Unidades de Compresor de Tornillo Rotativo: MODELOS 12 - 101
Unidades de Compresor de Tornillo Rotativo: MODELOS 12 - 101
Unidades de Compresor de Tornillo Rotativo: MODELOS 12 - 101
RXF
UNIDADES DE COMPRESOR DE TORNILLO
ROTATIVO
MODELOS 12 – 101
Table Of Contents
GENERAL INFORMATION OIL FILTER, SPIN-ON (RXF 12 – 50)............................. 24
PREFACE..........................................................................3 OIL FILTER (OF-1) CARTRIDGE STYLE (58 – 101)......24
DESIGN LIMITATIONS......................................................3 COALESCER OIL RETURN STRAINER.........................25
JOB INSPECTION.............................................................3 LIQUID INJECTION STRAINER......................................25
TRANSIT DAMAGE CLAIMS.............................................3 OIL PUMP STRAINER (Optional)....................................25
UNIT IDENTIFICATION.....................................................3 SUCTION CHECK VALVE BYPASS............................... 26
COMPRESSOR IDENTIFICATION...................................4 COALESCER FILTER ELEMENT................................... 26
GEOMETRICAL SWEPT VOLUME TABLE......................4 CHANGING OIL...............................................................26
SUCTION STRAINER CLEANING PROCEDURE..........27
INSTALLATION
DEMAND PUMP DISASSEMBLY....................................27
FOUNDATION................................................................... 5 DEMAND PUMP ASSEMBLY..........................................28
HANDLING and MOVING..................................................5 THRUST BEARING ADJUSTMENT............................. 29
SKID REMOVAL................................................................6 INSTALLATION OF CARBON GRAPHITE BUSHINGS
COMPRESSOR/MOTOR COUPLINGS............................6 ...................................................................................... 29
CH COUPLING..................................................................6 TROUBLESHOOTING THE DEMAND PUMP................30
HOLDING CHARGE and STORAGE.................................7 RECOMMENDED MAINTENANCE PROGRAM.............31
COMPRESSOR OIL.......................................................... 7 MAINTENANCE SCHEDULE.......................................... 31
OIL CHARGE.....................................................................7 VIBRATION ANALYSIS...................................................32
OIL HEATER......................................................................7 OIL QUALITY and ANALYSIS......................................... 32
OIL FILTER(S)...................................................................8 MOTOR BEARINGS........................................................32
SUCTION ISOLATION VALVE MOUNTING.....................8 OPERATING LOG........................................................... 32
THERMOSYPHON OIL COOLING....................................8 TROUBLESHOOTING GUIDE.........................................32
WATER-COOLED OIL COOLING.....................................9 ABNORMAL OPERATION
LIQUID INJECTION OIL COOLING..................................9 ANALYSIS and CORRECTION....................................... 33
DUAL DIP TUBE METHOD..........................................10 PRESSURE TRANSDUCERS - TESTING......................33
ECONOMIZER - HIGH STAGE (OPTIONAL).................10 PRESSURE TRANSDUCERS REPLACEMENT.............33
ELECTRICAL................................................................... 11 SLIDE VALVE TRANSMITTER
VOLTAGE PROTECTION.............................................11 REPLACEMENT - SLIDE STOP......................................35
MOTOR STARTER PACKAGE........................................12 TEMPERATURE SENSOR REPLACEMENT..................35
MINIMUM BURDEN RATINGS........................................13 OIL LEVEL TRANSMITTER REPLACEMENT................35
CONTROL POWER REGULATOR..................................13 TEMPERATURE and/or PRESSURE ADJUSTMENT.....35
OPERATION BARE COMPRESSOR MOUNTING................................35
OPERATION and START-UP INSTRUCTIONS.............14 TROUBLESHOOTING THE COMPRESSOR..................36
OIL SEPARATOR..........................................................36
RXF COMPRESSOR.......................................................14
LIQUID INJECTION OIL COOLING SYSTEM...............36
COMPRESSOR LUBRICATION SYSTEM......................14
HYDRAULIC SYSTEM...................................................37
NO PUMP OIL SYSTEM...............................................14
COMPRESSOR PORT LOCATIONS - RXF 12 - 19........38
COLD-START SYSTEM................................................14
SAE STRAIGHT THREAD O-RING FITTINGS - ASSEMBLY
DEMAND PUMP OIL SYSTEM.....................................15
PROCEDURE FOR RXF 58 - 101.................................40
COMPRESSOR OIL SEPARATION SYSTEM................15
P & I DIAGRAM, LIQUID INJECTION – SINGLE PORT. 41
COMPRESSOR HYDRAULIC SYSTEM..........................15
RXF COOLING OPTIONS (See P & I Diagrams)
CAPACITY CONTROL..................................................15
PLATE OIL COOLER.....................................................42
VOLUMIZER II Vi CONTROL........................................16
WIRING HARNESS - External for Analog Devices.........49
SLIDE VALVE CALIBRATION......................................16
WIRING HARNESS - AC to Heaters and Valves (External).50
COMPRESSOR OIL COOLING SYSTEMS.....................17
SINGLE-PORT LIQUID INJECTION.............................17 INSTALLATION OF ELECTRONIC EQUIPMENT
DUAL-PORT LIQUID INJECTION.................................17 WIRE SIZING...................................................................51
QUANTUM™HD EZ-COOL™ LIQUID INJECTION ADJUST- VOLTAGE SOURCE........................................................51
MENT PROCEDURE................................................17 GROUNDING...................................................................52
OPERATION OF DANFOSS VFD APPLICATIONS.......................................................52
LIQUID INJECTION VALVE..................................... 18 CONDUIT.........................................................................53
THERMOSYPHON OIL COOLING...............................21 WIRING PRACTICES......................................................53
INITIAL START-UP PROCEDURE..................................21 COMMUNICATIONS........................................................55
NORMAL START-UP PROCEDURE...............................22 UPS POWER AND QUANTUM™ HD PANELS................55
VFD SKIP FREQUENCIES..............................................22
FORMS
MAINTENANCE OPERATING LOG SHEET.............................................. 56
NORMAL MAINTENANCE OPERATIONS......................23 RXF COMPRESSOR PRESTART CHECKLIST..............57
GENERAL MAINTENANCE.............................................23 VIBRATION DATA SHEET..............................................62
COMPRESSOR SHUTDOWN and START-UP...............23
COMPRESSOR/MOTOR SERVICING............................24 INDEX..............................................................................65
GENERAL INSTRUCTIONS FOR REPLACING
COMPRESSOR UNIT COMPONENTS.........................24
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
GENERAL INFORMATION Page 3
CORRECT INSTALLATION
UNIT IDENTIFICATION
PROPER OPERATION Each compressor unit has two identification data plates. The
REGULAR, SYSTEMATIC PLANNED MAINTENANCE unit data plate containing unit model, serial number and Frick
sales order number is mounted on the control panel support
To ensure correct installation and application, the bracket. The compressor data plate containing compressor
equipment must be properly selected and connected to a model and serial number is mounted on the compressor body.
properly de-signed and installed system. The Engineering
plans, piping layouts, etc. must be detailed in accordance
with the best practices and local codes, such as those NOTICE
outlined in ASHRAE literature. When inquiring about the compressor or unit, or order-ing
repair parts, provide the MODEL, SERIAL, and FRICK
A refrigeration compressor is a VAPOR PUMP. To be certain
SALES ORDER NUMBERS from these data plates.
that it is not being subjected to liquid refrigerant carryover, it is
necessary that refrigerant controls are carefully selected and
in good operating condition; the piping is properly sized and
traps, if necessary, are correctly arranged; the suction line
has an accumulator or slugging protection; that load surges
are known and provisions made for control; operating cycles
and defrosting periods are reasonable; oil return is controlled;
and that high side condenser units control head pressures
and temperatures are within system and compres-sor design
limits.
It is recommended that the entering vapor temperature to
the compressor be superheated to 10°F above the
refrigerant saturation temperature to ensure that all
refrigerant at the compressor suction is in the vapor state.
DESIGN LIMITATIONS
The compressor units are designed for operation within
the pressure and temperature limits as shown in Frick
Publica-tion 070.410-SED.
The unit can be moved with a forklift by forking through the unit mounting supports to the skid before lowering the unit
base tubing. NEVER MOVE THE UNIT BY PUSHING onto the mounting surface.
OR FORKING AGAINST THE SEPARATOR SHELL OR
ITS MOUNTING SUPPORTS. If the unit is skidded into place, remove the cross members
from the skid and remove the nuts anchoring the unit to the
RXF 58 – 101 units can be moved with rigging, using a skid. Using a 10-ton jack under the separator, raise the unit at
crane or forklift by hooking into three lifting points on the the compressor end until it clears the two mounting bolts.
oil sepa-rator. See Figure 2. Spread the skid to clear the unit mounting support, then lower
the unit to the surface. Repeat procedure on opposite end.
WARNING
It is mandatory that the coupling center be removed and
the direction of motor rotation be confirmed before run-
ning the compressor. Proper rotation of the compressor
shaft is clockwise looking at the end of the compressor
shaft. Failure to follow this step could result in backward
compressor rotation which can cause compressor failure
or explosion of the suction housing.
Figure 2 - RXF 58 – 101 1. Inspect the shaft of the motor and compressor to ensure
that no nicks, grease, or foreign matter is present.
The unit can be moved with a forklift by forking under the
wooden skid (if provided), or it can be skidded into place 2. Inspect the bores in the coupling hubs to make sure that
with pinch bars by pushing against the skid. NEVER they are free of burrs, dirt, and grit.
MOVE THE UNIT BY PUSHING OR FORKING AGAINST THE
SEPARATOR SHELL OR ITS MOUNTING SUPPORTS. 3. Check that the keys fit the hubs and shafts properly.
4. Slide one hub onto each shaft as far as possible. It may
SKID REMOVAL
be necessary to use a screwdriver as a wedge in the slot
to open the bore before the hubs will slide on the shafts.
CAUTION 5. Hold the elastomeric gear between the hubs and slide both
This screw compressor package may be top-heavy. hubs onto the gear to fully engage the mating teeth. Center
Use caution to prevent unit from turning over. the gear and hub assembly so there is equal engagement on
both shafts. Adjust the space between hubs as specified in
If the unit is rigged into place, the wooden skid can be re- the CH Coupling Data Table below. SEE NOTICE:
moved by taking off the nuts and bolts that are fastening the
NOTICE RXF
BASIC
CHARGE
ADDITIONAL FOR
OIL COOLER
MODEL (gallon) (gallon)
The center section will be a little loose between the
hubs. This allows for growth during operation. 12 – 19 10 1
24 – 50 11 1
6. Torque the clamping bolts in both hubs to the torque value 58, 68 25 3½
given in the CH Data Table. DO NOT USE ANY LUBRICANT 85, 101 36 3½
ON THESE BOLTS.
Add oil by attaching the end of a suitable pressure type
HOLDING CHARGE and STORAGE hose to the oil drain valve (see Figure 3), located under
the oil separator. Using a pressure-type pump and the
Each compressor unit is pressure and leak tested at the John- recom-mended Frick® oil, open the drain valve and pump
son Controls-Frick factory and then thoroughly evacuated and oil into the separator.
charged with dry nitrogen to ensure the integrity of the unit
during shipping and short term storage prior to installation.
NOTICE
CAUTION Evacuation of the oil separator will assist the flow of oil
into the unit. Also, fill slowly because oil will fill up in
Care must be taken when entering the unit to ensure the separator faster than it shows in the sight glass.
that the nitrogen charge is safely released.
Oil distillers and similar equipment which trap oil must be
filled prior to unit operation to normal design outlet levels.
WARNING The same pump used to charge the unit may be used for
filling these auxiliary oil reservoirs.
