Nothing Special   »   [go: up one dir, main page]

DS Power SH SHP Manual Three Phase UPS Tescom PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 70

DS 300 SH - SHP Series

User Manual
Uninterruptible Power Supply System

3 phase In / 3 phase Out


10-20 kVA
DSP CONTROLLED UPS

Βόλου 7, 183 46 Μοσχάτο +30 210 9590080


Volou 7, 18 346, Moschato, Greece info@tescom-ups.gr www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

CONTENTS

I. GENERAL DESCRIPTION.......................................................................................3

1.1 Introduction ........................................................................................................3


1.2 Design Concept .................................................................................................6
1.2.1 Description of Blocks ................................................................................7
1.2.2 Operating Conditions of UPS ....................................................................7
1.3 Front view of UPS Conditions of UPS ................................................................8
1.4 Technical Specifications ....................................................................................10

II. UPS INSTALLATION ...............................................................................................11

2.1. Introduction ........................................................................................................11


2.2. Unpacking .........................................................................................................11
2.3. Equipment Positioning .......................................................................................11
2.4. Connecting the UPS Power Cables ...................................................................12
2.5. Safety Earth .......................................................................................................12
2.6. Cable Connection Procedure .............................................................................12
2.6.1. Description of Connection Terminals of the UPS ........................................13
2.7. Battery Installation .............................................................................................14

III. FRONT PANEL ........................................................................................................18

3.1. Introduction ........................................................................................................18


3.2. Front Panel Menu Descriptions ..........................................................................18
3.2.1 MEASUREMENTS menu ............................................................................21
3.2.2 ALARM LOGS menu ...................................................................................24
3.2.3 INFORMATION menu .................................................................................24
3.2.4 OPTIONS menu ..........................................................................................25
3.2.5 COMMAND menu .......................................................................................28
3.2.6 TIME menu .................................................................................................28
3.2.7 SERVICE menu ..........................................................................................29
3.2.8 ADJUST menu ............................................................................................29
3.2.9 User Pasword .............................................................................................30
3.3. Alarms and warning messages ..........................................................................30
3.4. Status Codes .....................................................................................................33
3.5. Alarm messages and quick troubleshooting .......................................................39

IV. OPERATING INSTRUCTIONS ................................................................................44

4.1 Introduction ..........................................................................................................44


4.2 Operating ups in online mode ..............................................................................44
4.2.1 Starting ups from a completely shut down position......................................44
4.2.2 Shutting down the ups ................................................................................44
4.2.3 Switching the UPS from a normal
operation to maintenance bypass condition ..............................................45
4.2.4 Switching the UPS from a maintenance
bypass condition to normal operation ........................................................45
4.3 UPS Behavior During mains outage ..................................................................46

2 www.tescom-ups.gr

1
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

V. PARALLEL OPERATION (DS - SHP MODELS)..........................................................50

5.1 Introduction ........................................................................................................50


5.2 Parallel Operation Mode setting of DS300SHP Series UPSs .............................51
5.3 Parallel mode status codes of the UPS ..............................................................54

VI. PARALLEL OPERATING INSTRUCTIONS (DS - SHP MODELS) ..........................57

6.1 Introduction ........................................................................................................57


6.2 Operating instructions for parallel connected UPSs............................................57
6.2.1 Starting UPSs from a completely shut down position.................................57
6.2.2 Shutting down the UPS .............................................................................57
6.2.3 Switching the UPS from a normal Operation to
Maintenance Bypass Condition ................................................................58
6.2.4 Switching the UPS from a Maintenance Bypass
Conditio nto Normal Operation .................................................................58

VII. NORMAL OPERATING INSTRUCTIONS (DS - SH MODELS)..............................59

7.1 Operating UPS in Online Mode ..........................................................................59


7.1.1 Starting UPS from a completely shut down position ..................................59
7.1.2 Shutting down the UPS .............................................................................59
7.1.3 Switching the UPS from a Normal Operation to
Maintenance Bypass Condition ................................................................59
7.1.4 Switching the UPS from a Maintenance Bypass
Condition to Normal Operation .................................................................60
7.2 UPS Behavior During Mains Outage ..................................................................60

VIII. MAINTENANCE.....................................................................................................46

8.1 Scheduled maintenance .................................................................................46


8.2 Daily checks ...................................................................................................46
8.3 Weekly checks ...............................................................................................46
8.4 Annual Maintenance.......................................................................................47
8.5 Storage conditions and transportation of ups .................................................47

IX. FAULTS AND TROUBLESHOOTING ....................................................................48

9.1 General Procedure for fault checking and troubleshooting ...................................48


9.2 Before calling service ...........................................................................................48

X. UPS REMOTE MONITORING AND CONTROL ......................................................49

10.1 Using Serial Port ................................................................................................49


10.2 Serial Communication port connection cable .....................................................49
10.3 Modem connection ............................................................................................50
10.3.1 Hardware configuration .............................................................................50
10.3.2 Functioning Principle .................................................................................50
10.3.3 Modem Programming Procedure...............................................................50
10.3.3.1 Smart modem (SM) programming .................................................50
10.3.4 Modem – UPS Connection Cable ..............................................................51
10.4 Dry contact (ınterface) connections....................................................................51
10.5 Remote monitoring panel connection of UPS.....................................................51

XI. EFFICIENT USAGE OF UPS IN TERMS OF ENERGY CONSUMPTION ..........52

2 3
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

SAFETY

IMPORTANT NOTICES
1. Read instructions carefully before installing and starting the UPS.
2. All warnings in the manual should be adhered to.
3. All operating instructions should be followed.
4. The unit should be supplied by a grounded outlet. Do not operate the unit without a ground source.
5. Power cables of the UPS should be routed carefully so that they are not to be walked on.
6. Please save this manual.
7. Please save or recycle the packaging materials.

