acid
Synth. Ester
IEC ASTM Further ASTM ester
Ageing
Liberation of
Pro‐Oxidants
Degree of refining
Fig. 56 Liberation of pro-oxidants depends on the degree of refining. Mineral oils optimized to
one oxidation stability method may not necessarily perform well in another one. The curves
serve only as an exemplaric illustration.
Page 59
Oxidation Stability of Insulating Fluids
- ASTM D1934 “Oxidative aging of electrical insulating petroleum oils by open-beaker method”
Original: 96h at 115°C with or without copper catalyst (15cm2 for 300ml ratio 20:1)
The evolution of acidity and DDF has been monitored. ASTM D1934, especially the extended version, allows a
differentiation to be drawn between vegetable fluids, but not between mineral oils. IEC 61125C; the bubbling of air
in particular has a major impact on the oxidation behavior of vegetable fluids [79].
1400
A
1200
1000
B
Induction time (h)
800 C
600
400
200
Oil A – highly refined inhibited naphthenic oil,Oil B – Hydrocracked inhibited oil,Oil C – standard grade inhibited oil
Fig. 57 Effect of severeness of the test method on result of oxidation stability measured by the
induction period
Page 60
Oxidation Stability of Insulating Fluids
Copper wire (a), Q.S. 9.7 cm² ± 0.1 cm² 28.6 cm² ± 0.3 cm² 28.6 cm² ± 0.3 cm²
- Sludge
Determination on the - Sludge - Induction period - Soluble acidity
oxidized sample - Soluble acidity (0.28 mg KOH / g oil) - Volatile acidity
- Total acidity
- Sludge
- Soluble acidity - DDF
- Volatile acidity - Induction period
Optional - DDF
- Total acidity (0.10 mg KOH /g oil)
- Oxidation rate - Oxidation rate
- DDF
(a) The solid copper used as oxidation catalyst consist of a wire of soft electrolytic copper, with a diameter
between 1 mm to 2 mm and of a length to yield the surface area, in contact with the sample, specified by
the chosen method.
Page 61
Oxidation Stability of Insulating Fluids
Page 62
Oxidation Stability of Insulating Fluids
C= Air, 0,15dm³/h
Air
•Temperature 120°C
•Test duration
–164 h non inhibited
–332 h trace inhibited
–500 h inhibited oils
•Results:
120°C PH
copper wire – Total acid number
– Sludge
Oxidation Tube Absorption Tube – DDF
total acidity = Soluble acids + volatile acids
Oxygen 1dm³/h
•Temperature 110°C
•Test duration
–72h/164h for Type I and II
•Results:
– Total acid number
– Sludge
Page 63
Oxidation Stability of Insulating Fluids
In 2001 a revised draft test method was developed, its status today is still draft however. So at present two Baader
tests are available:
As the glassware quality may continue to be unavailable in the future, the draft version (which evaluates the
neutralization number instead of saponification number) is more frequently used than the active version from 1978.
The neutralization number can be evaluated with current glassware quality.
- DIN 51554 – 2 Test at 110°C => Preferably used for electrical oils
- DIN 51554 – 3 Test at 95°C => preferably used for hydraulic fluids H and lubricating
oils C, C-L and C-LP – tests only the saponification number.
For electrical oils only part two is of relevance, therefore only this part is described below
Fig. 60 DIN 51554 part 2 (1978) – Test of susceptibility to ageing according to Baader
6.7.3.1 Scope
The test method is designed to predict the oxidation of insulating fluids in contact with atmospheric air. The version
of 1978 was designed to test unused uninhibited transformer oils.
6.7.3.2 Ageing
The specimens are aged at 110°C (+/- 0,5°C) for 140h with access to air. In order to accelerate the ageing a
copper wire spiral is immersed and lifted
Page 64
Oxidation Stability of Insulating Fluids
25 strokes per minute / 36000 strokes per day. No air or oxygen flows through the sample. The oil vapor is
condensed with a Liebig condenser (Fig. 60). The oxidation test must be performed in a dark room that is free from
dust, acid, ammonia, organic vapor and ozone.
- Visual inspection
- Saponification number
- Sludge content
To perform tests two specimens filled with 60ml oil are aged.
Copper catalyst: 2 mm diameter, 300 mm length wound in a spiral. The copper is activated by a wear and cleaning
procedure to provide a fresh activated copper surface for the oxidation test.
6.7.3.3 Evaluation
Visual inspection: Any changes in the appearance of the specimens and of the wire spirals are ascertained and,
where appropriate, recorded in the test report.