Holding charge shipping gauges on separator and
external oil cooler are rated for 30 PSIG and are for The sight glass located near the bottom of the separator
checking the shipping charge only. They must be re- shell at the discharge end should remain empty when the
moved before pressure testing the system and unit is in operation. The presence of oil in this end of the
before charging the system with refrigerant. Failure vessel during operation indicates liquid carryover or
to remove these gauges may result in catastrophic malfunction of the oil return.
failure of the gauge and uncontrolled release of
refrigerant resulting in serious injury or death.
All units must be kept in a clean, dry location to prevent
corrosion damage. Reasonable consideration must be
given to proper care for the solid-state components of the
mi-croprocessor.
Units which will be stored for more than two months must
have the nitrogen charge checked periodically. Contact
Johnson Controls-Frick for long term storage procedure.
COMPRESSOR OIL
WARNING
DO NOT MIX OILS of different brands, manufacturers,
or types. Mixing of oils may cause excessive oil Figure 3 - Oil Drain Valve
foaming, nuisance oil level cutouts, oil pressure loss,
gas or oil leakage and catastrophic compressor failure. OIL HEATER
Standard units are equipped with 500 watt oil heaters, which
NOTICE provide sufficient heat to maintain the oil temperature for most
indoor applications during shutdown cycles and to permit safe
The oil charge shipped with the unit is the best start-up. RXF 12–50 use one heater while mod-els 58–101
suited lubricant for the conditions specified at the use two. Should additional heating capacity be required
time of purchase. If there is any doubt due to the because of an unusual environmental condition, contact
refrigerant, operating pressures, or temperatures; Johnson Controls-Frick. The heater is energized only when
refer to Frick publication 160.802-SPC for guidance. the unit is not in operation.
OIL CHARGE
WARNING
The normal charging level is midway in the top sight
Do not energize the heater when there is no oil in the unit,
glass located midway along the oil separator shell.
otherwise the heater will burn out. The oil heater will be
Normal operating level is between the top sight glass and
energized whenever 120 volt control power is applied to
bottom sight glass. Oil charge quantities are as follows:
the unit and the compressor is not running, unless the 16
amp circuit breaker in micro enclosure is turned off (or 15
amp fuse (1FU) in the Plus panel is removed).
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 8 INSTALLATION
OIL FILTER(S) The liquid level in the refrigerant source must be 6 to 8 feet
above the center of the oil cooler.
CAUTION
After removing the suction sealing disc, confirm that
the check valve hinge pin is in the vertical position!
If the hinge pin is not in a vertical position, then
failure of the check valve may occur. Figure 5 - Thermosyphon Oil-Cooled System
1. Thermosyphon oil cooler is supplied with oil side piped
INCORRECT! to the compressor unit and socket weld ends supplied on
the refrigerant side.
2. A refrigerant-side safety valve is required when refriger-
ant isolation valves are installed between the cooler and
thermosyphon receiver. If no valves are used between the
cooler and thermosyphon receiver, the safety valve on the
thermosyphon receiver must be sized to handle the
volume of both vessels. Then, the safety valve on the
cooler vent (liquid refrigerant side) can be eliminated.
3. System receiver must be mounted below thermosyphon
receiver level in this arrangement.
4. The refrigerant source, thermosyphon or system
receiver, should be in close proximity to the unit to
minimize piping pressure drop.
5. The liquid level in the refrigerant source must not be
less than 6 feet above the center of the oil cooler.
6. An angle valve should be installed in the piping before the
CORRECT! thermosyphon oil cooler to balance the thermosyphon sys-
tem. Sight glasses should also be installed at the TSOC inlet
and outlet to aid in troubleshooting. The factory-mounted
Figure 4 - Suction Isolation Valve Mounting plate-type thermosyphon oil cooler requires a refrigerant-side
drain valve to be provided and installed by the customer.
THERMOSYPHON OIL COOLING
The component and piping arrangement shown in Figure 5 is
EQUIPMENT: The basic equipment required for a thermo intended only to illustrate the operating principles of thermo-
syphon system consists of: syphon oil cooling. Other component layouts may be better
suited to a specific installation. Refer to publication 070.900-E
1. A source of liquid refrigerant at condensing pressure for additional information on Thermosyphon Oil Cooling.
and temperature located in close proximity to the unit to
minimize piping pressure drop.
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
INSTALLATION Page 9
Intermediate, and 10°F suction superheat; R-507 tion. Because of this, an output from the microprocessor is
unloaded slide valve. generally used to turn off the supply of flashing liquid on a
shell and coil or DX economizer when the capacity falls below
High-stage compressor units may be supplied with single- approximately 60%-70% (85%-90% slide valve position). This
port (low Vi, side, or closed thread) or dual-port (low Vi is done to improve compressor operating efficiency. Please
and high Vi), liquid injection oil cooling. Single port will be note however that shell and coil and DX economizers can be
furnished for low compression ratio operation and dual used at low compressor capacities in cases where efficien cy
port for high compres-sion ratio operation. Booster is not as important as ensuring that the liquid supply is
compressor units use single-port (High Vi), liquid injection subcooled. In such cases, the economizer liquid solenoid can
oil cooling due to the typically lower compression ratios. be left open whenever the compressor is running.
The control system on high-stage units with dual-port, liquid Due to the tendency of the port pressure to fall with de
injection oil cooling switches the liquid refrigerant supply to creasing compressor capacity, a back- pressure regulator
the high port when the compressor is operating at higher valve (BPR) is generally required on a Flash Economizer
compression ratios (3.5 Vi and above) for best efficiency. System (Figure 11) in order to maintain some preset pressure
difference between the subcooled liquid in the flash vessel
Where low compression ratios (low condensing pressures)
and the evaporators. If the back-pressure regulator valve is
are anticipated, thermosyphon or water-cooled oil cooling
not used on a flash economizer, it is possible that no pressure
should be used.
difference will exist to drive liquid from the flash vessel to the
evaporators, since the flash vessel will be at suction pressure.
CAUTION In cases where wide swings in pressure are anticipated in the
flash economizer vessel, it may be necessary to add an outlet
It is imperative that an uninterrupted high-pressure pressure regulator to the flash vessel outlet to avoid
liquid refrigerant be provided to the injection system at overpressurizing the economizer port, which could result in
all times. Two items of EXTREME IMPORTANCE are the motor overload. Example: A system feeding liquid to the flash
design of the receiver/liquid injection supply and the vessel in batches.
size of the liquid line. It is recommended that the
receiver be oversized sufficiently to retain a 5-minute The recommended economizer systems are shown in
supply of refrigerant for oil cooling. The evaporator Figures 9 – 12. Notice that in all systems there must be a
supply must be secondary to this consideration. Failure strainer and a check valve between the economizer vessel
to follow these requirements causes wire draw which and the economizer port on the compressor. The strainer
can result in damage to the expansion valve, loss of oil prevents dirt from passing into the compressor and the
cooling, and intermittant oil cooling. One method of check valve prevents oil from flowing from the compressor
accomplishing this is described below. unit to the economizer vessel during shutdown.
Figure 8
becomes most important when one or more compressors If the economizer pressure fluctuates, then the
run at partial load, exposing the economizer port to suction economizer pressure can be relayed to the control panel
pressure. In the case of a flash vessel, there is no need for via a pressure transducer to an analog input. This is the
the redundancy of a back-pressure regulating valve on the purpose of the pow-ermizer option. If the powermizer
vessel and each of the multiple compressors. Omit the option is selected, Frick provides a factory mounted and
BPR valve on the flash economizer vessel and use one on wired pressure transducer on the economizer inlet.
each compressor, as shown in Figure 12.
ELECTRICAL
NOTICE
Before beginning electrical installation, read the
instruc-tions in the section "Proper Installation of
Electronic Equipment" at the back of this manual.
RXF units are supplied with a Quantum™HD control system.
Care must be taken that the controls are not exposed to
physical damage during handling, storage, and installation.
The single-box control door must be kept tightly closed to
prevent moisture and foreign matter from entry.
Figure 10 - Direct Expansion Economizer System
WARNING
Customer connections are made in the Quantum ™HD
control panel* mounted on the unit. The electrical
enclosures should be kept tightly closed whenever work is
not be-ing done inside. * Or starter panel (if provided).
VOLTAGE PROTECTION
NOTICE
Johnson Controls-Frick® does not advise nor
Figure 11 - Flash Economizer System support the use of UPS power systems in front of
the Quantum™HD panel.
With a UPS power system providing shutdown protection
for the Quantum™HD, the panel may not see the loss of
the 3-phase voltage on the motor because the UPS could
prevent the motor starter contactor from dropping out.
With the starter contactor still energized, the compressor
auxiliary will continue to feed an “Okay” signal to the
panel. This will allow the motor to be subjected to a fault
condition on the 3-phase bus. Some fault scenarios are:
1. The 3-phase bus has power “on” and “off” in a continu-
ous cyclic manner which may cause the motor to overheat
due to repeated excessive in-rush currents.
Figure 12 - Multiple Compressor Flash Economizer System
2. Motor cycling may damage the coupling or cause other
ECONOMIZER VI CONTROL mechanical damage due to the repeated high torque
motor “bumps”.
Based on suction and discharge pressures, the control panel
calculates the proper volume ratio (Vi) for the compressor. 3. Prolonged low voltage may cause the motor to stall and
However, additional refrigerant vapor entering through the overheat before the motor contactor is manually turned off.
economizer port affects this calculation. If the addition of
economizer gas is not taken into acount the compressor will Under normal conditions, the loss of 3-phase power will
over compress. This uses more energy than necessary. shut down the Quantum™HD panel, and it will restart upon
power return. If the panel was in:
Quantum control panels are capable of adjusting the Vi to • Auto – Compressor motor will return to running as pro-
compensate for economized compressors. If the grammed.
economizer pressure is fixed, a regulating valve may be
used. In this case, the economizer operating pressure can • Remote – The external controller would reinitialize the
simply be entered into the control panel. panel and proceed to run as required.
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 12 INSTALLATION
CAUTION
When starting at full voltage or across-the-line, a
shunting device must be installed or the Analog I/O
board in the Quantum™HD panel may be severely Figure 13 - Starter Wiring Diagram
dam-aged at start-up. See Figure 13.
Motor starter and interlock wiring requirements are shown in
the diagram, Figure 12. All of the equipment shown is sup-
plied by the installer unless a starter package is purchased
separately from Frick. Starter packages should consist of:
1. The compressor motor starter of the specified horse-
power and voltage for the starting method specified
(across-the-line, autotransformer, wye-delta or solid-
state).
NOTICE
If starting methods other than across-the-line are
desired, a motor/compressor torque analysis must
be done to ensure sufficient starting torque is
available. Contact Frick if assistance is required.
2. If specified, the starter package can be supplied as a com-
bination starter with circuit breaker disconnect. However, the
motor overcurrent protection/disconnection device can be
applied by others, usually as a part of an electrical power
distribution board.
3. A 3.0 KVA control power transformer (CPT) to supply
120 volt control power to the control system and separator
oil heaters is included. If environmental conditions require
more than 2000 watts of heat, an appropriately oversized
control transformer will be required. Figure 14 - Point-to-Point Wiring Diagram
The CT must see all the current on any one phase, sor safety devices.
therefore in wye-delta applications BOTH leads of any
one phase must pass through the CT. CONTROL POWER REGULATOR
CURRENT TRANSFORMER SIZE Compressor units that will be used in areas that suffer brown-
outs and other significant power fluctuations can be supplied
Calculate (CT) size using the following formula where SF is with a control power regulator. See Figure 15, Recommended
Service Factor and FLA is Full Load Amps of the Motor. Regulator Installation.
FLA x SF x 1.1 (round up to the next hundred)
Example: FLA = 379; Service Factor = 1.15
379 x 1.15 x 1.1 = 479
Use a 500:5 CT
DO NOT use undersized current transformers since the
panel will not be capable of reading potential current. If the
CT is higher than calculated, enter it's value for [CT Factor]
on the panel. The unit can operate with a CT one size larger
than calculated, however, replace with the proper size ASAP.
NOTICE
DO NOT operate unit with a CT more than one size
larger than recommended.
