All SGP MCQ
All SGP MCQ
All SGP MCQ
14. Recovery voltage is the value of the r.m.s. voltage that re-appears across the
poles of a
circuit breaker before
a) Restriking voltage
b) Final arc disncon
c) Rise of voltage
d) All of these
Ans: (b)
15. Time between separation of contacts and energisation of trip coil is called
a) Opening time
b) Closing time
c) Arching time
d) Decaying time
Ans: (a)
Division/Class: BE Sub: switchgear and protection Subject Teacher: Prof. T.V. Deokar
Answer.3. Air
Ques.6. With which of the following, a circuit breaker must be equipped for remote
operation?
1. Inverse time trip
2. Time-delay trip
3. Shunt trip
4. All of the above
Answer.3. Overload
Ques.9. Arc in a circuit behaves as
1. A capacitive reactance
2. An inductive reactance
3. A resistance increasing with voltage rise across the arc
4. A resistance decreasing with voltage rise across the arc
Answer.2. Instantaneous
Ques.20. The current zero interruption, in oil and air blast circuit breakers, is achieved by
1. Lengthening of the gap
2. Cooling and blast effect
3. Both 1 and 2
4. Deionizing the oil with forced air
Answer.1. Power
Ques.25. A differential relay measures the vector difference between
1. Two current
2. Two voltage
3. Two similar quantities
4. Any of the above
Answer.3. Constantly the electrical quantities which differ during normal and
abnormal condition
Ques.30. The voltage appearing across the contacts after the opening of the
circuit breaker is called _voltage.
1. Recovery
2. Surge
3. Operating
4. Arc
Answer.1. Recovery
Ques.34. The time interval which is passed in between the energization of the trip coil to
the instant of contact separation is called the
1. Opening Time
2. Closing Time
3. Delayed Time
4. None of the above
Ques.38. Insulation resistance of high voltage circuit breakers is carried out when
1. The circuit breaker is open
2. The circuit breaker is closed
3. Any of the above
4. None of the above
Answer.4. Short-circuits
Answer.1. Motors
Ques.42. Which of the following is the least expensive protection for overcurrent is a low
voltage system?
1. Rewire able fuse
2. Isolator
3. Oil circuit breaker
4. Air break circuit breaker
Answer.2. 2.2 kV to 33 kV
Ques.44. The current zero interruption, in oil and air blast circuit breaker, is achieved by
1. Deionizing the oil with forced air
2. Lengthening of the gap or cooling the blast effect
3. Lengthening of the gap
4. Cooling of the blast effect
Answer.3. Unity
Ques.50. For the protection of power station buildings against direct strokes the
requirements are
1. Interception
2. Interception and conduction
3. Interception, conduction, and dissipation
4. Interception, conduction, dissipation, and reflection
Ques.51. Which of the following is used for the measurement of the insulation resistance?
1. Megger
2. Wattmeter
3. Ammeter
4. Voltmeter
Answer.1. Megger
Ques.52. The interaction between a transmission line and the communication line is
minimized by
1. Transposing transmission as well as communication lines
2. Increasing the height of the transmission line tower
3. Increasing the distance between the two lines
4. All of the above
Answer.1. Open the circuit breaker, open the isolator, operate the earth switch
Ques.55. Discrimination between main and back up protection is provided by the use of
relays
1. Facts
2. Sensitive
3. Slow
4. None of the above
Answer.3. Slow
Ques.60. In busbar protection what is the method of providing an earthed metal barrier
surrounding a bus throughout its length called?
1. Fault bus protection
2. Time graded Overcurrent protection
3. Distance protection
4. Differential protection
Ques.62. For cost and safety, the outdoor substations are installed for voltages above
1. 11 kV
2. 33 kV
3. 60 kV
4. 110 kV
Answer.2. 33 kV
Ques.63. The short circuit in any winding of the transformer is the result of
1. Mechanical vibration
2. Insulation failure
3. Loose connection
4. Impulse voltage
Answer.1. Generators
Ques.68. For which of the following ratings of the transformer differential protection is
recommended?
1. Above 30 kVA
2. Equal to and above 5 MVA
3. Equal to and above 25 MVA
4. None of the above
Answer.4. Thermometer
Ques.72. When the fault current is 2000 A, for a relay setting of 50% with CT ratio 500/5,
the plug setting multiplier will be
1 1
.2 61
. 4
3 2
.4 8
.
Answer.4. 8
Ques.73. Which of the following devices will receive voltage surge first traveling on the
transmission line?
1. Lightning arresters
2. Relays
3. Step-down transformer
4. Switchgear
Ques.74. Which of the following parameter can be neglected for a short line?
1. Inductance
2. Capacitance
3. Resistance
4. Reactance
Answer.2. Capacitance
Ques.76. Which of the following circuit breakers has high reliability and minimum
maintenance?
1. Air blast circuit breakers
2. Circuit breaker with SF6 gas
3. Vacuum circuit breakers
4. Oil circuit breakers
Ques.79. What will be the reflection coefficient of the wave of the load connected to the
transmission line if surge impedance of the line is equal to load?
1. Zero
2. Unity
3. Infinity
4. None of the above
Answer.1. Zero
Ques.87. If the fault occurs near the impedance relay, the VI ratio will be
1. Constant for all distances
2. Lower than that of if the fault occurs away from the relay
3. Higher than that of if the fault occurs away from the relay
4. None of the above
Answer.2. Lower than that of if the fault occurs away from the relay
Ques.88. The torque produced in induction type relay (shaded pole structure) is
1. Inversely proportional to the current
2. Inversely proportional to the square of the current
3. Proportional to the current
4. Proportional to the square of the current
Ques.91. The following statement is associated with the Buchholz relay is not true
1. It is a gas actuated device
2. It is a current operative device
3. It is placed between the transformer tank and the conservator
4. It causes alarm for minor fault and tripping for major fault
Answer.1. Current
Answer.1. DC
Answer.3. Isolator
Ques.101. What is / are the main disadvantage of using oil as the quenching medium in
the circuit breakers?
a. Need periodical replacement.
b. Risk of formation of explosive mixture with air.
c. Possibility of causing fire hazards.
d. All of the above.