Saponification Number: Test method is DIN 51559 part 2. A certain amount of sample is dissolved in a blend of
toluene and ethanol (contains a color indicator). KOH is added and the sample is heated. Surplus KOH, which is
not consumed by saponification, is titrated with HCl. The saponification number is calculated form the consumed
KOH.
Dielectric dissipation factor: test method is DIN 57370 part 1 (comparable to IEC 60247).
Sludge content: After the sample has been cooled down it is filtered through a glass filter. The sludge content
according to Baader, is the sludge which is soluble in chloroform. First the residue on the filter is dissolved with
chloroform and the residue after separation of the chloroform is recorded as the sludge.
6.7.4.1 Scope
The method is to predict the oxidation of insulating fluids in contact with atmospheric air. Method can be used for
unused inhibited and unused uninhibited transformer oils.
6.7.4.2 Ageing
The specimens are aged at 110°C (+/- 0.5°C) for 140h (or 28d for inhibited oils) with access to air. In order to
accelerate ageing a copper wire spiral is immersed and lifted
25 strokes per minute / 36000 strokes per day. No air or oxygen flows through the sample. The vapor of the oil is
condensed with a Liebig condenser. The oxidation test must be performed in a dark room that is free of dust, acid,
ammonia, organic vapor and ozone.
Page 65
Oxidation Stability of Insulating Fluids
- Visual inspection
- Saponification number
- Sludge content
To perform all tests two specimens filled with 60ml oil are aged.
Copper catalyst: 2 mm diameter, 300 mm length wound to a spiral. The copper is activated by a wear and cleaning
procedure to provide a fresh activated copper surface for the oxidation.
6.7.4.3 Evaluation
Visual inspection: Any changes in the appearance of the specimens and of the wire spirals is assessed and, where
appropriate, recorded in the test report.
A certain amount of the sample is dissolved in toluene and ethanol (contains a color indicator). KOH is used for
titration until neutralization. The neutralization number is calculated from consumed KOH.
Dielectric dissipation factor: test method is DIN 57370 part 1 (comparable to IEC 60247).
Sludge content: After the sample has been cooled down it is filtered through a glass filter. The sludge content
according to Baader is the sludge which is soluble in chloroform. First the residue on the filter is dissolved with
chloroform and the residue after separation of the chloroform is recorded as the sludge.
6.7.5 ROTATING PRESSURE VESSEL OXIDATION TEST (RPVOT,ASTM D2112, ASTM D2272)
ASTM D2112 is intended for inhibited mineral oils and is often used as a quick screening test [80, 81]. The test is
carried out at 140°C in the presence of copper, water and overpressure of oxygen (90 psi). The result is
represented as the time during which the oil reacts with a certain amount of oxygen (Fig. 61).
Thin film of
Sealed
Glass Oil +
Page 66
Oxidation Stability of Insulating Fluids
6.7.6 DSC
Differential scanning calorimetry (DSC) can be used to evaluate the heat developed or taken up as the temperature
of a material is changed. In the absence of phase transitions, the heat requirements reflect the specific heat of the
materials. DSC can also be used to evaluate the latent heat associated with phase transitions.
In the 90s preliminary studies showed a promising outlook of DSC for detection of a sort of induction period related
with oil oxidative resistance. Consequently, in 1998 IEC set up an ad-hoc WG to develop a rapid oxidation stability
test method based on DSC. The WG decided to apply an enhanced version of common DSC apparatus called
PDSC (pressure differential scanning calorimetry) where the heat developed or taken up from oil sample is
measured in presence of an oxidizing and pressurized atmosphere.
Unfortunately, despite of the efforts of the researches the study reveals difficulties in the understanding and in the
reproducibility of the shape of curve; also the dependence of results on the equipment used, sample-holder type
and heating profile was not completely clarified. All of these limits therefore prohibit official use of this test
technique as an oxidation stability test, and as matter of fact in 2006 IEC decided to publish the document 62036-
TR as Technical Report, purely as information.