Figure 17
The sight glass located near the bottom of the coalescer
section of the oil separator should remain empty during
normal operation. If an oil level develops and remains in the
sight glass, a problem in the oil return separation system or
compressor operation has developed. Refer to Maintenance
for information on how to correct the problem.
COMMON
OUT
VENT COMMON
OUT
PRESSURE
YY4
Figure 18
VOLUMIZER II Vi CONTROL
The RXF compressor is equipped with a special internal
control that automatically adjusts the compressor volume ratio
to the most efficient of three available steps, (2.2, 3.5, or 5.0
volume ratio). This gives the compressor the ability to operate
at varying operating conditions while minimizing power
consumption by avoiding over or undercompression.
Solenoid valves 3 and 4 (See Figures 19 - 21 and location
on P & I diagram represented by YY3 and YY4) control the
Volumizer II volume ratio control. Oil is internally ported to
apply hydraulic pressure to two stepping pistons in order
to move the moveable slide stop to the optimum position.
The following chart shows the logic of solenoid operation
to adjust the volume ratio.
COMPRESSOR OIL COOLING SYSTEMS liquid refrigerant is then supplied to the motorized
expansion valve. Refer to P & I DIAGRAMS section for
The RXF unit can be equipped with one of several systems piping and instrumentation drawings.
for controlling the compressor oil temperature. They are single
or dual-port liquid injection, thermosyphon, or water-cooled oil DUAL-PORT LIQUID INJECTION
coolers. Each system is automatically controlled,
The dual-port liquid injection system is designed to obtain
independentof compressor loading or unloading.
the most efficient compressor performance at high and low
Oil cooling systems maintain oil temperature within the fol- compression ratios by permitting injection of liquid
lowing ranges for R-717: refrigerant into one of two ports optimally located on the
compressor. This minimizes the performance penalty
Liquid Injection Oil Cooling: 130 to 150°F
incurred with liquid injection oil cooling.
External* Oil Cooling: 120 to 140°F
* Thermosyphon Oil Cooling (TSOC) or Water-Cooled Oil The dual-port system contains all the components of the
Cooling (WCOC). single-port system with the addition of a 3-way motorized
valve and operates as outlined.
SINGLE-PORT LIQUID INJECTION
The liquid injection solenoid valve is energized by the micro
The single-port liquid injection system is designed to permit processor when the temperature sensor, installed in the
liquid refrigerant injection into one port on the compressor at compressor discharge, exceeds the setpoint. Liquid refriger-
any given moment and operates as outlined. ant is then passed through the motorized expansion valve to
the 3-way motorized valve. Depending on the compressor’s
The liquid injection solenoid valve is energized by the micro operating volume ratio (Vi), the microprocessor will select the
processor when the temperature sensor, installed in the flow of the liquid refrigerant to the optimum compressor port.
compressor discharge, exceeds the setpoint. High-pressure
Figure 22
DESCRIPTION: This screen allows the user to enter and EZ COOL PI CONTROL
view the basic operating parameters related to EZ Cool
LIOC PI control. [Setpoint] - Enter the value that you wish to control to.
The following are the EZ Cool LIOC Setup screen [Proportional Band] – This setpoint determines the size of a
selections available on this screen: region either above or below the Control Setpoint. Within this
region, the Proportional component of the PI Output value is
the number between 0% and 100% that directly
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 18 OPERATION
corresponds to the difference between the Control Input •• “Down” arrow push button (Figures 23 and 24)
(Actual) and the Control Setpoint (Setpoint). Outside of this - Decreases parameter number by 1 at each activation.
region, the Proportional component is either 100% or 0%. If •• “Up” arrow push button (Figures 23 and 24)
the PI’s Action is Forward, the Proportional Band extends - Increases parameter number by 1 at each activation.
above the Control Setpoint. If the PID’s Action is Reverse, the
Proportional Band extends below the Control Setpoint.
High Limit - The highest value that the output can be.
Low Limit - The lowest value that the output can be.
OPERATION OF DANFOSS
LIQUID INJECTION VALVE
The Danfoss ICAD (Industrial Control Actuator with Display) is
equipped with an LED Interface from which it is possible to
monitor and change the setting of parameters to adapt the
ICAD and the corresponding ICM (Motorized Industrial Figure 25
Control Valve) to the actual refrigeration application.
- Gives access to change a value once the Parameter
The setting of parameters is managed by means of the list has been accessed.
inte-grated ICAD (Figures 23 and 24) and consists of: - Acknowledge and save change of value of a parameter.
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
OPERATION Page
19
- To exit from the Parameter list and return to the 1. Ensure that there is power to the valve (24 VDC) and all
display of Opening Degree (OD), keep the push wiring is complete prior to configuring the motorized valve.
button activated for 2 seconds. The ICAD 600 requires 1.2 amps for operation and the ICAD
•• Display (Figure 26) 900 requires 2.0 amps.
- Normally the Opening Degree (OD) 0 - 100% of the 2. Identify which actuator is being used (ICAD 600 or 900)
ICM valve is displayed. No activation of push buttons and which motorized valve is being used (ICM 20, 25, 32,
for 20 seconds means that the display will always 40, 50, or 65). Ensure that the correct actuator is being
show 0 (Figure 25). used with the ICM valve as follows:
ICM20 with ICAD 600
ICM25 with ICAD 600
ICM32 with ICAD 600
ICM40 with ICAD 900
ICM50 with ICAD 900
ICM65 with ICAD 900
3. When the valve is initially powered, A1 and CA will be
flashing on the LED display. Hold the enter button down
for two seconds until these values stop flashing.
4. Push the down arrow button and scroll until j10 is displayed
Figure 26 and push the enter button. Using the up arrow, scroll until j11
is displayed and push the enter button. This step must be
•• Displays the parameter.
completed within 20 seconds or the valve will reset.
•• Displays the actual value of a parameter.
5. Push the down arrow button again and scroll until j26 is
•• Displays the function status by means of text (Figure 23).
displayed and push the enter button. Identify the ICM
- Mod represents that ICAD is positioning the ICM valve being used and push the up arrow until the correct
valve according to an analog input signal (Current). number is displayed for the ICM valve and then push the
- Low represents that ICAD is operating the ICM valve enter button. The values are as follows:
like an ON/OFF solenoid valve with low speed 1 for ICM20
according to a digital input signal. 2 for ICM25
- Med represents that ICAD is operating the ICM valve 3 for ICM32
like an ON/OFF solenoid valve with medium speed 4 for ICM40
according to a digital Input signal. 5 for ICM50
6 for ICM65
- High represents that ICAD is operating the ICM valve
like an ON/OFF solenoid valve with high speed 6. The ICAD will store these parameters with the power
according to a digital input signal (Figure 27). removed.
Alarms - ICAD can handle and display different alarms.
ICM
Description Comments
Alarm Text
No valve type A1 At start-up A1 and CA will be
selected displayed
Controller fault A2 Internal fault inside electronics
All input error A3 When input amps are > 22 mA
PARAMETER LIST
Display Factory
Description Name Min. Max. Setting Unit Comments
ICM OD ICM valve Opening Degree is displayed during normal operation.
- 0 100 - %
(Opening Degree) Running display value (see j01, j05).
Internal main switch
1: Normal operation
Main Switch j01 1 2 1 - 2: Manual operation. Valve Opening Degree will be flashing. With the
down arrow and the up arrow push buttons the OD can be entered
manually.
Operation mode
1: Modulating - ICM positioning according to Analogue input (see j03)
Mode jo2 1 2 1 - 2: ON/OFF - operating the ICM valve like an ON/OFF solenoid valve
controlled via Digital Input. See also j09.
Type of Analog input signal from external controller
1: 0-20mA
Analog Input signal j03 1 4 2 - 2: 4-20mA
3: 0-10V
4: 2-10V
Speed can be decreased. Max. speed is 100 %
Not active when j01 = 2
If j02 = 2, the display will indicate speed in display. Low, Med, and
Speed at ON/OFF
j04 1 100 100 % High also means ON/OFF operation.
and Modulating Mode
If j04 < = 33, Low is displayed
33 < If j04 < = 66, Med is displayed
If j04 > = 67, High is displayed
Not active before j26 has been operated.
Automatic calibration j05 0 1 0 - Always auto reset to 0.
CA will flash in the display during calibration.
Type of A0 signal for ICM valve position
0: No signal
Analog Output signal j06 0 2 2 - 1: 0 - 20mA
2: 4 - 20mA
Define condition at power cut when fail-safe is installed.
1: Close valve
Fail-safe j07 1 4 1 - 2: Open valve
3: Maintain valve position
4: Go to OD given by j12
Define function when Dl is ON (short circuited Dl terminals) when j02 = 2
Digital Input function j09 1 2 1 1: Open ICM valve (Dl = OFF = > Close ICM valve)
2: Close ICM valve (Dl = OFF = > Open ICM valve)
Enter number to access password protected parameters:
Password j10 0 199 0 - j26
Old alarms will be listed with the latest shown first. Alarm list can be
Old Alarms j11 A1 A99 - - reset by means of activating down arrow and up arrow at the same
time for 2 seconds.
Only active if j07 = 4
OD at powercut j12 0 100 50 - If fail-safe supply is connected and powercut occurs, ICM will go to
entered OD.
NB: Password protected. Password = 11
At first start-up, A1 will flash in display. Enter valve type.
0: No valve selected. Alarm A1 will become active.
1: ICM20 with ICAD 600
ICM configuration j26 0 6 0 2: ICM25 with ICAD 600
3: ICM32 with ICAD 600
4: ICM40 with ICAD 900
5: ICM50 with ICAD 900
6: ICM65 with ICAD 900
OD% j50 0 100 - % ICM valve Opening Degree
AI [mA] j51 0 20 - mA Analog Input signal
AI [V] j52 0 10 - V Analog Input signal
AO [mA] j53 0 20 - mA Analog Output signal
DI j54 0 1 - - Digital Input signal
DO Close j55 0 1 - - Digital Output Closed status. ON when OD < 3%
DO Open j56 0 1 - - Digital Output Open status. ON when OD > 97%
DO Alarm j57 0 1 - - Digital Output alarm status. ON when an alarm is detected
MAS mP SW ver. j58 0 100 - - Software version for MASTER Microprocessor
SLA mP SW ver. j59 0 100 - - Software version for SLAVE Microprocessor
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
OPERATION Page
21
THERMOSYPHON OIL COOLING adequate oil flow. There is still an orifice installed in the
compressor to control maximum oil flow. At initial start-up of
Thermosyphon oil cooling is an economical, effective method the package the hand expansion valve must be fully open.
for cooling oil on screw compressor units. Thermosyphon After initial start-up of the package the hand expansion valve
cooling utilizes liquid refrigerant at condenser pressure and should be adjusted. There are two methods of determining the
temperature which is partially vaporized at the condenser correct adjustment of this valve.
temperature in a shell and tube or plate-type vessel, cooling
the oil. The vapor, at condensing pressure, is vented to the The best method to determine target discharge temperature is to
condenser inlet and reliquified. This method is the most cost run CoolWare™ with the operating conditions of the compressor.
effective of all currently applied cooling systems since no The program will give you a theoretical discharge temperature of
compressor capacity loss or compressor power penalties are the compressor. Once this temperature is known, you may adjust
incurred. The vapor from the cooler need only be condensed, the hand expansion valve. The ideal discharge temperature is
not compressed. Refrigerant flow to the cooler is automa tic, within 5°F + or – of the theoretical discharge temperature. Adjust
driven by the thermosyphon principle, and cooling flow the valve to achieve the theo-retical discharge temperature. If you
increases as the oil inlet temperature rises. do not have access to CoolWare™, 180°F is a good target
discharge temperature for a high stage ammonia compressor.
Booster applications and compressors using HFC and HCFC
refrigerants may run cooler. Compressors with high discharge
pressure may run hotter.
Current thermosyphon systems are using single-pass oil 2. All RXF Models! For proper and safe operation, the com-
coolers and flow rates based on 3:1 overfeed. pressor must be run at the proper speed and discharge pres-
sure. Exceeding design conditions creates a potential hazard.