Ques.102. a three phases, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3s. What is
its symmetrical breaking current?
a. 1200 A
b. 3600 A
c. 35 kA
d. 104.8 kA
ANSWER: 35 kA
Ques.103. A thermal protection switch provides protection against what?
a. Overload
b. Temperature
c. Short circuit
d. Over voltage
ANSWER: Overload
Ques.104. Which of the following circuit breakers is used for the railway electrification?
a. Air blast circuit breaker
b. SF6 circuit breaker
c. Bulk oil circuit breaker
d. Minimum oil circuit breaker
Ques.106. Which among these circuit breakers produce the least arc energy?
a. Plain oil
b. Minimum oil
c. Air blast
d. Air break
ANSWER: Symmetrical
Ques.108. Which of the following circuit breaker is highly reliable and has a least
maintenance?
a. Oil circuit breakers
b. Air blast
c. Vacuum circuit breakers
d. SF6 circuit breakers
ANSWER: 89 kA
Ques.113. Which of the following circuit breakers has the lowest operating voltage?
a. SF6 circuit breaker
b. Air break
c. Air blast
d. Minimum oil circuit breaker
Ques.114. What is the making to breaking current ratio for an extra high voltage circuit
breaker?
a. More than 1
b. Equal to 1
c. Less than 1
d. A negative value
ANSWER: More than 1
Ques.115. Why is an isolator installed?
a. To isolate one portion of the circuit from another
b. As an substitute for the circuit breaker
c. It used on either sides of the circuit breaker
d. Both (a) and (c)
e. None of these
Ques.115. For which among the following the current ratings are not required?
a. Circuit breakers
b. Relays
c. Isolators
d. Load break switch
ANSWER: Isolators
Ques.116. The isolators used in the transmission lines are capable of breaking
a. Fault current
b. No current
c. Charging current
d. Load current
used?
a. Break abnormal current
b. Making under fault conditions
c. Breaking the circuit under no load condition
d. None of the above
Ques.122. On what factor does the operating speed of the relay depend?
a. Rate of flux built up
b. Armature core air gap
c. Spring tension
d. All of these
ANSWER: All of these
Ques.124.The most efficient torque producing actuating structure for the induction type
relays is
a. Shaded pole structure
b. Watt hour meter structure
c. Induction cup structure
d. Single induction loop structure
ANSWER: Induction cup structure
Ques.125. The least expensive protection for over current in low-voltage system is
A. Rewirable fuse
B. Isolator
C. Circuit breaker
D. Air-break switch
ANSWER: Rewirable fuse
Ques.128. For the protection of stator winding of an alternate against internal fault
involving ground the relay used is a
A. Biased differential relay
B. Directional over-current relay
C. Plain impedance relay
D. Buchholz relay
Ques.129. For the protection of a large squirrel cage induction motor against single
phase normally
A. An over-current relay is used
B. Differential relay is used
C. Directional relay is used
D. Negative sequence current sensitive relay is used
Ques.130. The most commonly used method for the protection of three phase feeder is
A. Time graded protection
B. Differential protection
C. Reverse power protection
D. None of the above
Ques.133.Pilot-wire protection scheme is the most economical and provides high speed
relaying for
A. Short length of lines upto 15 km
B. Medium length of lives up to 60 km
C. Long length of lines up to 200 km
D. All of the above
is/are
A. Magnetising inrush current
B. Mismatching characteristics of CTs
C. Charge of ratio as a result of tapping
D. All of the above
Ques.137.The main function of under voltage protective device generally employed with
a motor starter is to
A. Open the supply circuit on failure of power supply
B. Control the motor voltage
C. Prevent the opening of supply circuit
D. None of the above
Ques.140.In a balanced voltage pilot-wire protection scheme, if the pilot circuit gets short-
circuited, the relay will
A. Fail to trip on internal faults
B. Fail to trip on external faults
C. Trip on full load
D. Trip instantaneously
Ques.141. The frequency of carrier in the carrier current pilot scheme is in the range of
A. 1 kHz to 10 kHz
B. 10 kHz to 25 kHz
C. 25 kHz to 50 kHz
D. 50 kHz to 500 kHz
ANSWER: 50 kHz to 500 kHz
Ques.143. In carrier current protection the purpose of the wave trap is for
A. Trapping power frequency waves
B. Trapping high frequency waves entering into generators/ transformer unit
C. Both a and b
D. None of the above
ANSWER: Trapping high frequency waves entering into generators/ transformer unit
Ques.146. Requirements of protection power station buildings against direct strokes are
A. Interception
B. Conduction
C.. Dissipation
D. All of the above
ANSWER: All of the above
Ques.147.The protection against direct lighting strokes and a high-voltage steep waves is
provided by
A. Ground wires
B. Lightning arresters
C. Lightning arresters and ground wires
D. Earthling of neutral
ANSWER: Lightning arresters and ground wires
ANSWER: 66 KV
ANSWER: Sub-stations
What is switchgear
A. An apparatus used for switching, controlling and protecting the electrical circuits and equipments
B. It detects the faults only
C. It corrects the faults only
D. All of the above
ANSWER: D
Protective relays are devices that detect abnormal conditions in electrical circuits by measuring
A. Current during abnormal condition
B. Voltage during abnormal condition
C. Constantly the electrical quantities which differ during normal and abnormal conditions
D. None of the above
ANSWER: C
Which of the following is the least expensive protection for overcurrent is a low voltage system
A. Rewireable fuse
B. Isolator
C. Oil circuit breaker
D. Air break circuit breaker
ANSWER: A
Discrimination between main and back up protection is provided by the use of relays
A. Facts
B. Sensitive
C. Slow
D. None of the above
ANSWER: C
When the fault current is 2000 A, for a relay setting of 50 percentage with CT ratio 500/5, the plug setting multiplier
will be
A. 16
B. 12
C. 4
D. 8
ANSWER: D
Zones of protection has several zones_the squence of zone from source side is_
A. Generator-Transformer-busbar-Tx Line-distribution transformer-load
B. Generator-Transformer-busbar-Tx Line-busbar-distribution transformer-load
C. Transformer-busbar-Generator-Tx Line-distribution transformer-load
D. Transformer-Generator-busbar-Tx Line-distribution transformer-load
ANSWER: B
The current zero interruption, in oil and air blast circuit breaker, is achieved by
A. Deionizing the oil with forced air
B. Lengthening of the gap or cooling the blast effect
C. Lengthening of the gap
D. Cooling of the blast effect
ANSWER: B
A 50 Hz, 11 kV, 3 phase alternator with earthed neutral having a reactance of 3 ohms per phase and is connected to
bus bar through a circuit breaker, if the distributed capacitance upto CB between the phase and neutral is 0.01 MIC
OF. What is the frequency of oscillations?
A. 10000 Hz
B. 12500 Hz
C. 12628 Hz
D. 13265 Hz
ANSWER: C
When does the arc interruption in oil circuit breaker take place?
A. Contacts apart.
B. Voltages becomes zero
C. Current goes through zero
D. All of the above
ANSWER: C
To limit current chopping in vacuum circuit breakers, the contact material employed should have the properties of
A. Low conductivity and high vapour pressure.
B. Low conductivity and low vapour pressure.
C. High conductivity and high vapour pressure.
D. High conductivity and low vapour pressure
ANSWER: A
CB circuit with L - C introducing a damping circuit. For the critical damping what is the value of resistance switchin
R?
A. ROOT(LC)
B. 0.5*ROOT(C/L)
C. 0.5*ROOT(L/C)
D. 2*PI*ROOT(L/C)
ANSWER: C
A 50 Hz, 11 kV, 3 phase alternator with earthed neutral having a reactance of 3 ohms per phase and is connected to
bus bar through a circuit breaker, if the distributed capacitance upto CB between the phase and neutral is 0.01 MIC
O FARADAY, What is the peak re striking voltage?