In the past IR was applied in many studies on oil ageing and its sledges; in this regard the mostly common used
frequency bands were in the region 1800 – 800 cm-1:
6.7.8 EN 14112 – FAT AND OIL DERIVATIVES . FATTY ACID METHYL ESTER (FAME)
This method, known also as Rancimat is performed under following conditions (Fig. 45):
- no catalyst
- Flow 10 l air/h
- Temperature: 110°C
- 3 g sample
- Volatile oxidation products are transferred in a sampler with distilled water
- Result = Time until a conductivity of 200 µS/cm is reached
The induction time is determined from the maximum of the 2nd derivative of the curve for conductivity versus time
Page 67
Oxidation Stability of Insulating Fluids
This method has been modified by the use of a copper catalyst and applied for ranking of mineral oils and
vegetable esters. Acc. To this modified method vegetable esters are comparable with uninhibited mineral oils.
Copper has a very strong influence on the induction period, especially at lower temperatures. In the case of
uninhibited oils, a 10°C temperature increase leads to a doubling of the induction period. In the case of inhibited
oils, a 20°C temperature increase leads to a doubling of the induction period.
6.7.9 MICROCALORIMETER
Isothermal microcalorimeters have been used for years for measuring the oxidative stability of polyamides
pharmaceutics and propellants, for example. The method of using an isothermal microcalorimeter has been used
for research purposes and may be used for classification of insulating oils [82]. The area below the micro
calorimeter curves decreases with increasing oil/air ratio, given that there is a correlation between the amount of air
in the samples and the oxidation of the oils.
One common method was chosen, since it allows the use of a common criterion for all insulating fluids,
independent of the presence or absence of inhibitors. The insulating liquids studied were supplied by the
participants and consisted of inhibited and uninhibited mineral oils, unused or reprocessed, synthetic and natural
esters as well as liquids with new inhibitors, specially created for the test (not commercially available).
Additionally, participants were free to use methods commonly used in the practice and ones for which experience
was available.
Page 68
Oxidation Stability of Insulating Fluids
There was a great divergence of the results obtained by the various laboratories concerning the repeatability of the
test for induction period. After troubleshooting and corrections in the experiment setup a second run of results was
carried out.
Although the second round of results for the induction period are in better agreement, there nevertheless remains
high divergence for the results, especially for non-inhibited mineral oils. It seems that the method is complex
enough and the results vary, not only concerning the induction period, but also acidity, loss factor and sludge. It
seems that many of the volatile acids are absorbed by silicone tubing (turning yellow to brownish over time) and
therefore not detected in the aqueous extracts.
As a consequence, some recommendations to IEC 61125C will be made to improve the repeatability:
• Non use of silicone tubes, short paths between tubes, e. g. glass tubing joined with short flexible sleeves.
• Quality of air can be a concern. Control of air flow, as well as of the temperature and copper surface.
The result of the ranking depends very much on the selected test. The evaluation of insulation fluids with regard to
oxidation stability seems to be very much dependant on the application – free breathing or closed equipment.
In case of air access the ranking follows more or less the response of the oxidation inhibitor. However, here there
was also a difference between the induction time according to IEC 61125C and RPVOT test. It must also be
considered that only a few and widely divergent results were available for the RPVOT test.
In the case of the headspace method there is restricted amount of oxygen. Under such conditions there is not a
major oxidation impact and it also seems that uninhibited insulating fluids, as well as vegetable oils perform quite
well. Vegetable fluids without inhibitor packages tend to develop high acidity and loss factor. The headspace
method can in this respect be regarded as a functional test for testing service conditions.
In case of ageing of vegetable oils, viscosity has also been determined prior to and after ageing. The viscosity
increase is minimal.
To summarize, it is clear that prior introduction of a new insulating fluid, intensive studies and pilot projects are
needed. A combination of different tests may be useful to obtain a better correlation to experience in the field. This
should be considered when introducing a new insulating fluid onto the market.
One common method was chosen, since it allows the use of a common criterion for all insulating fluids,
independent of the presence or absence of inhibitors.
Additionally, participants were free to use methods commonly used in practice and ones for which experience was
available.
For determination of the induction period, the acidity of the water in the absorption tube needs to be titrated
regularly, and the accumulated volatile acidity plotted vs. time (Excel sheets have been provided for this). The
Page 69
Oxidation Stability of Insulating Fluids
induction time is the time needed for the volatile acidity to exceed 0.10 mg KOH/g. .
3447-2008 - high oleic vegetable oil, highly refined, inhibitor package (not DBPC)
3448-2008 - blend of a vegetable oil and esters of fatty acids and heavy monoalcohol, no additives
3451-2008 – depolarized reclaimed oil (reclaimed - combination of chemical reagent and sorbent)
3452-2008 – depolarized reclaimed oil (reclaimed - combination of chemical reagent and sorbent)
Page 70
Oxidation Stability of Insulating Fluids
3453-2008 – naphthenic-paraffinic based with total 0,40% inhibitors, consisting of hindered phenol type and
diarylamin type
All insulating fluids (with exception of the mineral oils with special inhibitors) have been used in real life, some of
them for pilot projects only.