The liquid/vapor returned from the cooler is separated in
3. Rotate and lubricate motor bearings according to manufac-
the receiver. The vapor is vented to the condenser inlet
and need only be reliquified since it is still at condenser turer’s recommendations PRIOR to initial start-up as required.
pressure (see Figure 28). 4. After running the unit for approximately three hours, ad-just
liquid injection oil cooling if applicable. If unit has water cooled
INITIAL START-UP PROCEDURE oil cooling, adjust water control valve to cooler.
Having performed the checkpoints on the prestart check 5. The compressor slide valve linear transmitter should be
list (see FORMS section), the compressor unit is ready for calibrated.
start-up. It is important that an adequate refrigerant load
6. Perform vibration analysis if equipment is available.
be available to load test the unit at normal operating condi-
tions. The following points should be kept in mind during 7. Pull and clean suction strainer after 24 hours operation. If it
initial start-up. is excessively dirty, repeat every 24 hours until system is
clean. Otherwise, follow the Maintenance Schedule. See the
1. Models 58 - 101 ONLY! It is imperative that during the
RECOMMENDED MAINTENANCE PROGRAM section.
initial start-up of the package that the hand expansion
valve on the main oil injection line is fully open to ensure
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 22 OPERATION
GENERAL MAINTENANCE 6. Shut off the cooling water supply valve to the oil cooler.
Drain water, if applicable. Attach CLOSED tags.
Proper maintenance is important in order to assure long
and trouble-free service from your screw compressor unit. 7. Protect oil cooler from ambient temperatures below
Some areas critical to good compressor operation are: freezing.
1. Keep refrigerant and oil clean and dry, avoid moisture
contamination. After servicing any portion of the refrigera
tion system, evacuate to remove moisture before returning
NOTICE
The unit should be inspected monthly during
to service. Water vapor condensing in the compressor
shutdown. Check for leaks or abnormal pressure. Use
while running, or more likely while shut down, can cause
rusting of critical components and reduce life. the main-tenance log to record readings to verify the
pressure stability of the unit. To prevent the seals and
2. Keep suction strainer clean. Check periodically, par- bearing from drying out, run oil pump (if available) and
ticularly on new systems where welding slag or pipe scale manually rotate the compressor shaft. Consult motor
could find its way to the compressor suction. Excessive manufac-turer for motor recommendations.
dirt in the suction strainer could cause it to collapse,
TO START UP AFTER SEASONAL OR PROLONGED SHUT-
dumping particles into the compressor.
DOWN, USE THE FOLLOWING PROCEDURE :
3. Keep oil filters clean. If filters show increasing pressure
drop, indicating dirt or water, stop the compressor and 1. Perform routine maintenance. Change oil and replace
change filters. Running a compressor for long periods with filters. Check strainers.
high filter pressure drop can starve the compressor for oil 2. Any water necessary for the operation of the system
and lead to premature bearing failure. that may have been drained or shut off should be restored
4. Avoid slugging compressor with liquid refrigerant. While or turned on.
screw compressors are probable the most tolerant to in- 3. Reset solenoid valves to automatic position, then open
gestion of some refrigerant liquid of any compressor type all valves previously closed. Remove tags.
available today, they are not liquid pumps. Make certain to
maintain adequate superheat and properly size suction 4. Compressor unit is ready for prestart checks. Refer to
accumulators to avoid dumping liquid refrigerant into com- PRESTART CHECKLIST.
pressor suction.
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 24 MAINTENANCE
COMPRESSOR/MOTOR SERVICING 2. Isolate the package by closing all package valves to the
system. Tag all closed valves.
Before removing the motor from an RXF unit, it is criti-cal
that proper support be provided for the compressor to
prevent damage to the oil separator. Insert blocks or a
jack between the separator shell and compressor casting.
CAUTION
Open any solenoid valves or other valves that may trap
Make sure the weight is held safely by the separator shell.
Loosen the compressor discharge flange bolts to relax any liquid between the isolation valves and other package
flange and pipe stress, then carefully remove the motor. valves to prevent injury or damage to components.
Similarly, before removing the compressor for servicing, SLOWLY vent separator to low-side system pressure
the back end of the motor must be supported to prevent using the suction check valve bypass.
damage. Again, insert either blocks or a jack between the
rear of the motor and the separator shell.
NOTICE
GENERAL INSTRUCTIONS FOR REPLACING Recover or transfer all refrigerant vapor, in accordance
COMPRESSOR UNIT COMPONENTS with local ordinances, before opening to atmosphere. The
separator MUST be equalized to atmospheric pressure.
When replacing or repairing components which are
exposed to refrigerant, proceed as follows:
1. Push [STOP] key to shut down the unit. CAUTION
2. Open disconnect switches for compressor motor starter Oil entrained refrigerant may vaporize, causing a
and oil pump motor starter (if applicable). sepa-rator pressure increase. Repeat transfer and
recovery procedure, if necessary.
3. Isolate the package by closing all package valves to the
system. Tag all closed valves. 3. Remove spin-on oil filter element and discard.
CAUTION NOTICE
Open any solenoid valves or other valves that may trap Use of oil filters other than Frick may cause
liquid between the isolation valves and other package warranty claim to be denied.
valves to prevent injury or damage to components.
4. Replace with new oil filter element. Make finger tight
4. SLOWLY vent separator to low-side system pressure plus an additional half turn.
using the suction check valve bypass. 5. Isolate the low pressure transducer, PE-4, to prevent
dam-age during pressurization and leak test.
NOTICE 6. Pressurize and leak test.
Recover or transfer all refrigerant vapor, in 7. Evacuate unit to 29.88" Hg (1000 microns).
accordance with local ordinances, before opening to
atmosphere. The separator MUST be equalized to 8. Open the suction and discharge service valves, and the
atmospheric pressure. low pressure transducer. Close disconnect switches for
the compressor. Start the unit.
OIL FILTER (OF-1) CARTRIDGE STYLE (58 – 101)
CAUTION RXF compressor units are furnished with one main oil filter
Oil entrained refrigerant may vaporize, causing a (OF-1). A second oil filter (OF-2) is installed as optional
sepa-rator pressure increase. Repeat transfer and equipment to facilitate the changing of the filter element(s)
recovery procedure, if necessary. without unit shutdown.
5. Make replacement or repair.
6. Isolate the low pressure transducer, PE-4, to prevent NOTICE
dam-age during pressurization and leak test.
Use of oil filters other than Frick may cause
7. Pressurize unit and leak test. warranty claim to be denied.
8. Evacuate unit to 29.88" Hg (1000 microns). To change the filter cartridge proceed as follows:
9. Open all valves previously closed and reset solenoid 1. If a single oil filter is installed, push [STOP] key to shut
valves to automatic position. Remove tags. down the unit. Open disconnect switches for the
10. Close disconnect switches for compressor motor compressor and (if applicable) oil pump motor starters.
starter and oil pump motor starter, if applicable. If dual oil filters are installed, open the outlet, then inlet
11. Unit is ready to put into operation. service valves of the standby filter.
3. Open bleed valve and purge pressure from the oil filter
CAUTION
cartridge. Oil entrained refrigerant may vaporize, causing a
4. Close discharge service valve. SLOWLY vent the separator separa tor pressure increase. Repeat transfer and
to low-side system pressure using the suction check valve recovery procedure, if necessary.
bypass. Close suction valve and suction check valve bypass. 3. Close strainer isolation valves. Remove the large plug
from the bottom of the strainer and remove the element
NOTICE from the strainer.
Recover or transfer all refrigerant vapor, in accordance 4. Wash the element in solvent and blow clean with air.
with local ordinances, before opening to atmosphere. The
separator MUST be equalized to atmospheric pressure. 5. Replace the cleaned element and removed plug. Open
strainer isolation valves.
6. Isolate the low pressure transducer, PE-4, to prevent
CAUTION dam-age during pressurization and leak test.
Oil-entrained refrigerant may vaporize, causing a 7.Pressurize and leak test. Evacuate unit to 29.88" Hg
pres-sure increase. Repeat venting and recovery (1000 microns).
procedure, if necessary.
8. Open the suction and discharge service valves, and the
5. Close oil filter isolation valves. Open drain valve on oil low pressure transducer. Close disconnect switches for
filter head and drain the oil. Remove the canister cover. the compressor. Start the unit.
Discard the cartridge and gasket.
LIQUID INJECTION STRAINER
6. Flush the filter body with clean Frick refrigeration oil;
To clean the liquid injection strainer the unit must be shut
wipe dry with a clean, lint-free cloth; and close drain valve.
down. The procedure is as follows:
7. Place a new cartridge in the filter canister. Replace the
gasket and spring and reinstall the canister cover. Torque 1. Push [STOP] key to shut down the unit, then open
cover bolts in sequence to: a. Finger tight discon nect switches for the compressor.
b. 17 ft-lb 2. Close the liquid supply service valve located before the
c. 35 ft-lb liquid solenoid.
8. Isolate the low pressure transducer, PE-4, to prevent 3. Immediately screw in the manual solenoid valve
damage during pressurization and leak test. stem to relieve liquid refrigerant pressure trapped
between the solenoid and the service valve.
9. Pressurize and leak test.
4. Close the service valve located between the compressor
10. Evacuate the unit to 29.88" Hg (1000 microns).
and the liquid injection thermal expansion valve.
11. Add 2 gallons of oil by attaching a suitable pressure-type
5. Carefully loosen capscrews securing the strainer cover
hose to the oil-charging valve located on top of the separator.
to the strainer. Allow pressure to relieve slowly.
Use a pressure-type oil pump and recommended Frick oil.
6. When all entrapped refrigerant has been relieved, carefully
12. Open the suction and discharge service valves, oil filter
remove loosened capscrews (as liquid refrigerant is sometimes
isolation valves, and the low pressure transducer.
caught in the strainer), strainer cover, and strainer basket.
Readjust suction check valve bypass. Close disconnect
switches for the compressor and (if applicable) the oil 7. Wash the strainer basket and cover in solvent and blow
pump motor start-ers. Start the unit. clean with air.
1. Push [STOP] key to shut down the unit. Open 9. Open the service valve between the compressor and
disconnect switches for the compressor. the liquid injection thermal expansion valve, purge
entrained air, and check for leakage.
2. Isolate the package by closing all package valves to the
system. Tag all closed valves. 10. Screw out the manual solenoid valve stem.
11. Carefully open the liquid supply service valve.
CAUTION 12. Leak test.
Open any solenoid valves or other valves that may trap
13. Close disconnect switches for compressor starter.
liquid between the isolation valves and other package
valves to prevent injury or damage to components. 14. Start the unit.
SLOWLY vent separator to low-side system pressure
using the suction check valve bypass. OIL PUMP STRAINER (Optional)
To clean the full-lube oil pump strainer, the unit must be
NOTICE shut down. The procedure is as follows:
1. Push [STOP] key to shut down the unit, then open the
Recover or transfer all refrigerant vapor, in accordance
disconnect switches for the compressor and (if applicable)
with local ordinances, before opening to atmosphere. The the oil pump motor starters.
separator MUST be equalized to atmospheric pressure.
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 26 MAINTENANCE
2. Close strainer service valves. 6. Replace coalescer filter retainer and nut. Tighten the nut
to 21 ft-lb torque. DO NOT OVERTIGHTEN NUT.
3. Open the drain valve located in the strainer cover and Excessive torque can damage the element and result in oil
drain the oil into a container. carryover. Install jam nut and tighten.
4. Remove the capscrews securing the strainer cover, 7. Install a new head gasket and replace the coalescer head.
strainer cover gasket, and element. Retain the gasket.
8. Tighten the head bolts, first to finger tight, then 65 ft-lb,
5. Wash the element in solvent and blow it clean with air. then 130 ft-lb.
6. Wipe the strainer body cavity clean with a lint-free clean cloth.
CAUTION
If the strainer is installed backwards, it will be damaged.
