METSEPM5110: Product Data Sheet
METSEPM5110: Product Data Sheet
METSEPM5110: Product Data Sheet
Main
Range of product PowerLogic
Device short name PM5110
Product or component Power meter
type
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Complementary
Power quality analysis Up to the 15th harmonic
Device application Power monitoring
Type of measurement Active and reactive power
Energy
Power factor
Frequency
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
Voltage
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Current
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Supply voltage 125...250 V DC
100...415 V AC (45...65 Hz)
Network frequency 45...65 Hz
Power consumption in VA 10 VA at 415 V
Display type Backlit LCD
Display resolution 128 x 128
Sampling rate 64 samples/cycle
Measurement current 10 mA...9 A
Analogue input type Voltage (impedance 5 MOhm)
Current (impedance 0.3 mOhm)
Measurement voltage 35...480 V AC 45...65 Hz between phases
20...277 V AC 45...65 Hz between phase and neutral
Number of inputs 3 current transformer
Measurement accuracy ± +/- 0.5 % voltage
± +/- 0.5 % current
± +/- 0.005 % power factor
± +/- 0.05 % frequency
± +/- 0.5 % apparent power
± +/- 0.5 % active power
± +/- 2 % reactive energy
± +/- 0.5 % active energy
Accuracy class Class 2 (reactive energy according to IEC 62053-24)
Class 0.5S (active energy according to IEC 62053-22)
Number of outputs 1 digital
Communication port protocol RS485: 2 wires, 9.6, 19.2 and 38.4 kbauds, even/odd or none, insulation: 2500 V
Data recording Min/Max of instantaneous values
Time stamping
Mounting mode Flush-mounted
Mounting support Framework
Environment
Electromagnetic compatibility Conducted and radiated emissions class class B, conforming to EN 55022
Immunity to magnetic fields class 4, conforming to IEC 61000-4-8
Conducted radio-frequency immunity test class 3, conforming to IEC 61000-4-6
Electrostatic discharge class 4, conforming to IEC 61000-4-2
Harmonics class class A, conforming to IEC 61000-3-2
IP degree of protection IP30 (body) conforming to IEC 60529
IP52 (front) conforming to IEC 60529
Relative humidity 5...95 % 50 °C
Pollution degree 2
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -40...85 °C
Operating altitude 2000 m