Although the second results for the induction period are in a better agreement, there nevertheless remains great
divergence of results, especially for non-inhibited mineral oils. It seems that the method is complex enough and the
results vary not only for induction period, but also for acidity, loss factor and sludge. It seems that a lot of the
volatile acids are absorbed by silicone tubing (turning yellow to brownish with time) and are therefore not detected
in the aqueous extracts.
• Non use of silicone tubes, short paths between tubes, e. g. glass tubing joined with short flexible sleeves.
• Quality of air can be a concern. Control of air flow, as well as of the temperature and the copper surface.
Ascending Order Oxidation Stability Acc. Different Methods
ASTM HS Tangens-
Induction Time (Neutr. HS Neutr delta PDSC Onset
IEC 61125C (h) Value) value (90°C) Rbot (min) Time (min)
3441 3451 3448 3448 3448 3448
3451 3448 3449 3446 3449 3451
3440 3447 3446 3451 3451 3449
3449 3441 3447 3438 3439 3440
3438 3440 3451 3444 3440 3439
3448 3443 3453 3442 3441 3441
3439 3438 3452 3449 3447 3447
3447 3446 3454 3439 3438 3438
3454 3442 3438 3454 3442 3452
3444 3452 3443 3452 3444 3443
3450 3454 3442 3447 3450 3450
3442 3453 3444 3440 3452 3442
3452 3444 3450 3443 3443 3444
3446 3450 3441 3441 3453 3453
3443 3439 3440 3450 3446 3446
3453 3449 3439 3453 3454 3454
3438-2008 – naphthenic based
3439-2008 –naphthenic - paraffinic based
Legend 3440-2008 - severely hydrotreated naphthenic base oil
3439 uninhibited mineral 3441-2008– naphthenic based, hydrotreated
3442 inhibited mineral 3442-2008 - severely hydrotreated naphthenic base oil
3446 Ester 3443-2008 – naphthenic based, inhibited with 0,30% DBPC
3450 refurbished/reclaimed 3444-2008 – naphthenic based, hydrotreated phenolic inhibited
3453 special inhibitors 3446-2008 – synthetic ester
3447-2008 - A high oleic vegetable oil, highly refined, inhibitor package (not DBPC)
3448-2008 - blend of a vegetable oil and esters of fatty acids and heavy monoalcohol, no additives
3449-2008 - vegetable oil, highly refined, inhibitor package
3450-2008 – hydrotreated used oil
3451-2008 – depolarized reclaimed oil
3452-2008 – depolarized reclaimed oil
3453-2008 – naphthenic-paraffinic based with total 0,40% inhibitors, consisting of hindered phenol type and diarylamin type
3454-2008 - naphthenic based, hydrotreated phenolic and aminic inhibited
Fig. 63 Type of insulating liquids used in the test and their evaluation according to different
methods
In order to compare the ranking between different methods, only the procedures carried out at uniform conditions
for all insulating fluids were selected. In order to avoid outliners, mean values have been taken for this comparison.
Page 71
Oxidation Stability of Insulating Fluids
Statistically meaningful values existed only for determination of the induction time according to IEC 61125C and for
the headspace test. The PDSC onset time was not comparable, so the values of only one laboratory were taken.
- Vegetable fluids
- Inhibited oils
- Synthetic ester
6.8.6 DISCUSSION
The result of the ranking depends very much on the selected test. The evaluation of insulation fluids with regard to
oxidation stability seems to be very much dependant on the application – free breathing or closed equipment
(Fig. 63).
In the case of air access the ranking follows more or less the response of the oxidation inhibitor. However, here
there was also a difference between the induction time according to IEC 61125C and RPVOT test [85].
It must also be considered that only a few and widely diverging results were available for the RPVOT test. PDSC
Onset time showed nearly the same ranking as RPVOT.
In the case of the headspace method there is a restricted amount of oxygen. Under such conditions there is no
major oxidation impact and it also seems that uninhibited insulating fluids, as well as vegetable oils perform quite
well. Vegetable fluids without inhibitor packages tend to develop high acidity and loss factor. The headspace
method (closed vial method) can in this respect be regarded as a functional test for testing service conditions for
designs which allow only a restricted amount of oxygen. In the case of ageing of vegetable oils, viscosity prior to
and after ageing was also determined. The viscosity increase is minimal under these conditions.