Figure 31 Figure 32
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
MAINTENANCE Page
29
4. Place tapered installation sleeve on shaft. Refer to Figure AS, AK, AL: Install the ball bearing into the bearing housing.
32. Sleeve is furnished with GG, AS, AK, and AL replacement Install the lip seal in the bearing housing end cap. The lip
mechanical seals. Coat rotor shaft, tapered installation sleeve, should face towards the end of the shaft. Put the bearing
and inner diameter of mechanical seal rotary member with a spacer collar in the lip seal and install in the bearing housing
generous amount of refrigeration oil. Petrolatum may be used and tighten the set screws securely. See Figure 30.
but grease is not recommended. 16. Insert a brass bar or piece of hardwood through the
5. Place seal spring on the shaft against the rotor hub. port opening between the rotor teeth to keep the shaft
Refer to Figure 32. from turning.
6. Slide rotary member, with lapped contact surface facing 17.Start the thrust bearing assembly into casing. Turn by hand
away from the spring, over installation sleeve on shaft until until tight. This forces the rotor against the head. Replace and
just contacting the spring. Do not compress the spring. tighten the locknut or shaft.
Re-move the installation sleeve. 18. Remove the brass bar or hardwood from port opening.
7.Coat the rotor shaft with refrigeration oil. Install the rotor 19. Adjust pump end clearance, refer to “Thrust Bearing
and shaft into the casing, slowly pushing until the ends of Adjustment.”
the rotor teeth are just below the face of the casing. Take
care not to damage the seal seat.
8. Leave the rotor in this position. Withdrawal of rotor and DANGER
shaft may displace the carbon seal rotating face and result BEFORE STARTING PUMP, ENSURE THAT ALL
in damage to the seal. DRIVE EQUIPMENT GUARDS ARE IN PLACE.
9. Place O-ring gasket on the head and install head and idler FAILURE TO PROPERLY MOUNT GUARDS MAY
assembly on pump. Pump head and casing were marked RESULT IN SERIOUS INJURY OR DEATH.
before disassembly to ensure proper reassembly. If not, be
sure the idler pin, which is offset in pump head, is positioned THRUST BEARING ADJUSTMENT
up and equal distance between port connections to allow for Loosen two screws in face of thrust-bearing assembly.
proper flow of liquid through the pump. See Figures 29 or 30.
10. Tighten the head capscrews evenly. If shaft cannot be rotated freely, turn thrust-bearing assembly
11. If the pump was equipped with a relief valve and was counterclockwise until shaft can be turned easily.
removed during disassembly, install on the head with new 1. While turning rotor shaft, rotate thrust-bearing assembly
O-Rings or gaskets. The relief valve adjusting screw cap clockwise until noticeable drag occurs. This is zero end
must always point towards the suction port. clearance.
12.In 2005, the use of single seal bearings were phased 2. Mark position of bearing housing with respect to the casing.
out. Pumps now use “Sealed for Life” bearings that have
3. Rotate thrust-bearing assembly counterclockwise the
seals on both sides. The new bearings can be installed
either side first and do not need to be packed with grease. distance listed below as measured on outside of bearing
For older models with single seal bearings, pack the inner housing.
ball bearing with multi-purpose grease, NLGI #2. 4. Tighten two setscrews in face of bearing housing after
GG, HJ, HL: Drive the bearing into the bore. Tap the inner adjustment is made to secure thrust-bearing assembly
race with a brass bar and lead hammer to position position.
bearing. Install the inner snap ring. For viscosities above 2500 SSU, add additional end
AS, AK, AL: Install the bearing retainer washer over the shaft clearance (0.004" for GG, HJ and HL size pumps and
before installing the ball bearing. Install the ball bearing in the 0.005" for AS, AK and AL size pumps).
casing with sealed side towards head end of the pump. Drive Pump Distance (in.) on O.D. End Clearance
the bearing into the bore. Tap the inner race with a brass bar
Size of Bearing Housing (in.)
and lead hammer to position the bearing.
GG 7/16 .003
13. GG, HJ, HL: Install the shaft snap ring in groove in the
shaft. See Figure 29. HJ, HL 9/16 .003
AS, AK, AL 1/2 .003
AS, AK, AL: Install the bearing spacer over the shaft and
against the single row ball bearing. See Figure 30. INSTALLATION OF CARBON GRAPHITE BUSHINGS
14. Pack the lubrication chamber between the inner ball When installing carbon graphite bushings, extreme care
bearing and double row ball bearing in the thrust bearing must be taken to prevent breaking. Carbon graphite is a
as-sembly approximately one-half full of multi-purpose brittle material and easily cracked. If cracked, the bushing
grease, NLGI #2. The thrust bearing assembly will take will quickly disintegrate. Using a lubricant and adding a
the remaining space. See Figures 29 or 30. chamfer on the bushing and the mating part will help in
15. Pack the double row ball bearing with multipurpose installation. The additional precautions listed below must
grease, NLGI #2. be followed for proper installation:
GG, HJ, HL: Install the ball bearing into the bearing 1. A press must be used for installation.
housing with shield side toward the coupling end of the 2. Be certain bushing is started straight.
shaft. See Figure 29. Install the snap ring into bearing
3. Do not stop pressing operation until bushing is in proper
housing to retain ball bearing. This snap ring has a
tapered edge to fit tapered groove in bearing housing. The position. Starting and stopping will result in a cracked bushing.
tapered edge is located away from the ball bearing. 4. Check bushing for cracks after installation.
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 30 MAINTENANCE
TROUBLESHOOTING THE DEMAND PUMP Some of the following may also help pinpoint the problem:
1. Pump does not pump.
DANGER a. Lost its prime - air leak, low level in tank.
b. Rotating in wrong direction.
BEFORE OPENING ANY VIKING PUMP LIQUID
c. Motor does not come up to speed.
CHAM-BER (PUMPING CHAMBER, RESERVOIR, d. Suction and discharge valves not open.
JACKET, ETC.) ENSURE: e. Strainer clogged.
1. THAT ANY PRESSURE IN THE CHAMBER HAS f. Relief valve set too low, relief valve poppet stuck open.
BEEN COMPLETELY VENTED THROUGH SUCTION g. Pump worn out.
OR DIS-CHARGE LINES OR OTHER APPROPRIATE h. Any changes in the liquid system, or operation that
OPENINGS OR CONNECTIONS. would help explain the trouble, e.g. new source of
2. THAT THE DRIVING MEANS (MOTOR, TURBINE, supply, added more lines, inexperienced operators,
ENGINE, ETC.) HAS BEEN “LOCKED OUT” OR MADE etc.
NONOPERATIONAL SO THAT IT CANNOT BE STARTED i. Tighten end clearance.
WHILE WORK IS BEING DONE ON THE PUMP. j. Head position incorrect.
FAILURE TO FOLLOW ABOVE LISTED PRECAUTIONARY 2. Pump starts, then loses its prime.
MEASURES MAY RESULT IN SERIOUS INJURY OR DEATH. a. Low level in tank.
b. Liquid vaporizing in the suction line.
Mark valve and head before disassembly to ensure proper c. Air leaks or air pockets in the suction line; leaking air
reassembly. through packing or mechanical seal.
If trouble does develop, one of the first steps toward find- d. Worn out.
ing the difficulty is to install a vacuum gauge in the suction 3. Pump is noisy
port and a pressure gauge in the discharge port. Readings a. Pump is being starved (heavy liquid cannot get to
on these gauges often will give a clue as to where to start pump fast enough). Increase suction pipe size or
looking for the trouble. reduce length.
b. Pump is cavitating (liquid vaporizing in the suction
Vacuum Gauge—Suction Port line). Increase suction pipe size or reduce length; if
1. High reading would indicate: pump is above the liquid, raise the liquid level closer
a. Suction line blocked - foot valve stuck, gate valve to the pump; if the liquid is above the pump,
closed, strainer plugged. increase the head of liquid.
b. Liquid too viscous to flow through the piping. c. Check alignment.
c. Lift too high. d. May have a bent shaft or rotor tooth. Straighten or
d. Line too small. replace.
2. Low reading would indicate - e. May be a foreign object trying to get into the pump
a. Air leak in suction line. through the suction port.
b. End of pipe not in liquid. 4. Pump not up to capacity
c. Pump is worn. a. Starving or cavitating - increase suction pipe size or
d. Pump is dry - should be primed. reduce length.
3. Fluttering, jumping, or erratic reading: b. Strainer partially clogged - clean.
a. Liquid vaporizing. c. Air leak in suction piping or along pump shaft.
b. Liquid coming to pump in slugs - possibly an air leak or d. Running too slowly - is motor the correct speed and
insufficient liquid above the end of the suction pipe. is it wired up correctly
c. Vibrating from cavitation, misalignment, or damaged e. Relief valve set too low or stuck open.
parts. f. Pump worn out.
g. Tighten end clearance.
Pressure Gauge - Discharge Port h. Head position incorrect.
1. High reading would indicate: 5. Pump takes too much power.
a. High viscosity and small and/or long discharge line. a. Running too fast - is correct motor speed, reducer
b. Gate valve partially closed. ratio, sheave size, etc. being used.
c. Filter plugged. b. Liquid more viscous than unit sized to handle - heat
d. Vertical head did not consider a high specific gravity the liquid, increase the pipe size, slow the pump
liquid. down, or get a bigger motor.
e. Line partially plugged from buildup on inside of pipe. c. Discharge pressure higher than calculated - check with
f. Liquid in pipe not up to temperature. pressure gauge. Increase size or reduce length of pipe,
g. Liquid in pipe has undergone a chemical reaction reduce speed (capacity), or get bigger motor.
and has solidified. d. Pump misaligned.
h. Relief valve set too high. e. Extra clearance on pumping elements may not be
2. Low reading would indicate: sufficient for operating conditions. Check parts for
a. Relief valve set too low evidence of drag or contact in pump and increase
b. Relief valve poppet not seating properly. clearance where necessary
c. Too much extra clearance. 6. Rapid Wear.
d. Pump worn.
Examination of a pump that has gradually lost its ability to
3. Fluttering, jumping, or erratic reading: deliver capacity or pressure would show a smooth wear pat-
a. Cavitation. tern on all parts. Rapid wear shows up as heavy grooving,
b. Liquid coming to pump in slugs. galling, twisting, breaking, or similar severe signs of trouble.
c. Air leak in suction line.
d. Vibrating from misalignment or mechanical problems.
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
MAINTENANCE Page
31
RECOMMENDED MAINTENANCE PROGRAM the 6 month vibration analysis is not required. Frick PhD
provides continuous vibration monitoring that fulfills the
In order to obtain maximum compressor unit performance
maintenance requirement. Should the Frick PhD have an
and ensure reliable operation, a regular maintenance
alarm or shut down event, a full spectrum vibration
program should be followed (see Maintenance Schedule):
analysis would then be required to specifically identify the
The compressor unit should be checked daily for leaks, cause of the alarm or shut down.
ab-normal vibration, noise, and proper operation. A log
In addition, a Frick compressor package without PhD
should also be maintained. Initial oil analysis and vibration
moni-toring already in operation can be retrofitted with the
analysis should be done at start-up and continued per the
Frick PhD on- board vibration monitoring system to fulfill
mainte-nance schedule.
the vibration maintenance recommendation. However, it is
Vibration analysis is recommended every 6 months to ensure also necessary to establish a current baseline vibration
that the internal components of the screw compressor are in with a full spectrum analysis in order for the PhD retrofit to
compliance with expected vibration levels, based on the initial, be compliant.
full spectrum baseline performed at start-up. If the Frick PhD
on-board vibration monitoring system is utilized,
MAINTENANCE SCHEDULE
Recommended schedule for Frick screw compressor package preventive maintenance operations.