A. 18.36 kV
B. 17.96 kV
C. 15.96 kV
D. 12.65 kV
ANSWER: B
On what factor does the rate of rise of restriking voltage (RRRV) depend?
A. System voltage.
B. Circuit power factor only
C. Switching conditions
D. Both (B) and (C)
ANSWER: D
By using low resistance method for arc extension what is the value of arc resistance?
A. Arc resistance is zero.
B. Arc resistance is high
C. Arc resistance is low
D. Arc resistance is very high
ANSWER: C
In Current chopping phenamenon the voltage across CB contact is when magnetising current is I
A. V=I*Root(L/C)
B. V=0.5*Root(L/C)
C. V=2*pi*Root(L/C)
D. V=I*Root(C/L)
ANSWER: A
Which of the following medium is employed for the extinction of arc in air circuit breaker?
A. Water
B. Oil
C. SF6
D. Air
ANSWER: D
Which of the following circuit breaker is design for the least operating voltage?
A. Vacuum circuit breaker
B. Air circuit breaker
C. SF6 circuit breaker
D. Oil circuit breaker
ANSWER: B
Which of the following circuit breaker is design for the highest operating voltage?
A. Vacuum circuit breaker
B. Air blast circuit breaker
C. SF6 circuit breaker
D. Oil circuit breaker
ANSWER: B
A device which is used to protect an electric circuit from damage caused by over load or short circuit is
A. Wave trapper
B. CVT
C. circuit breaker
D. lighting arrester
ANSWER: C
The making and breaking currents of a 3 phase ac circuit breakers in power systems are respectively in for
A three phase circuit breaker is rated 2000 MVA, 33 kV. What will be its making current?
A. 35 kA
B. 49 kA
C. 70 kA
D. 89 kA
ANSWER: D
What is the normal pressure at which the SF6 gas is maintained in the closed position of the breaker?
A. 2 kg / cm2
B. 2.5 kg /cm2
C. 2.8 kg / cm2
D. 3 kg / cm2
ANSWER: C
During arc extinction SF6 gas gets converted to which among these?
A. Gets decomposed to SF4 and SF2
B. Gets decomposed to S and F
C. Gets reduced to SF6
D. Gets oxidized
ANSWER: A
The sequence of components in block diagram of static relay from soure side is
A. Rectifier-transducer-amplifier-trip cirucit-relay measuring circuit-output device
B. Transducer-Rectifier-amplifier-relay measuring circuit-output device-trip cirucit
C.Transducer-amplifier-relay measuring circuit-Rectifier-output device-trip cirucit
D.Transducer-Rectifier-relay measuring circuit-amplifier-output device-trip cirucit
ANSWER: D
In a thermal relay, a bi-metal strip consists of two metal strips having different
A. thermal conductivity
B. efficient of expansion
C. specific heat
D. all
of the
above
ANS
WER:
B
SGP MCQS QUESTION BANK
2. Which of the following circuit breakers is used for the railway electrification?
a. Air blast circuit breaker
b. SF6 circuit breaker
c. Bulk oil circuit breaker
d.Minimum oil circuit breaker
ANSWER:B
ANSWER:D
8) The rating of the circuit breaker is usually determined on the basis of fault.
a. Symmetrical
b. Line to line
c. Single line to ground
d.Double line to ground
ANSWER: Symmetrical
9) Which of the following circuit breaker is highly reliable and has a least maintenance?
a. Oil circuit breakers
b. Air blast
c. Vacuum circuit breakers
d.SF6 circuit breakers ANSWER:
ANSWER:B
ANSWER :B
12)In which relay having no effect on arc fault-
Impedance
reactance
MHO
Thermal overlod
ANSWER : B
Symmetrical breaking
Average value of a.c. component
R.m.s. value of a.c. component
All of these
ANSWER:C
14) Non directional over current relay scheme is not suitable for-
Ring main and interconnected
Tie Scheme
Sectionlise
None of these
ANSWER :A
ANSWER : B
19) A three phase circuit breaker is rated 2000 MVA, 33 kV. What will be its making current?
a. 35 kA
b. 49 kA
c. 70 kA
d.89 kA
ANSWER: 89 kA
SGP MCQS QUESTION BANK
20) Plain circuit breaker can’t be used for voltage above-
400kv
3.3kv
66kv
11kv
ANSWER:D 11KV
22) The earth fault protection of short and medium lines is used-
Quadrilateral relay
Electro magnetic
Electro mechanical
none
ANSWER : A
24) Assertion
(A): In comparison to making capacity of a circuit breaker its breaking
capacity is normally higher.
Reason (R): The breaking capacity of a CB is expressed as √3 * VI * 10-6 MVA
a. Both A and R are true and R is the correct explanation of A
b. Both A and R are true and R is not the explanation of A
c. A is true but R is false
d. A is false but R is true.
SGP MCQS QUESTION BANK
ANSWER: A is false but R is true.
25) It is a technology to improve situation and visibility within power system grids
is
WAM
PMU
PLCC
None
ANSWER : A
28) For single frequency transients, ratio of peak restriking voltage to time
between voltage zero and peak voltage is called-
Restriking voltage
Recovery voltage
RRRV
Active Recovery voltage
ANSWER:C RRRV
ANSWER :A
32) For which among the following the current ratings are not required?
a. Circuit breakers
b. Relays
c. Isolators
d.Load break switch
ANSWER: C- Isolators
33) The isolators used in the transmission lines are capable of breaking
a. Fault current
b. No current
c. Charging current
d. Load current
35) What is the major cause of the failure of the circuit breaker?
a. Trip circuit open
b. Trip latch defective
c. Spring defective
d. All of these
ANSWER:C
41) On what factor does the operating speed of the relay depend?
a. Rate of flux built up
b. Armature core air gap
c. Spring tension
d. All of these
ANSWER:C -MVA
SGP MCQS QUESTION BANK
43) In impedance relay, current element torque should be-
Equal to voltage element torque
None of these
ANSWER:B
ANSWER:C
ANSWER :C
45) In the following figure, which component ensures the safety of the line from damage?
a. Relay
b. Circuit breaker
c. Bus bar
d.Current transformer
ANSWER: A-Relay
SGP MCQS QUESTION BANK
ANSWER :A
A three phase circuit breaker is rated 2000 MVA, 33 kV. What will be its making current?
35KA
49KA
65KA
89KA
ANSWER:D 89KA
ANSWER : B
ANSWER : A
ANSWER : A
52) On what factor does the operating speed of the relay depend?
a. Rate of flux built up
b. Armature core air gap
c. Spring tension
d. All of these
ANSWER : B
54) The low pass filter which filter out undesired frequency component is
Alliasing Filter
Aniti-aliasing Filter
PMU
SGP MCQS QUESTION BANK
Samplig
ANSWER : B
.