Page 72
Oxidation Stability of Insulating Fluids
6.8.7 CONCLUSION
A combination of different tests may be useful to make a better correlation to experience in the field. This should be
considered when introducing a new insulating fluid. The RRT showed that insulating oils designed according to
only to one test, e.g. RPVOT may show contrary behavior in other tests, e.g. induction time according to IEC
61125C. This was the case with the two new oils with a new inhibitor mix created for the RRT.
Therefore, prior to introduction of new insulating fluids with new type of inhibitors or inhibitor mix, intensive studies
and pilot projects are needed.
Page 73
Oxidation Stability of Insulating Fluids
There is no direct correlation between the oxidation stability tests and the performance of insulating oils in service.
This is due not only to the different environments in a transformer or other electrical equipment, but also to the
particular working conditions such as load, design, cooling type etc. Nevertheless, enough evidence exists showing
that oils with low oxidation stability also have a shorter service life. A comparison of experience under similar
conditions indicates that inhibited insulating oils have a longer life than uninhibited ones. Knowing the factors which
contribute to insulating fluid oxidation and excluding them leads to a prolongation of the insulating fluid life. This is
especially important in case of natural esters. Less demanding applications, in terms of load or oxygen ingress may
perform well with uninhibited insulating fluids. High loaded free breathing equipment will have a longer insulating oil
life with inhibited oils. The choice of an insulating fluid becomes more and more application oriented, based on
customer and design requirements with regard to dielectric and physico-chemical considerations as well as
environmental aspects and fire safety.
Oxidation stability of insulating fluids is not only a matter of unused new fluids. It changes during service and
influences the diagnostic parameters used for condition assessment of the equipment, e.g. gas-in-oil analysis and
oil values. Knowledge of this behavior is essential for distinguishing between ageing of the fluid and failure in the
equipment.
A poor condition of the fluid does not necessarily mean poor condition of the equipment. Prolonging of oil life in
service will, in many cases, help prolong the effective use of equipment far beyond the designed life span.
Depending on the task, more or less sophisticated methods can be used – starting from simple inhibitor addition up
to oil reclaiming. Oil reclaiming removes most of the ageing byproducts, but also present inhibitors, therefore
inhibition after reclaiming is necessary for a long-lasting effect. The effect of reclaiming depends on many factors
such as oil and adsorbent type, reclaiming conditions, etc., and should be studied in more detail separately.
Oxidation stability is closely related to corrosivity, since sulfur compounds are responsible for both. With oil ageing
or some oil treatments non-corrosive oils may turn corrosive; therefore, all oil characteristics should be monitored in
service.
Main conclusions of the Cigre D1.30 work project are listed below:
- oxidation stability is important for oil performance and is to be regarded together with other oil properties
- oxidation stability is strongly related to the degree of refining and the interaction of natural and synthetic
inhibitors and passivators
- for qualifying of a new insulating liquid for electrical equipment more than one method for oxidation
stability should be applied and the results compared with existing experience
Page 74
Oxidation Stability of Insulating Fluids
- inhibited oils age more slowly (have a longer service life) than uninhibited ones
- reclaiming with subsequent inhibition prolongs the effective life of oil in service
- the choice of insulating fluid should be application oriented, i.e. considering design and operation
conditions
Page 75
Oxidation Stability of Insulating Fluids
Bibliography
[1] Duval M., Crine J.-P., Behaviour and Stability of Insulating Oils in EHV Current Transformers, IEEE, Vol. EI-
20, Nr. 2, 1985, 437-441
[2] Hilker A., Communication to D1.30.
[3] Nynas Transformer Oil Handbook, Nynas Naphthenics AB, Sweden, 2004
[4] Krishnamoorthy P. R. ,. Krishnaswamy K. R. , Vijayakumari S.,. Kumar K., « Ageing of mineral oils – a
diagnostic study », Proceedings of the 3rd International Conference on Properties and Applications of
Dielectric Materials, July 8-12, 1991, Tokyo, Japan
[5] Cigre Brochure 436, “ Experiences in Service with New Insulating Liquids”, WG A2.35, October 2010
[6] Bertrand Y, Communication to D1.30
[7] Denisov, E. T.; Afana'sev, I. B., Oxidation and Antioxidants in Organic Chemistry and Biology. Taylor and
Francis Group: Boca Raton, FL, 2005
[8] Smith, M. B.; March, J., March´s advanced organic chemistry. In 5 ed.; John Wiley & Sons Inc.: New York,
2001
[9] Ingold, K. U., Inhibition of the Autoxidation of Organic Substances in the Liquid Phase. Chem. Rev. 1961, 61
(6), 563-589
[10] Frankel, E. N., Lipid Oxidation. The oily press, PJ Barnes: Bridgwater, UK, 2005
[11] Denison, G. H., Oxidation of Lubricating Oils, Effect of natural sulfur compounds and of peroxides. Ind. Eng.