FREQUENCY OR HOURS OF OPERATION (MAXIMUM)
10,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
90,000
15,000
25,000
35,000
45,000
55,000
65,000
75,000
85,000
95,000
1000
5000
8000
200
MAINTENANCE
VIBRATION ANALYSIS 1. Only use Frick® oil filter elements or warranty claim
Periodic vibration analysis can be useful in detecting may be denied.
bearing wear and other mechanical failures. If vibration 2. Participate in a regular, periodic oil analysis program to
analysis is used as a part of your preventive maintenance maintain oil and system integrity. Oil Analysis Kit part
program, take the following guidelines into consideration. num-ber: 333Q0001853.
1. Always take vibration readings from exactly the same 3. Oil samples for analysis should be taken after the oil filter. A
places, at exactly the same percent of load. ¼" purge valve is provided between the filter and compressor.
2. Use vibration readings taken from the new unit at
start-up as the base line reference.
MOTOR BEARINGS
3. Evaluate vibration readings carefully as the instrument
range and function used can vary. Findings can be easily CAUTION
misinterpreted. Lubricate motor bearings properly before start- up.
4. Vibration readings can be influenced by other Maintain subsequent lubrication as recommended
equipment operating in the vicinity or connected to the by the motor manufacturer. See Figure 33.
same piping as the unit. For additional information,
request Frick publica-tion 070.902-IB.
® OPERATING LOG
OIL QUALITY and ANALYSIS The use of an operating log, as shown in this manual (see
Table of Contents...FORMS), permits thorough analysis of
High quality refrigeration oil is necessary to ensure the operation of a refrigeration system by those
compres sor longevity and reliability. Oil quality will rapidly responsible for its maintenance and servicing. Continual
deteriorate in refrigeration systems containing moisture recording of gauge pressures, temperatures, and other
and air or other contaminants. In order to ensure the pertinent informa-tion enables the observer and
quality of the refrigera tion oil in the compressor unit. serviceman to be constantly familiar with the operation of
the system and to recognize immediately any deviations
WARNING from normal operating condi-tions. It is recommended that
readings be taken at least every four hours.
DO NOT MIX OILS of different brands, manufacturers,
or types. Mixing of oils may cause excessive oil TROUBLESHOOTING GUIDE
foaming, nuisance oil level cutouts, oil pressure loss,
gas or oil leakage and catastrophic compressor failure. Successful problem solving requires an organized approach
to define the problem, identify the cause, and make the proper
correction. Sometimes it is possible that two relatively obvi-
NOTICE ous problems combine to provide a set of symptoms that can
The Frick oil charge shipped with the unit is the best mislead the troubleshooter. Be aware of this possibility and
suited lubricant for the conditions specified at the time avoid solving the “wrong problem”.
of purchase. If there is any doubt due to the refrigerant,
operating pressures, or temperatures, refer to Frick Oil
publication 160.802-SPC for guidance.
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
MAINTENANCE Page
33
TRANSDUCER CONNECTION
NOTICE Suction Pressure PE-4
To change the discharge pressure transducer (PE-3), it will Discharge Pressure PE-3
be necessary to depressurize the entire compressor Oil Pressure PE-1 & PE-2
package. Follow "General Instructions For Replacing Com-
5. Unscrew the transducer using a wrench on the metal hex at
pressor Unit Components" section before going to step 3.
the base of the transducer. DO NOT ATTEMPT TO LOOSEN
OR TIGHTEN TRANSDUCERS BY THEIR TOP CASING.
CABLE COLOR CODE 6. Install new transducer, reconnect DIN connector, and
1 PIN 1 + SUPPLY retighten DIN connector screw.
PIN 2 DC COMMON 7. Recalibrate.
3
2 PIN 3 SIGNAL
NOTICE
CASE GND If replacing older hard-wired transducer, cut cable at
back of old transducer and rewire to the Danfoss unit.
Figure 34 - Pressure Transducer Color Key
8. Reopen the transducer isolation valve or compressor
3. Refer to Figure 34 to identify wiring harness connectors. package isolation valves.
4. Remove DIN connector screw, then remove DIN connector
9. Turn on control power.
from the transducer.
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
MAINTENANCE Page
35
NOTICE
For calibration of the Slide Valve unit, refer to the Ana-
log Calibration instructions in publication 090.040-O.
OIL TEMPERATURE System conditions rapidly fluctuate causing liquid injection system to overrespond. Stabilize
FLUCTUATES system operation.
Check calibration and operation of motor valve - Adjust P & ID setpoints for analog output.
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
MAINTENANCE Page 37
SLIDE VALVE WILL LOAD BUT YY1 solenoid coil burned out. Replace coil.
WILL NOT UNLOAD
Check valve in solenoid valve piston bad. Replace or repair.
Dirt inside solenoid valve preventing valve from operating both ways. Clean valve.
Solenoid may be mechanically actuated by inserting a piece of 3/16" rod against armature pin and pushing
spool to opposite end. Push YY1 valve to confirm unload capability. If valve works, problem is electrical.
Slipper seals worn out or damaged. Replace.
Check valve in slide valve piston sticking. Remove and clean check valve.
SLIDE VALVE WILL UNLOAD YY2 solenoid coil burned out. Replace coil.
BUT WILL NOT LOAD
Dirt inside solenoid valve preventing valve from operating both ways. Clean valve.
Solenoid may be mechanically actuated by inserting a piece of 3/16" rod against armature pin
and pushing spool to opposite end. If valve works, the problem is electrical.
SLIDE STOP WILL NOT FUNC- Solenoid coil burned out. Replace coils.
TION IN EITHER DIRECTION
Solenoid valve sticking. Replace valve.
SLIDE VALVE and/or SLIDE Slipper seals worn out or damaged.
STOP WILL NOT MOVE
Unloader spindle or slide valve jammed.
Slide stop indicator rod jammed.
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 38 MAINTENANCE
SAE STRAIGHT THREAD O-RING FITTINGS - ASSEMBLY PROCEDURE FOR RXF 58 - 101
When performing maintenance or replacing the compres- 1. Inspect components to ensure that male and female
sor, the hydraulic tubing may need to be removed and re- port threads and sealing surfaces are free of burrs, nicks
installed. The following procedure outlines the proper and scratches or any foreign material.
installation of SAE straight thread fittings to SAE straight
thread ports. 2. If the O-ring is not pre-installed to the fitting on the
male end, install the proper size O-ring.
The male and female ends of SAE straight thread O-ring ports
have UN/UNF straight threads. An elastomeric O-ring is fitted 3. Lubricate the O-ring with a light coating of system oil or
to the male end. On assembly, the O-ring is firmly sandwiched petroleum jelly.
between the angular sealing surface of the fe-male port and
4. Screw the fitting into the female port until the hex flat
the shoulder of the male end. Sealing is thus affected and
contacts the port face. Light wrenching may be necessary.
maintained by the O-ring compression which results from the
clamping force generated by the tightening action. The 5. Tighten to the appropriate torque value shown in the
straight threads do not offer sealing action; they provide the Assembly Torque Table.
resistance (holding power) for service pressure.
NOTE: Compressor port locations for RXF 58 -101 are located on the following page.
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
MAINTENANCE Page 41
COMPRESSOR
DRIVE SHAFT
TUBING LINE
SIGHT
SOLENOID GLASS
VALVE MOTORIZED
STRAINER EXPANSION
S VALVE
LIQUID REFRIGERANT
FROM RECEIVER
LIQUID LINE
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 42 MAINTENANCE
TUBING LINE
SOLENOID
VALVE MOTORIZED
EXPANSION
STRAINER VALVE
S
LIQUID REFRIGERANT
FROM RECEIVER
LIQUID
LINE SIGHT
GLASS
YY
9
COMPRESSOR COMPRESSOR
S
SUCTION PRESS. LOW VI
COMPRESSOR
HIGH VI TUBING LINE
TO SEPARATOR
SOLENOID
VALVE MOTORIZED
EXPANSION
STRAINER VALVE
S
LIQUID REFRIGERANT
FROM RECEIVER
LIQUID
LINE SIGHT GLASS
RXF MODELS 12 through 19 without OIL PUMP (See OIL COOLING ADDITIONS)
LEGEND*
C COMPRESSOR PE PRESSURE ELEMENT XE VIBRATION ELEMENT
CV CHECK VALVE PI PRESSURE INDICATOR XAH VIBRATION HIGH ALARM
F FILTER OR FILTER DRIER PIC/TIC PRESS./TEMP. INDICATING CONTROLLER XAHH VIBRATION HIGH SHUTDOWN
HTR HEATER PM PUMP MOTOR ZT POSITION TRANSMITTER
LG SIGHT OR LEVEL GLASS PSV PRESSURE SAFETY VALVE ZI POSITION INDICATOR
LSL OIL LEVEL SWITCH LOW PV PRESSURE VESSEL
LSLL LOW OIL LEVEL SHUTDOWN STR STRAINER * Continued following page
M MOTOR TAH HIGH TEMPERATURE ALARM
NV NEEDLE VALVE TAHH HIGH TEMP. SHUTDOWN
P PUMP TAL LOW TEMPERATURE ALARM
PAH HIGH PRESSURE ALARM TALL LOW TEMPERATURE SHUTDOWN
PAHH HIGH PRESSURE SHUTDOWN TCV TEMPERATURE CONTROL VALVE
PAL LOW PRESSURE ALARM TE TEMPERATURE ELEMENT
PALL LOW PRESSURE SHUTDOWN YY SOLENOID VALVE/EVENT VALVE
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 44 MAINTENANCE
RXF MODELS 12 through 19 with OIL PUMP (See OIL COOLING ADDITIONS)
LEGEND (Cont.)
CONNECTIONS ** NOTES:
1 MAIN OIL SUPPLY 1. PRESSURE TRANSDUCERS INDICATE:
2 SLIDE VALVE PISTON PE-1 OIL PRESSURE
7 SUCTION PRESSURE PE-3 DISCHARGE PRESSURE
10 DISCHARGE PRESSURE PE-4 SUCTION PRESSURE
11 LIQ. INJ. BLEED LINE 2. TEMPRERATURE PROBES INDICATE:
12 COALESCER BLEED LINE TE-1 SUCTION GAS TEMPERATURE
16 THERMOWELL TE-2 DISCHARGE GAS TEMPERATURE
18 MAIN OIL INJECTION TE-3 LUBE OIL TEMPERATURE
22 CAPACITY VALVE VENT TO SUCTION TE-4 SEPARATOR OIL TEMPERATURE
3. TERMINATIONS "A" THROUGH "C" REFER TO
** Not all ports are shown. See COMPRESSOR CONNECTION POINTS FOR VARIOUS OPTIONS.
PORT LOCATIONS for all ports.
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
MAINTENANCE Page
45
RXF MODELS 24 throughy 50 without OIL PUMP (See OIL COOLING ADDITIONS)
LEGEND*
C COMPRESSOR PE PRESSURE ELEMENT ZT POSITION TRANSMITTER
CV CHECK VALVE PI PRESSURE INDICATOR ZI POSITION INDICATOR
F FILTER OR FILTER DRIER PIC/TIC PRESS./TEMP. INDICATING CONTROLLER
HTR HEATER PM PUMP MOTOR * Continued following page
LG SIGHT OR LEVEL GLASS PSV PRESSURE SAFETY VALVE
LSL OIL LEVEL SWITCH LOW PV PRESSURE VESSEL
LSLL LOW OIL LEVEL SHUTDOWN STR STRAINER
M MOTOR TAH HIGH TEMPERATURE ALARM
NV NEEDLE VALVE TAHH HIGH TEMP. SHUTDOWN
P PUMP TAL LOW TEMPERATURE ALARM
PAH HIGH PRESSURE ALARM TALL LOW TEMPERATURE SHUTDOWN
PAHH HIGH PRESSURE SHUTDOWN TCV TEMPERATURE CONTROL VALVE
PAL LOW PRESSURE ALARM TE TEMPERATURE ELEMENT
PALL LOW PRESSURE SHUTDOWN YY SOLENOID VALVE/EVENT VALVE
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 46 MAINTENANCE
RXF MODELS 24 through 50 with OIL PUMP (See OIL COOLING ADDITIONS)
LEGEND (Cont.)