55) Proper sampling phenomenon represent in-
Wsm>/2Wsg
Wsm< 2Wsg
Wsm= 2Wsg
none of these
ANSWER : A
56) Loss of Excitation protectd by which device-
Offset MHO Relay
Admitance relay
Thermal overload
All of these
ANSWER : A
ANSWER : C
ANSWER : C
59) The diff.protection is based in current circlation principle is known as-
Bias Protection
SGP MCQS QUESTION BANK
% of diff.protection
overload
Merz prize
ANSWER : D
60) Incipient fault oil level resulting and decomposition oil protected by-
Buchholz relay
Thermal overload
Induction type
All of these
ANSWER : A
a. AC
b. DC
c. Either AC or DC
d. None of these
ANSWER: Either AC or DC
62) For 10MVA ,33KV/3.3kv power transformer wit delta star connecton obtain
CT ratio fo diff.protection scheme to circulated current of 400/ 5Ain pilot
wires.determine CT ratio of HT side
13.85
15.85
17.08
20
ANSWER : A
ANSWER : D
65) For mesured of overheat ,tempreture sensor embeded with whatstones bridge
principle are use-
Thermal Overload realy
RTD
Induction type
Impedance type
ANSWER : B
ANSWER : B
66) The most efficient torque producing actuating structure for the induction type relays is
a. Shaded pole structure
b. Watt hour meter structure
c. Induction cup structure
d.Single induction loop structure
2 Tesla
3Tesla
2.5 Tesla
ANSWER : B
ANSWER : A
69) An alternator is provided with restricted earth fault protection.the alternator is rated
5000KVA,11000 volt,20% of wdg is to be kept unprotected and relay setting 25%.Find
resistance to be added in neutral to GND connection
20.30
19.36
16.5
18
ANSWER : B
70) In an alternator, the armature reaction will be completely magnetizing in case the load
power factor is-
A.Zero lagging
B.Zero leading
C.0.866
SGP MCQS QUESTION BANK
D.Unity
ANSWER : B
ANSWER : B
A.Brushes
B.Poles
C.Armature
ANSWER : B
A.50 Hz
B.60 Hz
ANSWER : A
75)An alternator coupled to which primemover will usually have the highest rotating speed
A.Steam engine
D.Steam turbine
ANSWER : D
C.Frequency of waveform
ANSWER : D
ANSWER : C
A.0.2% to 0.5%
B. 2% to 5%
C. 2% to 15%
D. 0% to 30%
ANSWER : B
SGP MCQS QUESTION BANK
80) Star/star transformers work satisfactorily when........
ANSWER : B
ANSWER : D
82)Which of the following inductor will have the least eddy current losses?
A. Air core
C. Iron core
ANSWER : A
83) The direction of rotation of universal motor can be reversed the by reversing the flow of
current through
A.Armature winding
SGP MCQS QUESTION BANK
B.Field winding
ANSWER : C
A Resistance
B Radiation
C Conductance
D Polarisation
ANSWER : C
85) Find the receiving impedance of a transmission line having a voltage of 24V and a
conduction current of 1.2A is
A 25.2
B 22.8
C 28.8
D 20
ANSWER : D
86) Find the characteristic impedance expression in terms of the inductance and capacitance
parameters.
A Zo = √(LC)
B Zo = LC
C Zo = √(L/C)
D Zo = L/C
SGP MCQS QUESTION BANK
ANSWER : A
87) In long transmission lines Resistance and Capacitance parameters of lines are connected
in
A Series, shunt
B Series, series
C Shunt, shunt
D Shunt, parallel
ANSWER : D
A 20 KV to 100 KV
B Upto 20 KV
C Above 100 KV
D 60 KV to 80 K
ANSWER : C
ANSWER : D
90) When the power is to be transmitted over a distance of 500 km, the transmission voltage
should be in the range
A 150kV - 220Kv
SGP MCQS QUESTION BANK
B 110 kV - 150 kV
C 66 kV - 100 kV
D 33 kV - 66 kV
ANSWER : A
91) Neglecting losses in a transmission system, if the voltage is doubled, for the same power
transmission, the weight of conductor material required will be-
A four times
B double
C half
D one fourth
ANSWER : D
92) By which phenomenon does the energy transmission take place between the walls of the
tube in waveguides?
a. Reflection
b. Refraction
c. Dispersion
d. Absorption
ANSWER : A
93) At what pressure is the SF6 gas filled in the whole installation of GIS substations?
a. 3 kg / cm2
b. 5 kg / cm2
c. 3 kg / m2
d. 5 kg / m2
SGP MCQS QUESTION BANK
ANSWER : A
C. Switching resistance in relay restrain circuit at pre-set time interval by means of a timer
element
95) Distance protection scheme is preferred over graded lime-lag over-current protection in
HV and EHV lines because
A. It is faster in operation
B. It is simple
C. It is cheaper in cost
ANSWER : A
96) A three-step distance protection the reach of the three zones of the relay at the
beginning of the first line typically extends into
A. 100% of the first line, 50% of the second line and 20% of the third line
B. 80% of the first line, of 50% of the second line and 20% of the third line
C. 80% of the first line, 50% of the second line and 10% of the third line
D. 50% of the first line, 50% of the second line and 20% of the third line
ANSWER : B
A. Thermal
B. Electromagnetic
C. Induction
ANSWER : D
D. Either A or B
ANSWER : D
A. Under reaches
B. Over reaches
C. Reach unaffected
ANSWER : A
ANSWER : B
A. Impedance relay
B. Mho relay
C. Reactance relay
D. Induction relay
ANSWER : B
102) For the protection of lines against faults involving variable fault resistance, the
preferred relaying scheme is a
SGP MCQS QUESTION BANK
ANSWER : D
A. Nondirectional relay
B. Directional relay
C. Differential relay
ANSWER : B
ANSWER : B
106) Which one of the following relay has the capability of anticipating the possible
major fault in a transformer ?
A. Over-current relay
B. Differential relay
C. Buchholz relay
D. Over fluxing relay
ANSWER : C
107) Zero sequence current is used for relaying purpose only in the case of
SGP MCQS QUESTION BANK
ANSWER : C
108) How many relays are used to detect interphase fault of a three line system?
A. One
B. Two
C. Three
D. Six
ANSWER : C
109) For protection of parallel feeders fed from one end, the relays required are-
A. Nondirectional relays at the source end and directional relay at the load end
ANSWER : A
110) In order that current should flow without causing excessive heating or voltage drop, the
relay contacts should
SGP MCQS QUESTION BANK
A. Have low contact resistance
ANSWER : D
Protective Relays page-1
1.A single phasing relay can be used with
a) 1ɸ motor
b) 2r ɸ motor
c) 3 ɸ motor
d) All of these
Ans: (c)
2. A relay is used to
a) Break the fault current
b) Sense the fault
c) Sense the fault and direct to trip the circuit breaker
d) All of these
Ans: (c)
10. Basic relay connection requirement is that the relay must operate for
a) Load
b) Internal faults
c) Both (a) and (b)
d) None of these
Ans: (b)
28. For protection against synchronizing power surges, which relay is used?
a) Split-phase relays
b) Impedance relays
c) Reactance relays
d) MHO relays
Ans: (d)
31. In an impedance relay, fault current is maximum if fault occurs near the
a) Relay
b) Center of the line
c) Transformer
d) None of these
Ans: (a)
these Ans:
2. If the operation of a relay does not involve any change in air gap, then the
ratio of rest to pick up is usually .
a) Low
b) Medium
c) High
a) 0.2 to 0.3
b) 0.3 to 0.4
c)
0
.