Chem. 1944, 36 (5): 477-482
[12] Halliwell B., Guteridge J. , Free Radicals in Biology &Medicine, Oxford University Press, 1998
[13] Rudnick L. R., Synthetics, Mineral Oils and Bio Based Lubricants, Chemistry & Technology, Taylor & Francies,
2006.
[14] Rudnick L., Lubricant Additives, Chemistry & Applications, CRC Press, 2009
[15] Lipshtein et al., “Transformer Oil”, US Department of Commerce, National Technical Information Service, 1970
[16] Clark F., “Insulating Materials for Design and Engineering”, John Wiley&Son, New York-London, 1967
[17] Lamarre C., Duval M., Crine J—P:, “Influence of Oxidation Byproduts onElectrical Properties of Inhibited
Transformer Oils”, Conference Record of 1986 IEEE Int. Symposium of Electrical Insulation, Washington DC,
June 9-11, 1986.
[18] Lamarre C., Crine J—P:, Duval M., “Influence of Oxidation on the Electrical Properties of Inhibited Naphthenic and
Paraffinic Transformer Oils”, IEEE, Vol. EI-22, Nr. 1, Febr. 1987, 57-62.
[19] Knothe G., Dunn R. , Dependance of Oil Stability Index of Fatty Compounds on Their Structure and Concentration and
Presence of Metals, JAOCS, Vol. 80, Nr. 10, 1021-1026
[20] Siddharth Jain, M. P. Sharma, Stability of Biodiesel and ist Blends: A review, Renewable and Sustainable Energy Reviews
14 (2010) 667-678
[21] Kyu-Wan Lee, Zhenyu Hong, Fengnv Piao, Young-Wun Kim, Keun-Woo Chung, Bond reactivity and
Antioxidant Effect on the Autooxidation of Soybean Oil, Journal of Industrial and Engineering Chemistry, 16
(2010) 419-424.
[22] Bertrand Yves, Laurichesse Delphine, Comparison of the Oxidation Stability of Vegetable Based and Mineral
Insulating Oils, MatPost07, 2007, Lyon
[23] Darwin A., Perrier C., Folliot Ph., The Use of Natural Ester Fluids in Transformers, MatPost07, 2007, Lyon.
[24] Perrier C, Ryadi M, Bertrand Y, Tran Duy C, Comparison Between Mineral and Ester Oils, D1 102, Cigre
Session Paris, 2010.
[25] Perrier C., Beroual A., Experimental Investigations on Insulating Liquids for Power Transformers : Mineral,
ester and silicone Oils, IEEE, Vol. 25, Nr. 6, 2009, 6 – 13.
[26] Atanasova-Hoehlein I., Rehorek Ch., Hammer Th, Gassing and Oxidation Behaviour of Insulating Fluids under Thermal
Stress, Cigre 6th Regional Africa Conference, Paper C107, 2009.
[27] Atanasova-Hoehlein I., Hammer Th., Schaefer M., Diagnostic Markers for Oxidation Condition of Mineral Oil and Ester
Insulating Fluids, Cigre Session Paris, 2010, paper D1 213.
[28] Atanasova-Hoehlein I, Frotscher R., Carbon Oxides in the Interpretation of Dissolved Gas Analysis in Transformers and Tap
Changers, IEEE, vol. 26, Nr. 6, 2010, 22 – 26
[29] Martin D, Lelekakis N. et al, Preliminary Results for Dissolved Gas Levels in a Vegetable Oil Filled Power Transformer,
IEEE, vol. 26, Nr. 5, 2010, 41 – 48.
Page 76
Oxidation Stability of Insulating Fluids
[30] Martin D, Lelekakis N. et al, Further Studies of a Vegetable-Oil-Filled Power Transformer, IEEE, vol. 27, Nr. 5, 2011, 6 –
13.
[31] Wilhelm H.-M., Communication to D1.30, 2010.
