EKC 315A Danfoss Rs8cS302
EKC 315A Danfoss Rs8cS302
EKC 315A Danfoss Rs8cS302
industrial evaporator
EKC 315A
REFRIGERATION AND
AIR CONDITIONING Manual
Introduction
Application
The controller and valve can be used where there are require-
ments to accurate control of superheat and temperature in con-
nection with refrigeration.
E.g.:
• Cold store (air coolers)
• Processing plant (water chillers)
• A/C plant
Advantages
• The evaporator is charged optimally – even when there are great
variations of load and suction pressure
• Energy savings – the adaptive regulation of the refrigerant injec-
tion ensures optimum utilisation of the evaporator and hence a
high suction pressure
• Exact temperature control – the combination of adaptive
evaporator and temperature control ensures great temperature
accuracy for the media
• The superheating is regulated to the lowest possible value at
the same time as the media temperature is controlled by the
thermostat function
Functions
• Regulation of superheat
• Temperature control
• MOP function
• ON/OFF input for start/stop of regulation
• Input signal that can displace the superheat reference or the
temperature reference
• Alarm if the set alarm limits are exceeded
• Relay output for solenoid valve
• PID regulation
• Output signal following the temperature showing in the display
System
The superheat in the evaporator is controlled by one pressure
transmitter P and one temperature sensor S2.
The valve can be one of the following types:
• TQ (PHTQ, TEAQ)
• AKV (AKVA)
TQ is a modulating valve, and when this is used a solenoid valve
must also be used in the liquid line.
AKV is a pulsating valve.
Where the AKV valve is used it also functions as solenoid valve.
Temperature control is performed based on a signal from tem-
perature sensor S3 which is placed in the air current before the
evaporator. Temperature control is in the shape of an ON/OFF
thermostat that shuts off the liquid flow in the liquid line, either
via the solenoid valve in TQ applications or directly when AKV is
used.
Superheat function
You may choose between two kinds of superheat, either:
• Adaptive superheat or
• Load-defined superheat
MOP
The MOP function limits the valve’s opening degree as long as the
evaporating pressure is higher than the set MOP value.
Override function
Via the analog input a displacement can be made of the tempera-
ture reference or of the superheat reference. The signal can either
be a 0-20 mA signal or a 4-20 mA signal. The reference can be
dsplaced in positive or negative direction.
Relays
The relay for the solenoid valve will operate when refrigeration
is required. The relay for the alarm function works in such a way
thatr the contact is cut in in alarm situations and when the con-
troller is de-energised.
Analog output
The controller is provided with an analog current output which
can be set to either 0-20 mA or 4-20 mA. The signal will either fol-
low the superheat, opening degree of the valve or the air tem-
perature.
PC operation
The controller can be provided with data communication so that it
can be connected to other products in the range of ADAP-KOOL®
refrigeration controls. In this way operation, monitoring and data
collection can be performed from one PC – either on the spot or in
a service company.
See also page 14.
Ref. Diff.
Unit r05 Units
Here you select whether the controller is to indicate the temperature values in °C or 0: °C + bar
in °F. If indication in °F is selected, other temperature settings will also change over to 1: °F + psig
Fahrenheit, either as absolute values or as delta values (in AKM only °C + bar – is displayed
The combination of temperature unit and pressure unit is depicted to the right. – whatever the setting).
External contribution to the reference r06 ExtRefOffset
This setting determines how large a contribution is to be added to the set setpoint
when the input signal is max. (20 mA). See o10.
Correction of signal from S2 r09 Adjust S2
(Compensation possibility through long sensor cable).
Correction of signal from S3 r10 Adjust S3
(Compensation possibility through long sensor cable).
Start/stop of refrigeration r12 Main Switch
With this setting refrigeration can be started and stopped. Start/stop of refrigeration
can also be accomplished with the external switch function. See also appendix 1.