4
t
o
0
.
6
d
)
0
.
t
o
1
.
Ans:
a) Impedance
b) Current difference
c) Voltage difference
d) None of
these Ans:
a) Stability, reliability
b) Speed sensitivity
c) Selectivity,
adequacy d) No ne
o f t hese
Ans:
6. Protective relays are devices which detect abnormal conditions in
electrical circuit by measuring .
a nd a bno r ma l co nd it io ns Ans:
these Ans:
a) Current difference
b) Voltage difference
c) Impedance difference
CT’s Ans:
a) Line-to-line fault
b) Line-to-line circuit
c) Dead short circuit
d) Bot h ( a) and ( b) o ccur r ing s imu
lt a neo us ly Ans:
a) 100 kV
b) 200 kV
c) 500 kV
d) 1000
kV Ans:
11. The voltage appearing across the contacts after the opening of the
circuit breaker is called .
a) Arc voltage
b) Recovery voltage
c) Surge voltage
d) Break open
voltage Ans:
a) 5 to 10 kg/cm2
2
b) 10 to 15 kg/cm
2
c) 15 to 20 kg/cm
d) 20 to 30
kg/cm2 Ans:
d) None of
these Ans:
14. In oil and air blast circuit breakers, the current zero interruption is attained
by .
a) Lengthening of arc
b) Cooling and blast effect
c) Deionizing the oil with
forced air d) Bot h ( a) and (
b) abo ve
Ans:
a) Alternators
b) Transformers
c) Switch yard
d) Transmission
lines Ans:
16. Which of the following is a directional relay?
a) Reactance relay
b) Mho relay
c) Reactance
relay d) Bot h (
b) and ( c)
Ans:
a) Induction type
b) Shaded pole type
c) Thermocouple type
d) Per ma ne nt mag net mo ving
co il t ype Ans:
a) Polarized type
b) Balance beam type
c) Hinged armature
type d) I nduct io n
d isc t ype
Ans:
a) Voltage polarities
b) Flow of current
c) Flow of power
d) All of
these Ans:
a) Thermal emission
b) Alternators
c) Field emission
d) Tr ans mis s io n
line s Ans:
21. Bulk oil circuit breaker is suitable for voltages up to .
a) 4 kV
b) 25 kV
c) 10
kV d)
36 kV
Ans:
system Ans:
23. The voltage across the circuit breaker pole after final current zero is.
a) Restriking voltage
b) Supply voltage
c) Recovery voltage
d) None of
these Ans:
24. Which of the following circuit breakers takes minimum time installation?
Ans:
25. In a power system, the rate of rise of Restriking voltage depends upon .
these Ans:
26. In a circuit breaker, the arcing contents are made of .
a) Aluminum
b) Electrolytic
c) Copper tungsten alloy
d) Tungst
en Ans:
27. The following medium is employed for extinction of arc in air break circuit
breakers?
a) Air
b) Oil
c) Water
d) None of
these Ans:
28. The following circuit breaker does not use pneumatic operating mechanism
.
d) SF6 circuit
breaker Ans:
a) Thermal emission
b) Alternators
c) Field emission
d) Tr ans mis s io
n line s Ans:
a) 4 kV
b) 25 kV
c) 10
kV d)
36 kV
Ans:
31. Circuit breakers are essentially .
b) Arc extinguishers
c) Transformers to isolate two systems
d) Circuits to break the
system Ans:
32. The voltage across the circuit breaker pole after final current zero is.
a) Restriking voltage
b) Supply voltage
c) Recovery voltage
d) None of
these Ans:
33. Which of the following circuit breakers takes minimum time installation?
Ans:
34. In a power system, the rate of rise of Restriking voltage depends upon .
d) None of
these Ans:
a) Aluminum
b) Electrolytic
c) Copper tungsten alloy
d) Tungst
en Ans:
36. Fault diverters are basically .
a) Circuit breakers
b) Fast switches
c) Relays
d) Fuse
s Ans:
37. The following medium is employed for extinction of arc in air break circuit
breakers?
a) Air
b) Oil
c) Water
d) None of
these Ans:
38. The following circuit breaker does not use pneumatic operating mechanism
.
d) SF6 circuit
breaker Ans:
a) Instantaneous relays
b) Definite time lag
c) Inverse time
lag d) All o f t
hes e
Ans:
b) Voltage
c) Current
d) Reactan
ce Ans:
41. In carrier current protection, wave trap is used is for trapping .
these Ans:
a) A.C. only
b) D.C. only
c) Both (a) and (b)
d) None of
these Ans:
a) MHO relays
b) Reactance relays
c) Impedance relays
d) All of
these Ans:
Ans:
a) Overhead lines
b) Transformer
c) Motors
d) Cable
s Ans:
46. Under voltage relays are used for .
a) Motors
b) Alternators
c) Bus bars
d) All o f t
hes e Ans
a) Earth faults
b) Interphase faults
c) Both (a) and (b)
d) None of
these Ans:
a) Transformer
b) Alternator
c) Overhead
lines d) C. T. ,
P. T.
Ans:
Ans:
a) Inter-turn faults
b) Heavy Loads
c) External Faults
d) Magnet iz ing
a) Over voltage
b) Short circuits
c) Over current
d) All of
these Ans:
coil Ans:
a) In three zones
b) In two zones
c) Independent of zone
d) None of
these Ans:
a) Current
b) Power
c) Voltage
d) I mpeda
nce Ans:
these Ans:
56. A relay is used to .
these Ans:
these Ans:
a) Transformer
b) Overhead line equipment
c) Alternator
d) Moto
rs Ans:
a) Air gap
b) Back up stop
c) Number of ampere turns
d) All of
these Ans:
a) Impedance type
b) MHO type
c) Reactance type
d) All of
these Ans:
61. Buchholz relay is used to protect against .
a) Inter-turn fault
b) External faults
c) Rotor faults
d) E ver y int er na l
fau lt Ans:
a) 0.0001 sec
b) 0.001 sec
c) 0.01 sec
d) 0.1
sec
Ans:
a) Directional type
b) Non-directional type
c) Unidirectional type
d) None of
these Ans:
64. Basic relay connection requirement is that the relay must operate for .
a) Load
b) Internal faults
c) Both (a) and (b)
d) None of
these Ans:
65. In an impedance relay, fault current is maximum if fault occurs near the .
a)Re la y
b) Center of the line
c) Transformer
d) None of
these Ans:
66. More faults occur in .
a) Generators
b) Underground cables
c) Transformers
d) Over head -
line s Ans:
a) SCR
b) Thyristors
c) UJT
d) No ne o f t
hese Ans:
b) Polarized type
c) Balanced beam type
d) All of
these Ans:
a) In three zones
b) In two zones
c) Independent of zone
d) None of
these Ans:
these Ans:
71. Drop out to cutoff ratio for most relays is of the order of .
a) 0.2 to 0.3
b) 0.3 to 0.4
c) 0.4 to 0.6
d) 0. 6 to
1. 0
Ans:
a) Impedance
b) Current difference
c) Voltage difference
d) None of
these Ans:
a) Stability, reliability
b) Speed sensitivity
c) Selectivity,
adequacy d) No ne
o f t hese
Ans:
a nd a bno r ma l co nd it io ns Ans:
75. Time interval from instant of contact separation to time of arc extinction is
called .