CONNECTIONS ** NOTES:
1 MAIN OIL SUPPLY 1. PRESSURE TRANSDUCERS INDICATE:
2 SLIDE VALVE PISTON PE-1 OIL PRESSURE
7 SUCTION PRESSURE PE-3 DISCHARGE PRESSURE
10 DISCHARGE PRESSURE PE-4 SUCTION PRESSURE
11 LIQ. INJ. BLEED LINE 2. TEMPRERATURE PROBES INDICATE:
12 COALESCER BLEED LINE TE-1 SUCTION GAS TEMPERATURE
16 THERMOWELL TE-2 DISCHARGE GAS TEMPERATURE
19 SUCTION PRESSURE TE-3 LUBE OIL TEMPERATURE
22 CAPACITY VALVE VENT TO SUCTION TE-4 SEPARATOR OIL TEMPERATURE
3. TERMINATIONS "A" THROUGH "C" REFER TO
** Not all ports are shown. See COMPRESSOR CONNECTION POINTS FOR VARIOUS OPTIONS.
PORT LOCATIONS for all ports.
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
MAINTENANCE Page
47
RXF MODELS 58, 68, 85, & 101 without OIL PUMP (See OIL COOLING ADDITIONS)
LEGEND *
C COMPRESSOR PE PRESSURE ELEMENT TE TEMPERATURE ELEMENT
CV CHECK VALVE PI PRESSURE INDICATOR TI TEMPERATURE INDICATOR
HTR HEATER PIC/TIC PRESS./TEMP. INDICATING CONTROLLER YY SOLENOID VALVE/EVENT VALVE
LG SIGHT OR LEVEL GLASS PM PUMP MOTOR
M MOTOR PSV PRESSURE SAFETY VALVE * See additional Legend items on opposite
OF OIL FILTER STR STRAINER
P PUMP TAH HIGH TEMPERATURE ALARM page.
PAH HIGH PRESSURE ALARM TAHH HIGH TEMP. SHUTDOWN
PAHH HIGH PRESSURE SHUTDOWN TAL LOW TEMPERATURE ALARM
PAL LOW PRESSURE ALARM TALL LOW TEMPERATURE SHUTDOWN
PALL LOW PRESSURE SHUTDOWN TCV TEMPERATURE CONTROL VALVE
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 48 MAINTENANCE
RXF Models 58, 68, 85, & 101 with OIL PUMP and DUAL OIL FILTERS (See OIL COOLING ADDITIONS)
LEGEND (Cont.)
CONNECTIONS NOTES:
1 MAIN OIL SUPPLY 16 OIL PRESSURE 1. PRESSURE TRANSDUCERS INDICATE:
2 SLIDE VALVE PISTON 18 CAPACITY VENT VALVE TO SUCTION PE-1 OIL PRESSURE
6 SUCTION PRESSURE PE-3 DISCHARGE PRESSURE
8 DISCHARGE PRESSURE ** Not all ports are shown. See COMPRESSOR PE-4 SUCTION PRESSURE
9 LIQ. INJ. BLEED LINE PORT LOCATIONS for all ports. 2. TEMPRERATURE PROBES INDICATE:
10 COALESCER BLEED LINE TE-1 SUCTION GAS TEMPERATURE
11 THERMOWELL (SUCT. TEMP.) TE-2 DISCHARGE GAS TEMPERATURE
12 MAIN OIL INJECTION TE-3 LUBE OIL TEMPERATURE
13 SUCTION PRESSURE TE-4 SEPARATOR OIL TEMPERATURE
3. TERMINATIONS "A" THROUGH "C" REFER TO CONNEC-
TION POINTS FOR VARIOUS OPTIONS.
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV
MAINTENANCE 2015) Page 49
WIRING HARNESS - External for Analog Devices
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 50 MAINTENANCE
NOTICE
It is very important to read the installation instructions
thoroughly before beginning the project. Make sure you
have drawings and instructions with your equipment. If
not, call the manufacturer and request the proper
instructions and drawings. Every manufacturer of elec-
tronic equipment should have a knowledgeable staff,
willing to answer your questions or provide additional
information. Following correct wiring procedures will
ensure proper installation and consequently, proper
operation of your electronic equipment.
WIRE SIZING
Control power supply wires should be sized one size larger
than required for amperage draw to reduce instanta-neous
voltage dips caused by large loads such as heaters,
contactors, and solenoids. These sudden dips in voltage can
cause the electronic control panel, whether it is a micropro- Figure 38
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 52 PROPER INSTALLATION OF ELECTRICAL EQUIPMENT
GROUNDING NEC size ratings are for safety purposes and not necessarily
for adequate relaying of noise (EMI) to earth ground to avoid
Grounding is the most important factor for successful opera- possible interference with sensitive equipment. Therefore
tion and is typically the most overlooked. The NEC states that sizing this conductor 1 – 2 sizes larger than required by code
control equipment may be grounded by using the rigid conduit will provide better transfer of this noise.
as a conductor. This worked for the earlier relay systems, but
it is in no way acceptable for electronic control equipment. Frick requirements for the ground conductor are:
Conduit is made of steel and is a poor conductor relative to an • Stranded Copper
insulated stranded copper wire. Electronic equipment reacts
• Insulated
to very small currents and must have a proper ground in order
to operate properly; therefore, stranded copper grounds are • One size larger than NEC requirements for
required for proper operation.
conventional starters
• Two sizes larger than NEC requirements for VFD starters
For proper operation, the control power ground circuit must be
• Conduit must be grounded at each end
a single continuous circuit of the proper sized insulated
stranded conductor, from the electronic control panel to the • This circuit must be complete from the motor to the
plant supply transformer (Figure 39). Driving a ground stake starter continuing in a seamless manner back to the
plant supply transformer (power source).
at the electronic control may also cause additional problems
since other equipment in the plant on the same circuits may For Direct Coupled, Package Mounted Starters, the ground
ground themselves to the ground stake causing large ground between the motor and the starter may need to be made
flow at the electronic control panel. Also, running multiple externally (Figure 40). The connection on the starter end must
ground conductors into the electronic control panel from be on the starter side of the vibration isolators. Be certain the
various locations can create multiple potentials resulting in connection is metal to metal. Paint may need to be removed
ground loop currents. A single ground wire (10 AWG or 8 to ensure a proper conductive circuit. The use of counter-sunk
AWG) from the electronic control panel, that is bonded to the star washers at the point of connec-tion at each end will
control power neutral at the secondary side of the control maximize metal to metal contact.
power transformer in the starter and then to the 3-phase
ground point, will yield the best results.
Figure 40
Figure 39
VFD APPLICATIONS
To install correctly, run a separate, properly sized (10 or 8 electrical ducts carrying 3-phase power to starters/vfd or
AWG typically) insulated ground along with and taken to motors.
ground with, the 3-phase ground at the 3-phase supply • Control power, communications, analog, or signal wiring
transformer (plant). This will require that the 3-phase ground should be run overhead (preferred) or in a separate
and the control power ground be electrically isolated except trench. If these lines are not in threaded metallic or
for the connection at the plant supply transformer. threaded PVC-coated metallic, abiding by the
This style of grounding should steer the noise (EMI/RFI) to separation requirements noted above is necessary.
earth ground, reducing the potential for it to affect the • Though not recommended, if cable trays are used,
sensitive equipment, which could occur if the grounds metallic dividers must be used for separation of
were left coupled. conductors of unlike voltages and types (AC or DC).
NOTICE NOTICE
If all other recommendations for grounding are When in doubt contact the factory or use threaded
followed, this process should not be necessary. metallic or threaded PVC coated metallic conduit.
Do not drill into an electronic control panel to locate conduit If the electronic control panel has a starter built into the
connections. You are probably not entering the panel where same panel, be sure to run the higher voltage wires where
the manufacturer would like you to since most manufactur-ers indicated by the manufacturer. EMI from the wires can
recommend or provide prepunched conduit connections. You interfere with the electronics if run too close to the circuitry.
may also be negating the NEMA rating of the enclosure.
Drilling can cause metal filings to land on the electronics and Never daisy-chain or parallel-connect power or ground
create a short circuit when powered is applied. If you must wires to electronic control panels. Each electronic control
drill the panel, take the following precautions: panel must have its own control power supply and ground
wires back to the power source (Plant Transformer). Multiple
• First, call the panel manufacturer before drilling into the electronic control panels on the same power wires create
panel to be sure you are entering the panel at the right current surges in the supply wires, which may cause control-
place. ler malfunctions. Daisy-chaining ground wires, taking them to
• Take measures to avoid ESD (electrostatic discharge) ground at each device, allows ground loop currents to flow
to the electronics as you prep the inside of the between electronic control panels which also causes
Electronic control panel. This can be done by employing malfunctions. See Figure 42.
an antistatic wrist band and mat connected to ground.
• Cover the electronics with plastic and secure it with
masking or electrical tape.
• Place masking tape or duct tape on the inside of the
panel where you are going to drill. The tape will catch
most of the filings.
• Clean all of the remaining filings from the panel before
removing the protective plastic.
When routing conduit to the top of an electronic control panel,
condensation must be taken into consideration. Water can
condense in the conduit and run into the panel causing
catastrophic failure. Route the conduit to the sides or bottom
of the panel and use a conduit drain. If the conduit must be
routed to the top of the panel, use a sealable conduit fitting
which is poured with a sealer after the wires have been
pulled, terminated, and the control functions have been
checked. A conduit entering the top of the enclosure must
have a NEMA-4 hub type fitting between the conduit and the
enclosure so that if water gets on top of the enclosure it
cannot run in between the conduit and the enclosure. This is
extremely important in outdoor applications.
NOTICE
It is simply NEVER a good practice to enter through the
top of an electronic control panel or starter panel that does
not already have knockouts provided. If knockouts are not
provided for this purpose it is obvious this is not
recommended and could VOID WARRANTY. Figure 42
Never add relays, starters, timers, transformers, etc.
in-side an electronic control panel without first
contacting the manufacturer. Contact arcing and EMI
emitted from these devices can interfere with the
electronics. Relays and timers are routinely added to
electronic control panels by the manufacturer, but the
manufacturer knows the acceptable device types and
proper placement in the panel that will keep interference to
a minimum. If you need to add these devices, contact the
manufacturer for the proper device types and placement.
NOTICE
It is very important to read the installation instructions thoroughly before
beginning the project. Make sure you have drawings and instructions for the
equipment being installed. If not, call the manufacturer to receive the proper
instructions and drawings. Every manufacturer of electronic equipment should
have a knowledgeable staff, willing to answer your questions or provide
additional information. Following correct wiring procedures will ensure proper
installation and consequently, proper operation of your electronic equipment.
070.410-IOM (NOV 2015) RXF ROTARY SCREW COMPRESSOR UNITS
Page 56 FORMS
NOTE: Customer connections are to be made per the electrical diagram for the motor starter listed under
the installation section and per the wiring diagram listed under the maintenance section of the IOM.
Please complete and sign this form & fax to 717-762-8624 as confirmation of completion.
