DS240 Series: 1-Phase Type 2 Surge Protector
DS240 Series: 1-Phase Type 2 Surge Protector
DS240 Series: 1-Phase Type 2 Surge Protector
DS240 series
• Compact single-phase Type 2 SPD
• Discharge currents : In : 20 kA / Imax : 40 kA
• Common/Differential mode
• Pluggable module
• Remote signaling contact (option)
• Complies with EN 61643-11 and IEC 61643-1
DS240 S-xxx/G
Characteristics
Dimensions - Electrical diagram
CITEL part number DS240-120 DS240-230 DS240-400
(in mm) Single-phase network 120 V 230 V 230 V
Neutral configuration TN TN TT-TN-IT
Max. operating voltage Uc 150 Vac 255 Vac 400 Vac
Temporary overvoltage withstand UT 150 Vac 255 Vac 400 Vac
9
Operating current Ic < 1 mA < 1 mA < 1 mA
Leakage current at Uc
Protection mode(s) MC/MD (2) MC/MD (2) MC
L N
Nominal discharge current In 20 kA 20 kA 20 kA
11
12
14
11
12
C C
Disconnection indicator 2 (or 1) mechanical indicators
Remote signaling of disconnection Option DS240S - output on changeover contact
Ft
Ft
MI Mounting symmetrical rail 35 mm
Ft t°
MI t° t°
Operating temperature -40/+85 °C
Protection class IP20
Housing material Thermoplastic UL94-V0
Standards compliance
NF EN 61643-11 France Parafoudre Basse Tension - Essais Classe II
IEC 61643-1 International Low Voltage SPD - Test Class II
EN 61643-11 Europe Low Voltage SPD - Test Class II
DS240S-xxx DS240S-xxx/G UL1449 3rd Edition USA Surge Protection Device (SPD) - Type 2
V : High energy varistor Note 1: Rating in compliance with NF C15-100 art. 534.1.5.3. An order to increase service continuity, higher rating can be used (up to 125
A). For further information, please consult product instructions.
GDT : High energy Gas tube Note 2 : MC = Common mode (L/PE ou N/PE)/ MD = Differential mode (L/N)
Ft : Thermal fuse Note 3 : /G verions are available
C : Remote signaling contact
t° : Thermal disconnection system