a) Arcing time
b) Opening time
c) Closing time
d) None of
these Ans:
76. A distance relay measures .
a) Current difference
b) Voltage difference
c) Impedance difference
d) Distance between two
CT’s Ans:
a) Line-to-line fault
b) Line-to-line circuit
c) Dead short circuit
d) Bot h ( a) and ( b) o ccur r ing s imu
lt a neo us ly Ans:
a) Equal to zero
b) Less than now
c) Equal to
one d) Mor e
t han o ne
Ans:
Ans:
decrease Ans:
81. Fusing factor is defined as the ratio between .
voltage Ans
a) 25 A
b) 50 A
c) 75 A
d) 100
A
Ans:
hed
b) R.m.s. value actually reached
c) Average value actually reached
d) None of
these Ans:
these Ans
85. Cartridge type fuse can be used up to a voltage of .
a) 400 V
b) 11 kV
c) 20
kV d)
33 kV
Ans:
86. Liquid type H.R.C. fuses are used up to a voltage of .
a) 33 kV
b) 66 kV
c) 132
kV
d) 200 kV
Ans:
Ans:
o
f
a) Trip Coil
b) Contacts
c) Handle
d) Mediu
m Ans:
a) Manually
b) Aut o mat ic a lly
c) That it should give warning
d) None of
these Ans:
91. Arcing time is the time between .
these Ans:
92. For single frequency transients, ratio of peak Restriking voltage to time
between voltage
zero and peak voltage is called .
a) Restriking voltage
b) Recovery voltage
c) Rat e o f r ise Rest r ik ing vo lt age
d) Active recovery
voltage Ans:
93. Time between energization of trip coil and separation of contacts is called
.
a) Closing time
b) Opening time
c) Both (a) and
(b) d) No ne o f
t hese
Ans:
breaker Ans:
a) Zer o & inf in it e imped a nce be fo r e & a ft er int er rupt io n r espect ive ly
b) Infinity & zero impedance before & after interruption respectively
c) Equal impedance before & after interruption
d) None of
these Ans:
Ans:
a) Restriking voltage
b) Rate of rise Restriking
voltage c) Po wer facto r
d)
F
r
e
q
u
e
n
c
y
A
n
s
:
a) Resistance switching
b) Inductive switching
c) Capacitive switching
d) Diode
switching Ans:
100. Recovery voltage is the value of the r.m.s. voltage that re-appears across
the poles of a circuit breaker before .
a) Restriking voltage
b) Fina l ar c d ist inct io n
c) Rise of voltage
d) All of
these Ans:
w vo lt age Ans:
a) Decrease in voltage
b) Increase in voltage
c) Pressure of arc
d) Mechanical
stresses Ans:
a) Short duty
b) Intermittent duty
c) Repeated duty
d) All of
these Ans:
a) Breaking capacity
b) Making capacity
c) Short time
capacity d) All o f
t hes e
Ans:
105. Phenomenon of arc interruption takes place at .
a) Zero voltage
b) Zero current
c) High current
d) High voltage
Ans:
d) All of
these Ans:
value Ans:
a) High
b) Low
c) Medium
d) None of
these Ans:
a) Is easily inflammable
b) May from an explosive mixture with air
c) Requires
maintenance d) All
o f t hes e
Ans:
these Ans:
111. Curr
ent copping tendency is minimized by using the F6 gas at
relatively .
velocity. Ans:
criterion. Ans
type
s of
brea
kers.
Ans:
b) and ( c) . Ans:
cases. Ans:
116. A 3-phase breaker is rated at 2000 MVA, 33kV, its making current will be .
a) 35 kA
b) 49 kA
c) 70
kA d)
89 kA
Ans:
above. Ans:
118. Where voltages are high and current to be interrupted is low the
breaker preferred
is .
above. Ans:
119. If the time of operating of a relay for unity TMS is 10secs., the time of
operation for 0.5 TMS will be .
a) 20 secs.
b) 5 secs.
c) 10 secs.
d) None of the
above Ans:
a) Carrier protection.
b) Tr ans fo r mer pr ot ect io n.
c) Generator protection.
d) Motor
protection. Ans:
122. The relay with inverse time characteristics will operate within .
a) 10 ms
b) 5 to 10s
c) 10 to 20s
d) above
25 s Ans:
123. IDMT relays are used to protect the power transformer against .
Ans:
124. In case of electro mechanical relay, relay coil is normally designed for
. a) 1 & 5 A
b) 5 and 10 A
c) 10 and 25A
d) 50 and100
A Ans:
125. If the time of operation of a relay for unity TMS is 10 sec, the time of
operation for 0.4
TMS will be .
a) 4s
b) 25 s
c) 10 s
d) none of
these. Ans:
a) 6. 25 A
b) 10 A c)
12.5 A
d
damping. Ans:
a) Impedance
b) Reactance,
c) Mho.
d) All o f t he
abo ve Ans:
Ans:
130. Threshold characteristics of a plain impedance relay in a complex Z plane is
a .
origin Ans:
a) Non-directional relay.
b) Directional relay.
c) Differential relay.
d) None of
these. Ans:
Ans:
133. The relay best suited for phase fault relaying for medium
transmission line
is .
a) MHO relay.
b) Reactance relay.
c)I mpeda nc e r e la y. d) None of
these. Ans:
134. For ground fault, we prefer .
135. For the protection of lines against faults involving variable fault
resistance, the preferred relaying scheme is .
r e la y. Ans:
136. The relay used for phase fault protection of short transmission lines is .
a) Reactance relay
b) Impedance relay.
c) MHO relay
d) IDMT
relay Ans:
137. The relay best suited for phase fault relaying for long transmission lines is
.
a) MHO r ela y.
b) Reactance relay.
c) Impedance relay.
d) Induction
relay. Ans:
a) Impedance relay.
b) MHO r e la y.
c) Reactance relay.
d) Induction
relay. Ans:
139. Which of the following relays has inherent directional characteristic?
a) MHO.
b) Reactance.
c) Impedance.
d) None of the
above. Ans:
140. For the protection of a very long extra high voltage line, the protective
relay used
is .
Ans:
a) Induction relay.
b) T her ma l r e la y.
c) Impedance relay.
d) MHO
relay. Ans:
voltages. Ans:
a) Feeders.
b) Alternators
c) Transforme
rs. d) All o f t
hese.