Define thermostat function r14 Therm. Mode
0: No thermostat function. Only the superheat is regulated
1: Thermostat function as well as regulation of superheat.
Alarm
The controller can give alarm in different situations. When there is an alarm all the
light-emitting diodes (LED) will flash on the controller front panel, and the alarm relay
will cut in.
Alarm for upper deviation A01 Hgh.TempAlrm
The alarm for too high S3 temperature is set here. The value is set in Kelvin. The alarm
becomes active when the S3 temperature exceeds the actual reference plus A01. (The
actual reference can be seen in u28).
Alarm for lower deviation A02 Low.TempAlrm
The alarm for too low S3 temperature is set here. The value is set in Kelvin. The alarm
becomes active when the S3 temperature drops below the actual reference minus
A02.
Alarm delay A03 TempAlrmDel
If one of the two limit values is exceeded, a timer function will commence. The alarm
will not become active until the set time delay has been passed. The time delay is set
in minutes.
With data communication the impor-
tance of the individual alarms can be
defined. Setting is carried out in the
“Alarm destinations” menu. See also
page 14
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you reconnect the supply voltage
Connections
Necessary connections
Terminals: Data communication
25-26 Supply voltage 24 V a.c.
23-24 Supply to actuator
17-18 Only at TQ actuator: Signal from actuator
20-21 Pt 1000 sensor at evaporator outlet (S2)
14-15 Pressure transmitter type AKS 33
9-10 Relay switch for start/stop of solenoid valve
1-2 Switch function for start/stop of regulation. If a switch is
not connected, terminals 1 and 2 must be shortcircuited.
Appendix 1 Appendix 2
Interaction between internal and external start/stop functions Cable length for the TQ actuator
and active functions. The actuator must be supplied with 24 V a.c. ± 10%.
To avoid excessive voltage loss in the cable to the actuator, use a
Internal Start/stop Off Off On On thicker cable for large distances.
External Start/stop (DI) Off On Off On
Refrigeration (DO2) Off On
Wire cross section
Standby tempera-
TQ actuator Regulating
ture
Expansion valve relay Off On
Temperature monitoring No Yes
Sensor monitoring Yes Yes
Cable length
Appendix 3 Appendix 4
If the flow of refrigerant is to be distributed to several expansion If there are two evaporators sharing the same suction line, the
valves, this can be accomplished by using AKV valves and EKC signal from the pressure transmitter can be used by two control-
controllers as slave modules. lers.
Standby temperatures for TQ valves. The two types of regulation for superheat are, as follows:
Load-defined superheat
n26
The setting is based on the TQ valve’s closing curve. With a plus
value the valve can be kept slightly open. With a minus value the The reference follows a defined curve.This curve is defined by
valve can be closed completely. If the minus value is high you three values: the closing value, the min. value and the max.
can be sure that the valve will close, but then it will also react value. These three values must be selected in such a way that
slowly when it has to open again. the curve is situated between the MSS curve and the curve for
average temperature difference ∆Tm (temperature difference
n27 between media temperature and evaporating temperature.
This setting defines the number of degrees the actuator has to Setting example = 4, 6 and 10 K).
be warmer when the valve is completely open. If the value is
high you can be sure that the valve is completely open, but then
it will also react slowly when it has to close again.
Example
Each controller is provided This cable is also connected to The gateway can now be con- At the service company a
with a plug-in module. a gateway type AKA 243/AKA nected to a modem. modem, gateway and PC with
245. system software type AKM
The controllers are then con- When an alarm occurs from have been installed.
nected to a two-core cable. This gateway will now control one of the controllers, the
the communication to and gateway will - via the modem All the controllers’ functions
Up to 119 controllers may be from the controllers. - make a phone call to the can now be operated from the
connected to one cable. service company. various menu displays.
It will collect temperature val-
ues and it will receive alarms. The programme will for exam-
When there is an alarm the ple upload all the collected
alarm relay will be activated for temperature values once a day.
two minutes.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
RC-EM
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.