Shaft Side Delay Opposite Shaft Side Delay Step Up Dead Band _________ PSI
High Warning_______ F_____ Sec High Warning_ ______ F_____ Sec Step Up Delay ________ Sec
High Shutdown______ F_____ Sec High Shutdown______ F_____ Sec Step Down Dead Band _________ PSI
Step Down Delay ________ Sec
Motor Stator__________________ High Pressure Override _________ PSI
High Pressure Override Delay_ _____ Sec
Stator 1 Delay Stator 2 Delay
High Warning______F_ ______ Sec High Warning_ _____F_ ______ Sec Analog Controls Analog Output A ____________
High Shutdown_____F_ ______ Sec High Shutdown_____F_ ______ Sec Analog Output B ____________
Proportional Band _________
Stator 3 Delay PSI Integration Time ________
High Warning______F_ ______ Sec Sec High Limit _________ PSI
High Shutdown_____F_ ______ Sec Low Limit ________ Sec
Miscellaneous
Remote Capacity Deadband________ % Max Slide Valve Timer________ 1/10 Sec
High Compressor Oil Pressure _________________ Max Discharge Pressure ____________ PSI
Shutdown_____PSI Delay _____ Sec Max Discharge and Oil Temp_ ________°F
Compressor Inboard
Compressor Outboard (Coupling End Center) Motor Inboard (Coupled End)
(Noncoupled End) Vertical Direction Horizontal _______ . ______ IPS Overall
Axial Direction ____.____ IPS Overall Vertical _______ . ______ IPS Overall
____.____ IPS Overall Axial _______ . ______ IPS Overall
Compressor
Outboard
Vertical Direction
____.____ IPS (Male)
____.____ IPS (Female)
Compressor Inboard
(Jackshaft) Motor Outboard (Noncoupled End)
Horizontal Direction Horizontal _______ . ______ IPS Overall
____.____ IPS Overall Vertical _______ . ______ IPS Overall
Axial _______ . ______ IPS Overall
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (AUG 14)
NOTES Page 63
070.410-IOM (AUG 14) RXF ROTARY SCREW COMPRESSOR UNITS
Page 64 NOTES
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV 2015)
INDEX Page
65
Index
Symbols Idler Pin, 27 Flashing Liquid, 10
3-phase ground, 53 Locknut, 27 Flash Vessel, 10
O-Ring Gasket, 29 Isolation Valve, 10
3-phase supply, 53
Pump, 28 Microprocessor, 10
B Pump Head, 27, 29 Outlet Pressure Regulator, 10
Back Flushing, 9 Bleed Refrigeration Oil, 28 Strainer, 10
Valve, 25 Booster Rotor, 28, 29 Subcooling Liquid, 10
Applications, 15 Rotor Hub, 28 Elastomeric Gear, 6
Brownouts, 13 Rotor Shaft, 29 EMI, 53
Rotor Teeth, 29 External Controller, 11
C Seal, 28 External Oil Cooling, 21
Cable Trays, 53 Seal Housing Bore, 28
Seal Seat, 28 F
Carbon Graphite Bushings, 27, 28,
29 Chemical Cleaning Process, 9 Seal Spring, 29 Filter Elements, 8
CH Coupling Data Table, Snap Ring, 27 Flexible Drive Coupling, 6
6 Clamping Bolts, 7 Spring, 28, 29 Forklift, 6
Closed-Loop Fluids, 9 Tapered Installation Sleeve, 29 Foundation, 3, 5, 14, 51, 56
Closed-Loop System, 9 Thrust-Bearing Assembly, 28 Anchor Bolts, 5
Coalescer, 15 Troubleshooting, 30 Grout, 5
Coalescer Filter Element, 8 Air Leak, 30 Housekeeping Pads, 5
Codes, 53 Alignment, 30 I-Beams, 5
Cold-Start Valve, 14 Cavitation, 30 Pipe Supports, 5
Comm Port, 55 Discharge Port, 30 Reinforced Concrete, 5
Comm Port Protection, 55 Discharge Pressure, 30 Vibration Expert, 5
Communications, 55 End Clearance, 30
Filter, 30 H
Compressor
Discharge, 15 Foot Valve, 30 Hand Expansion Valve, 21
Motor, 11 Gate Valve, 30 Handling And Moving, 5
Compressor Motor Starter, 12 Head, 30 Crane, 5
Compressor Port Locations Misalignment, 30 Forklift, 5
RXF 12 - 19, 38 Motor, 30 Lifting Ring, 6
RXF 24 - 50, 39 Motor Speed, 30 Rigging, 5
RXF 58 - 101, 41 Pressure Gauge, 30 Hard Water Conditions, 9
Compressor Prestart Checklist, 57 Pump, 30 Heat Exchanger, 9
Compressor Shaft, 6, 14 Relief Valve, 30 Heat-Sink Paste, 9
Compressor Unloading, 15 Sheave Size, 30 High-Stage Operation, 14
Compressor Volume Ratio, 15, 16 Strainer, 30 Hydraulic System, 15
Conduit, 53 Suction Line, 30
Suction Pipe, 30 I
Cone/Button, 8
Constant Speed Starters, 53 Suction Port, 30 Initial Start-Up, 21
Constant Voltage (Cv) Transformer, Vacuum Gauge, 30 Inlet Service Valve, 24
55 Control Power Regulator, 13 Valve, 30
Vaporizing, 30 J
Cooling Tower Water, 9 Cooling
Water, 9 Vibrating, 30 Jack, 6
CoolWare™, 21 Differential Pressure, 14
Direct Expansion Economizer System, L
coupling, 11
Current Transformer, 12 11 Liquid Carryover, 7
Cutout Parameters, 15 Direct Motor Drive, 6 Liquid Injection, 9, 17
Discharge Temperature, 21 Analog Input Signal, 19
D Drive Hubs, 6 Danfossliquid Injection Valve, 18
Daisy-Chaining, 55 Dry Nitrogen, 7 Digital Input Signal, 19
Demand Pump DX Economizer, 10 Dual Dip Tube Method, 10
Bearing Retainer Washer, 28 Enter Push Button, 18
E High-Stage Units, 10
Bearings, 28
Bearing Spacer, 27 Economizer ICAD (Industrial Control Actuator
Carbon Graphite Bushings, 29 Back-Pressure Regulator Valve, 10 with Display), 18
Casing, 27, 29 Balancing Load, 10 ICM Valve, 19
End Clearance, 29 Check Valve, 10 Low Condensing Pressures, 10
Head, 27 DX Economizer, 10 Mod, 19
Economizer Port, 10 Motorized Industrial Control Valve,
Idler, 27
18
070.410-IOM (NOV 2015) Page 66
Opening Degree, 19 RXF ROTARY SCREW COMPRESSOR
Parameters, 18 UNITS INDEX
Parameter List, 20
Analog Output Signal, 20 P & I Diagram, 41 Oil Distillers, 7
Automatic Calibration, 20 Pressure Sensors, 35 Oil Filter, 8
Digital Input Function, 20 Pressure Transducers, 33 Oil Heaters, 7
Fail-Safe, 20 Conversion Data, 34 Operating Volume Ratio, 17
ICM Configuration, 20 Replacement, 33 Optical Isolation, 55
Main Switch, 20 Testing, 33 O-Ring Compression, 40
Mode, 20 Refrigerant Vapor, 24, 25
Modulating Mode, 20 Refrigeration Oil, 32 P
Old Alarms, 20 Safety Equipment, 23 pH, 9
Password, 20 Sensor Well, 35 Power Feed, 53 Power
Solenoid Valve, 19 Service Valves, 24 Fluctuations, 13
Liquid Injection Oil Cooling, 21 Spin-On Oil Filter Element, 24 Pressure Differential, 15
Liquid Injection Thermal Expansion Starting Torque, 26 Proper Installation of Electronic
Valve, 21 Strainer Elements, 26 Equip-ment, 51
Liquid Loading, 21 Strainer Service Valves, 26 PVC-Coated Metallic,
Liquid Refrigerant, 17 Suction Check Valve Bypass, 24, 26 53 PVC conduit, 53
Liquid Starvation, 21 Suction Service Valve, 26
Low Voltage, 11 Suction Strainer, 23 Q
Lubrication System, 14 Suction Valve Bypass, 26 Quantum™HD, 11, 15, 55
M Superheat, 23
Temperature Sensor, 35 R
Magnetic Field, 53 Temperature Transmitter, 34, 35 Reboot, 55
Main Oil Injection Port, 15 Troubleshooting. See Index, TROU- Recovery Procedure, 27
Maintenance, 23 BLESHOOTING RXF Rotary Screw Compressor, 14
Abnormal Vibration, 31 Ventilation, 23 Moveable Slide Valve, 14
Bare Compressor Mounting, 35 Vibration Analysis, 32 Shaft Seal, 14
Bearing Failure, 23 Vibration Data Sheet, 62
Coalescer Filter Element, 26 Vibration Level, 23 S
DIN Connector Plug, 35 Volume Ratio Control, 35 Scaling, 9
Discharge Service Valve, 26 Water Vapor, 23 Self-Lubricating, 14
Disconnect Power, 23 Wiring Harness, 50 Separator, 6
Disconnect Switches, 24 Maintenance Schedule, 31 Severe Water Conditions, 9
Drain Valve, 26 Maximum Oil Flow, 21 Shell And Coil Economizer System, 10
Dry Nitrogen, 23 Mechanical, 57 Shipping Gauges, 7
Filter Elements, 32 Metal Conduit, 53 Shutdown, 23
Isolation Valves, 23 Microprocessor, 10, 17 Liquid Injection, 23
Leaks, 31 Moments, 9 Package Valves, 23
Linear Transmitter, 35 Motor, 11 Solenoid Valves, 23
Liquid Injection Strainer, 25 Bearings, 21 Strainers, 23
Liquid Injection Valves, 23 Contactor, 11 Sight Glass, 7, 15, 27
Liquid Refrigerant, 23 Cycling, 11 Signal Wiring, 53
Low Pressure Transducer, 24 Rotation, 6, 14 Single-Port Liquid Injection, 17
Moisture, 32 Motor Starter Contactor, 11 Skip Frequencies, 22
Motor Bearings, 32 Mounting Bolts, 6 Slide Stop, 22
Lubrication, 32 Movable Slide Valve, 15 Slide Valve, 22
Noise, 31 Multiple Compressor Economizer Slide Valve Piston, 15
Nuisance Oil Level Cutouts, 26, 32
System, 11 Sola® Constant Voltage (Cv) Trans-
Oil-Charging Valve, 26 former, 11
Oil Cooler, 26 N Solenoid Valve, 17
Oil Filter Element, 26 Neoprene Drive Spacer, 6 Star Networks, 55
Oil Filters, 24 Noise Suppression, 55 Start-Up
Oil Foaming, 26 Suction Strainer, 21
Oil Level Control, 35 O Start-Up
Oil Level Transmitter, 35 Dual Oil Filters, 24 Coolware™, 21
Oil Pressure Loss, 26, 32 Main Oil Filter, 24 Discharge Temperature, 21
Oil Pump Strainer, 25 Oil Charge Reservoir, 15 Hand Expansion Valve, 21
Oil Quality, 32 Oil Cooling Initial Start-Up, 21
Operating Log, 32 Liquid Injection, See "Liquid Injec- Prestart Checklist, 21
tion" on page 65 Theoretical Discharge Temperature,
Thermosyphon, See "Thermosy- 21
phon Oil Cooling" on page 67 Water Control Valve, 21
RXF ROTARY SCREW COMPRESSOR UNITS 070.410-IOM (NOV
INDEX 2015) Page 67
T
Temperature Sensor, 17
Thermosyphon Oil Cooling, 8, 17, 21
Condensing Pressure, 21
Drain Valve, 8
Liquid Refrigerant, 8
Refrigerant-Side Safety Valve, 8
Thermostatically Controlled Mixing
Valve, 8
Vapor Mixture, 21
Welding, 9
Threaded Metallic, 53
Threaded Pvc-Coated Metallic, 53
TROUBLESHOOTING, 36–37
Excessive Noise And Vibration, 36
High Oil Temperature, 36
Low Oil Temperature, 36
Oil Temperature Fluctuates, 36
Rapid Oil Loss, 36
Slide Valve, 37
U
Uninterrupted Power Supply, 55
Unit Data Plate, 3
Unshielded, 53
UN/UNF Straight Threads, 40
UPS, 11, 55
UPS Power, 55
UPS Power System, 11
V
Variable Frequency Drives, 53
Vessel, 21
VFD, 22
VFD Applications, 52
VFD Output, 52
Vibration Analysis, 21
Vibration Data Sheet, 62
Voltage Isolation, 55
W
Water Control Valve, 21
Water-Cooled Oil Cooling, 17
Water Treatment, 9
Welding, 9
November 2015 Form Revisions
p.11 – Added Economizer Vi Control text
p.21 – Revised RXF 58-101 text. Last paragraph - valve to be two turns open.