Ans:
144. Both voltage and current signals are required for .
relay. Ans:
a) Under-voltage relay.
b) Translay relay.
c) Thermal relay.
d) Buchholz
relay. Ans:
146. In the case of transmission line protection, over current relay is used .
d) Only up to
1,100kV Ans:
a) Transformer
b) Transmission line
c) Motors
d) Gener
ato r s Ans:
148. A relay which has no moving parts and performs measurement with solid
state circuit
is .
a) Differential relay
b) Static relay
c) Induction type relay
d) Thermal
relay Ans:
149. Which of the following relay does not make use of electromagnetic force
.
Indu
ctio
type
rela
Ans:
150. Over conventional electromechanical relays, the transistor relay has the
limitations of
.
Ans:
151. In a static overload relay, inverse time characteristics are obtained by.
a) A transistor amplifier
b) An int egr at ing c ir cu it
c) A transistor switch.
d) A differentiating
circuit Ans:
a) Phase comparison
b) Amplitude comparison
c) Starting an impedance relay
d) Biasing a MHO
relay Ans:
a) Transformer amplifier
b) Transistor logic
circuit c) Rect ifier br
idge
d) Thyristor Bridge
Ans:
these Ans:
comparators Ans:
a) Distance protection
b) D iffer e nt ia l pr ot ect io n
c) Both (a) & (b)
d) Neither (a) nor
(b) Ans:
a) alternators.
b) transformers.
c) transmission
lines. d) bot h ( a)
and ( b).
Ans:
158. Merz-Price relays are used for .
a) motor protection,
b) capacitor protection.
c) rectifier
protection. d)
gener ato r prot ect
io n.
Ans:
a) circuit breakers.
b) transforme
rs. c) CTs.
d)
160. Differential protection scheme is used for alternators of capacity more than .
a) 500 kVA.
b) 1 MVA.
c) 2 MVA.
d) 25
MVA.
Ans:
Decelerati
on of the
rotor. Ans:
a) Short-circuit resistance.
b) Transient reactance.
c)Sync hr o no us r eact ance
d) None of the
above Ans:
163. We do not require any protection against prime mover failure in case of .
generators. Ans:
164. The most common type of protection used or stator winding faults such as
phase to phase
or phase-to- ground short circuit in case of alternator is .
a) Over-current protection.
b) Mer z- Pr ice pr ot ect io n.
c) Buchholz protection.
d) None of the
above. Ans:
a) Thermal relays.
b) Over-current relays.
c)T her ma l se ns it ive r e la ys.
d) Either of the
above Ans:
b) Dover-current relay.
c) Plain impedance relay.
d) Buchholz
relay. Ans:
167. The bias factor S in unit protection synchronous generators .
above. Ans:
169. For the protection of a large squirrel cage induction motor against
single phasing normally .
170. The main function of under voltage protective device generally employed
with a motor starter is to .
above. Ans:
a) Stator.
b) Rotor.
c) Over-load.
d) Under-voltage.
e) Unbalanced supply voltages and reverse or open
phase starting. f) All o f t he abo ve.
Ans:
172. Earth fault protection for an electric motor is provided by means of .
Ans:
173. The relay used for protection of power transformers against internal faults
is .
a) Buchho lz r e la y
b) MHO relay
c) Induction relay
d) Impedance
relay Ans:
a) Δ- Y
b) Y- Δ
c) Δ- Δ
d) Y-Y
Ans:
a) Δ- Δ connection
b) Y- Δ
connection c)
Y- Y co nnect io
n
d) Δ
–Y
co
nn
ec
ti
ns
:
176. A 3 –phase 11/66 kV delta / star transformer protected by Merz price
scheme has CT ratio
of 400/5 on LT side. Ratio of CT on HT side will be equal to .
a)
b)1:23:1
23
c) 23: √3
d) √3:23
Ans:
current Ans:
a) External faults
b) Magnetizing current inrush
c) Overloadin
g d) I nt er
na l fau lt
Ans:
above. Ans:
voltage Ans:
a) Same p ha se
b) Opposite in phase
c) Phase difference of 60 degrees
d) Phase difference of 90
degrees Ans:
183. For preventing the maloperation of Merz price protection scheme on inrush
of
magnetizing current .
above. Ans:
Ans:
185. protection used for protection of transmission line is a unit type
protectio
n.
a) Distance
b) Current graded over-current
c) Carrier current
current Ans:
a) Distance protection.
b) Current graded over-current protection.
c) Time graded over-current protection.
d) In-rush
protection. e) ( a),
( b) and ( c) .
Ans:
187. Graded time lag over-current relaying without directional features can he
employed for
protection of .
a) Ring mains.
b) Parallel feeders.
c) Radial feeders.
d) None of the
above Ans:
above. Ans:
189. For the protection of parallel feeders fed from one end the relays required
are .
a) Non-directional relays at the source end and directional relays at the load
end.
above. Ans:
above Ans:
above Ans:
instantaneously.
Ans:
194. Carrier current protection scheme is normally used for protection of HV
cables only
.
No
ne
of
the
abo
ve.
Ans
195. The frequency of carrier in the carrier current pilot scheme is in the range of .
a) 1 kHz to 10 kHz.
b) 10 kHz to 25 kHz.
c) 25 kHz to 50
kHz. d) 50 kHz to
500 kHz.
Ans:
196. T
above Ans:
198. In an overhead transmission line, wave traps are used for the detection of .
Fau
lt
po
wer
sig
nal
Ans
:
199. Coupling capacitors used in carrier protection have values usually
in the range of .
a) 1 to 20 µF.
b) 100 to 500 µF
c) 0.01 to 0.1 µF.
d) 1,
000
to
5,
000
pF
Ans
200. The line trap in the case of carrier current pilot consists of .
Par
allel
R-C
circ
uit.
Ans
Ans:
203. Line trap and coupling capacitors are used for carrier current
protection in which
.
(c) Both the line trap and coupling capacitor have low impedance to 50
Hz signal but high impedance to carrier current signal.
(d) Both the line trap and coupling capacitor have high impedance to 50 Hz
signal but low impedance to carrier current signal.
Ans:
204. In a 3-step distance protection, the reach of the three zones of the relay at
the beginning
of the first line typically extends into .
a) 100% of the first line, 50% of the second line and 20% of the third
line.
b) 80% o f t he fir st line, 50% o f t he seco nd line a nd 20% o f t he
t hir d line.
c) 80% of the first line, 50% of the second line and 10% of
the third line.
d) 50% of the first line, 50% of second line and 20% of
a) It’s full-length.
b) 50% of its full-length.
c) 25% of its full-
length d) 80% o f it
s fu ll- le ngt h.