[32] Duval M. on Behalf of Cigre D1 32 DGA in Non-Mineral Oils and Load Tap Changers and Improved DGA Diagnostic
Criteria, Brochure 443, Dec. 2010.
[33] Petersen A. et al. “Comparison of Sealed Conservator Systems in Power Transformers vs. Desiccant Breather
Protection System”, Paris CIGRE Session 2008
[34] Qiu, C., Han, S., Cheng, X., Ren, T., Distribution of thioethers in hydrotreated transformer base oil by
oxidation and ICP-AES analysis, Ind. Eng. Chem. Res. 2005, 44, 4151-4155
[35] Speight, J. G., Refining chemistry. pp. 499-535 in The chemistry and technology of petroleum, 3rd ed, 1999,
Marcel Dekker, New York
[36] Fenske, M. R., Stevenson, C. E., Lawson, N. D., Herbolsheimer, G., Koch, E. F., Oxidation of Lubricating Oils.
Factors Controlling Oxidation Stability, Ind. Eng. Chem. 1941, 33, (4), 516-524.
[37] Burn, A. J., Greig, G., Optimum aromaticity in lubricating oil oxidations. J. Inst. Pet. 1972, 58, (564), 346-350.
[38] Wiklund, P., The response to antioxidants in base oils of different degree of refining. Lubr. Sci. 2007, 19, (3),
169-182.
[39] Liander, H. and Ericson, G. "Catalysts for Accelerated Ageing Testing of Transformer Oil." ASTM Special
Technical No. 172, 1956
[40] Kalantar, A.; Levin, M., Factors affecting the dissolution of copper in transformer oils. Lubr. Sci. 2008, 20, (3),
223-240.
[41] Rabelo Neto, R. C., Lima, D. O., Pinheiro, T. D. S., Almeida, R. F., Castro Dantas, T. N., Dantas, M. S. G.,
Araujo, M. A. S., Cavalcante, C. L., Jr., Azevedo, D. C. S., Thermo-Oxidative Stability of Mineral Naphthenic
Insulating Oils: Combined Effect of Antioxidants and Metal Passivator, Ind. Eng. Chem. Res. 2004, 43, (23),
7428-7434.
[42] Schaut A., Autru S., Eeckhoudt S, “Effects of Irgamet 30 on transformer oil”, Communication to WG. D1.30,
2011
[43] Thomson, C. N., Mechanism of copper catalysis in insulating oil oxidation. J. Inst. Petrol. 1958, 44, (417), 295-
317
[44] Hamblin, P. C., Kristen, U., Chasan, D., Ashless antioxidants, copper deactivators and corrosion inhibitors:
Their use in lubricating oils., Lubr. Sci. 1990, 2, (4), 287-318.
[45] Duval on Behalf of Cigre D1.11/A2.11, Recent Developments in DGA Interpretation, Cigre Brochure 296, June
2006.
[46] Atanasova-Höhlein I., „Unusual Cases of Gassing of Transformers in Service“, IEEE Electrical Insulation
Magazine, vol. 22, Nr. 1, 22 – 25, 2006.
[47] Masanori Kohtoh, Shuhei Kaneko, Shigemitsu Okabe, „Aging Effect on Electrical Characteristics of Insulating
Oil in Field Transformers“, IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 16, Nr. 6, 1698-
1706.
[48] Wilson G., National Grid UK, Communication to D1.30.
[49] Berger N., Philippini J. C., Tobazeon R. on behalf of Cigre TF 15.02.04 “Progress in the determination of the
loss factor and/or resistivity of insulating fluids”, Electra, 185, 59-73, 1999.
[50] Lundgaard L. on Behalf of Cigre D1.01.10“Ageing of Cellulose in Mineral Oil Insulated Transformers”, Cigre
Brochure 323, October 2007.
[51] Lundgaard L., Hansen W., Ingbrigtsen S, “Ageing of Mineral Oil Insulated Cellulose by Acid Catalysis””IEEE,
2008, 540 – 546.
[52] Q. Liu, Z.D. Wang, N. Azis, W.W. Sampson, P. Jarman, S. Ryder, and H. Z. Ding, "Assessment of ageing
conditions through paper tensile strength analysis of scrapped transformers," in International Symposium
of High Voltage (ISH 2009), Cape Town, South Africa, 2009.
[53] Scatiggio F., Terna, Communication to D1.30
[54] Lutz H.,“System de préservation d’huile de transformateurs ed problémes associés”, Rapport présenté au
nom du Comité International d’Études N°12 du CIGRE – Paris.