Ans:
a) It is fa st er in o per at io n
b) It is simple
c) It is cheaper in cost.
d) All of the
above. Ans:
a) I ncr eases
b) Decreases
c) Remains constant
d) Drops to zero
instantaneously Ans:
d) All of above
Ans:
a) arcing to core
d) bot h ( a) and (
b) Ans:
a) lightning
b) resonance
c) switching
d) all o f t
hese Ans:
SWITCHGEAR & PROTECTION Multiple Choice Questions :-
Ans: d
Ans: d
3. SF6 gas
(c) is nontoxic
Ans: c
(b) porcelain
Ans: a
5. Which of the following medium is employed for extinction of arc in air circuit breaker ?
(a) Water
(b) Oil
(c) Air
(d) SF6
Ans: c
6. With which of the following, a circuit breaker must be equipped for remote operation ?
Ans: c
(a) fuses
(b) relays
Ans: c
(a) short-circuit
(b) temperature
(c) overload
Ans: c
Ans: d
Ans: a
SWITCHGEAR & PROTECTION Objective Questions
(d) temperature
Ans: e
(a) induction
(c) thermal
(d) electromagnetic
Ans: e
13. Thermal overload relays are used to protect the motor against over current due to
(a) short-circuits
(c) grounds
(d) all of the above
Ans: b
(a) delayed
(b) instantaneous
Ans: b
Ans: c
Ans: d
17. In order that current should flow without causing excessive heating or voltage drop, the relay
contacts should
(a) have low contact resistance
Ans: d
Ans: a
Ans: a
20. The current zero interruption, in oil and air blast circuit breakers, is achieved by
Ans: c
Ans: d
Ans: d
(a) power
(b) current
Ans: a
Ans: c
Ans: d
Ans: a
Ans: c
29. Protective relays are devices that detect abnormal conditions in electrical circuits by measuring
(c) constantly the electrical quantities which differ during normal and abnormal conditions
Ans: c
30. The voltage appearing across the contacts after opening of the circuit breaker is called _voltage.
(a) recovery
(b) surge
(c) operating
(d) arc
(e) none of the above
Ans: a
Ans: d
Ans: c
Ans: d
Ans: d
Ans: a
Ans: a
Ans: a
Ans: c
(a) overload
(c) open-circuits
(d) short-circuits
Ans: d
(a) 2
(b) 4
(c) 6
(d) 10
Ans: d
Ans: a
42. Which of the following is the least expensive protection for overcurrent is low voltage system ?
(b) Isolator
Ans: a
(a) 33kVto66kV
(b) HkVto33kV
(c) 3.3kVandllkV
Ans: c
44. The contacts of high voltage switches used in power system are submerged in oil. The main purpose
of the oil is to
Ans: c
(a) SFe
Ans:
46. To protect most of the electrical equipment handling low power, the types of relays used are
(a) thermocouple
Ans: c
Ans: b
48. Ungrounded neutral transmission system is not recommended because of system
(b) insulation overstress may lead to failure and subsequent phase to phase faults
Ans: d
49. The reflection co-efficient at the open circuited end of a transmission line.
(a) zero
(b) infinity
(c) unity
Ans: c
50. For the protection of power station buildings against direct strokes the requirements are
(a) interception
Ans: c
51. The line insulation is the insulation level of the station equipment.
(b) same as
(c) more than
(d) proportional to
Ans: e
52. The interaction between a transmission line and communication line is minimized by
Ans: d
53. When a wave propagates on a transmission line, it suffers reflection several times at
(a) tapping
Ans: d
(c) An impedance relay has maximum fault current when fault occurs near the relay
55. Discrimination between main and back up protection is provided by the use of relays which are
(a) fact
(b) sensitive
(c) slow
Ans: c
(a) current
(b) voltage
(c) impedance
Ans: d
Ans: d
(c) The peak short current is (1.8 xV2) times the A.C. component
(d) The MVA at fault is equal to base MVA divided by per unit equivalent fault reactance
Ans: a
Ans: e
(a) reactors
(b) resistors
(c) capacitors
Ans: a
Ans: c
62. For cost and safety, the outdoor substations are installed for voltages above
(a) 11 kV
(b) 33 kV
(c) 60kV
(d) 110kV
Ans: b
63. The short circuit in any winding of the transformer is the result of
Ans: d
(a) Impedance
(b) Reactance
Ans: a
65. For which of the following protection from negative sequence currents is provided ?
(a) Generators
(b) Motors
(d) Transformers
Ans: a
(b) Reactance
(c) Impedance
Ans: b
Ans: d
68. For which of the following ratings of the transformer differential protection is recommended ?
(a) thermocouple
(b) pyrometer
(a) generators
(b) busbars
(c) transformers
(d) motors
71. The relay with inverse time characteristic will operate within
(b) 5 to 10 sec
(c) 5 to 20 sec
(d) 20 to 30 sec
73. Which of the following devices will receive voltage surge first travelling on the transmission line ?
(a) Lightning arresters
(b) Relays
(c) Step-down transformer
(d) Switchgear
Ans: a
74. Which of the following parameter can be neglected for a short line ?
(a) Inductance
(b) Capacitance
(c) Resistance
(d) Reactance
Ans: b
76. Which of the following circuit breakers has high reliability and minimum maintenance ?
(a) Air blast circuit breakers
(b) Circuit breaker with SF6 gas
(c) Vacuum circuit breakers
(d) Oil circuit breakers
Ans: b
79. What will be the reflection co-efficient of the wave of load connected to transmission line if surge impedance of the
line is equal to load ?
(a) Zero
(b) Unity
(c) Infinity
(d) None of the above
Ans: a
80. The inverse definite mean time relays are used for over current and earth fault protection of transformer against
(a) heavy loads
(b) internal short-circuits
(c) external short-circuits
(d) all of the above
Ans: b
82. Air blast circuit breakers for 400 kV power system are designed to operate in
(a) 100 microsecond
(b) 50 millisecond
(c) 0.5 sec
(d) 0.1 sec
Ans: b
87. If the fault occurs near the impedance relay, the VII ratio will be
(a) constant for all distances
(b) lower than that of if fault occurs away from the relay
(c) higher than that of if fault occurs away from the relay
(d) none of the above
Ans: b
88. The torque produced in induction type relay (shaded pole structure) is
(a) inversely proportional to the current
(b) inversely proportional to the square of the current
(c) proportional to the current
(d) proportional to square of the current
Ans: b
89. The steady state stability of the power system can be increased by
(a) connecting lines in parallel
(b) connecting lines in series
(e) using machines of high impedance
(d) reducing the excitation of machines
(e) none of the above
Ans: a
90. The inductive interference between power and communication line can be minimized by
(a) transposition of the power line
(b) transposition of the communication line
(c) both (a) and (b)
(d) increasing the distance between the conductors
Ans: c
104. By which of the following methods major portion of the heat generated in a H.R.C. fuse is dissipated ?
(a) Radiation
(b) Convection
(c) Conduction
(d) All of the above
Ans: c
106. The information to the circuit breaker under fault conditions is provided by
(a) relay
(b) rewirable fuse
(c) H.R.C. only
(d) all of the above
Ans: a
110. In a single bus-bar system there will be complete shut down when
(a) fault occurs on the bus itself
(b) fault occurs on neutral line
(c) two or more faults occur simultaneously
(d) fault occurs with respect to earthing
Ans: a