[55] Wilson A.C.M. , “Oxidation stability of Insulating Oil“, Proceedings IEEE, vol. 112- March 1965.
[56] Fessler W. A. et al. ”Accelerated Aging Studies of Distribution Transformers Containing Naphtenic and
Paraffinic Mineral Oil”, IEEE-ISEI 1978.
[57] Scatiggio F. et al. “Understanding and Management of Sulfur Corrosion from Insulating Oil”, Paris CIGRE
Session 2008.
[58] Wilson G. “Assessment of Reclamation Feasibility for In-Service Transformer Oils”, Periodic report number 1,
National Grid-Cranfield University, December 2002- June 2003.
Page 77
Oxidation Stability of Insulating Fluids
[59] Pahlavanpour B. on behalf of Cigre D1.01 (TF 12), “Insulating Oil Regeneration and Dehalogenation”, Cigre
Brochure 413, April 2010.
[60] Kovacevic S., “Oxidation Stability of refurbished Oils”, Communication to D1.30.
[61] Ritchie L., Sneddon C., Lee-Davey J., Setford, S, Wilson G. “The Characteristic Oil Oxidation Profile as
Measured Using Oil Density, Communication to D1.30.
[62] Lukic J. Communication to D1.30.
[63] Laboncz S. Communication to D1.30
[64] Haug, A M, Koncan-Gradnik M., Communication to D1.30.
[65] Berg Ø., Herdlevær K., Dahlund M., Renström K., Danielsen A., and Thiess U., “Experiences from on-site
transformer oil reclaiming,” in CIGRÉ Main Session 2002, Paris, France, Paper 12-103
[66] Wilson G. “Assessment of Reclamation Feasibility for In-Service Transformer Oils”, Final report, National
Grid-Cranfield University, July- December 2004.
[67] Wilson G. “Regeneration without Inhibition”, Communication to D1.30.
[68] Atanasova-Hoehlein I., Communication to D1.30.
[69] Lombard A., Osborne J. “The relationship between passivator and gas formation”, Eskom. Doble Conference,
Soth Africa, 2010.
[70] Wilson G. “UK Experience with Reclaimed Oils”, Communication to D1.30.
[71] Dahlund M., Johansson H., Lager U., and Wilson G., “Understanding the Presence of Corrosive Sulfur in
Previously Non-Corrosive Oils Following Regeneration”, 2010 International Conference of Doble Clients,
Boston, March 2010
[72] Dahlund M., Lorin P., Werle P., Effects of on-line reclaiming on the corrosive sulphur content of transformer
oil“ GCC Power 2010, Doha
[73] Dahlund M., Pettersson L., Önnerud H., Gustafsson K., Leandersson R.,.Karlsson S., “Removing corrosive
sulphur from transformer oil by using conventional on-line oil reclaiming technique”, CIGRE Joint A2/D1
Colloquium, Brügge, 2007]
[74] Scatiggio F., ”The Side Effect of Passivation”, communication to D1.30.
[75] Briosso E., Marull F., Momesso G “Effects of Adding Passivator on to the Oil DDF ofUnits with Aged
Insulation, 12th Regional Cigre Conference, Itaipu, 20-24.05.2007.
[76] Wiklund P “Stability of Benzotriazole Copper Surface Passivators in Insulating Oil”, Ind. Eng. Chem. Res.,
2007, Vol. 46, 3312-3316.
[77] Fofana I., Sabau J., Bouaicha A., Farzaneh M. “An Improved Preventive Maintenance Technique for Freely
Breathing Power transformers”, 16th Int. Symp. On High Voltage Ing.,Paper F-2, 2009, SAIEE, Innes House,
Johannesburg, 1482-1487.
[78] YuHimin, Gupta, Communication to D1.30.
[79] Perrier C., Beroual A., “Experimental Investigations on Insulating Liquids for Power Transformers: Mineral,
Ester and Silicone Oils”, IEEE, Vol. 25, Nr. 6, 2009, 6 – 13.
[80] [Schaut A., De Rop A., Ecckhoudt S, “RBOT-IEC 61125C for inhibited oils”, Communication to D1.30, 2011.
[81] Scatiggio F., “Experience with RPVOT”, Communication to D1.30 2011.
[82] Tronstad I., “Microcalorimeter as a tool for studying oxidation stability of insulating liquids”, to be published.
[83] Ameye J. “Voltammetric Techniques for Transformer Fluid Oxidative Health Monitoring”, Fluitec
Communication to D1.30.
Page 78