WARNING!

• Do not insert any object into ventilation holes or other openings.


• To reduce the risk of fire or electric shock, install in temperature and humidity controlled
indoor area free of conductive contaminants.
• To reduce the risk of fire, replace fuses with the same type and rating when necessary.

CAUTION!
• Only qualified personnel should install or service UPS/batteries.

• Risk of electric shock, do not remove cover. No user serviceable parts inside, refer
servicing to qualified service personnel.

• The output may be energized even when the unit is not connected to a mains supply.

• Risk of electric shock! Hazardous live parts inside. This unit is energized from the
battery supply even when the input AC power is disconnected.

• To reduce the risk of electric shock, disconnect the UPS from the mains supply before
installing a computer interface signal cable. Reconnect the power cables only after signaling
interconnections have been made.

CAUTION !
Units are designed to operate on the concrete floor.

ABOUT THE BATTERIES

CAUTION: RISK OF ELECTRIC SHOCK!


The battery circuit is not isolated from the mains voltage. Hazardous voltages
may occur between the battery terminals and the ground!

• A battery can present a risk of electric shock or burn from high short circuit currents. The
following precautions should be taken when working on batteries :
* Remove watches, rings or other metal objects.
* Use tools with insulated handles.

• The batteries in this UPS are recyclable. Batteries must be disposed of according to local
environmental laws. The batteries contain lead and pose a hazard to the environment and human
health if not disposed of properly.

• Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate the
batteries. They contain an electrolyte which is toxic and harmful to the skin and eyes. If electrolyte
comes into contact with the skin the affected area should be washed immediately.
• The internal energy source (the battery) cannot be de-energized by the user.
• When changing batteries, install the same number and same type of batteries.

4 www.tescom-ups.gr

3
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

I. GENERAL DESCRIPTION

1.1 Introduction

TESCOM DS300SHP Series Uninterruptible Power Supplies are double-conversion;


on-line UPSʼs manufactured with the latest IGBT and PWM technology, to produce an
uninterruptible, fully DSP (Digital Signal Processor) controlled pure sine wave output to
critical loads.
TESCOM DS300SHP Series units are 3-phase in/3-phase out devices, and they are
installed between a three phase critical load, and a 3-phase+N mains supply
The advantages of using DS300SHP UPS:

• Power blackout protection:

If the mains power fails, the UPS continues to supply the critical load using the
energy stored in its batteries, keeping the load immune from power disturbances.

• Increased power quality:

The UPS has its own internal voltage and frequency regulating software, which
ensures that, its output to the critical load is maintained within close tolerances, independent
of voltage and frequency variations on the mains power lines.

• Fully digital control by three DSP controller for each UPS:

The UPS is controlled by 3 independent DSP chips which are communicating each
other continuously. Rectifier, Inverter and User Interface modules have separate DSPʼs to
achieve the highest performance. Each DSP module has many parameters to control and
monitor the system to have the best electrical power output and to help diagnostic.

• Increased noise rejection:

By rectifying the input AC power to DC power and then converting it back to AC


(Double-Conversion) any electrical noise present on the input mains supply line is effectively
isolated from the UPS output. Therefore the critical load is supplied with only clean and
uninterrupted AC power.

4 5
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

Basic Features:

• PWM and IGBT technology


• Pure sinusoidal output wave form and true on-line topology
• High input power factor (IGBT rectifier), Input current limiting
• Low input current THD (IGBT rectifier)
• Low output voltage THD
• High AC/AC and DC/AC efficiency (up to 94%)
• 3 separate DSP (Digital Signal Processor) control
• Cold-start feature
• Static By-Pass feature: Provides uninterruptable transfer to bypass source in case of
overload or UPS fault.
• Maintenance bypass switch and warning system, by-pass short circuit protection
• Generator operation sense input
• LCD alphanumeric display panel providing battery, load, voltage, power and status
information in detail to user
• Improved diagnostics and correct fault information
• Up to 500 event memory record system (15000 alarms or warnings total)
• Real time clock and calendar system
• Overload operation 10 minutes at 100% - 125% load, 1 minute at 125% - 150% load
• Output overload, over-current and short circuit protection, output current limiting
• Reliable operation at even 100% unbalanced load condition
• Non-linear load supply feature (CF 3:1)
• Double polarity battery (with common terminal)
• Automatic and manual battery test
• 3 separate maintenance clock counters
• Battery charge with current limiting
• Automatic and manual boost charge feature
• Battery deep discharge protection
• Temperature protection with 3 separate sensors
• Interactive communication
• Diagnostic and settings with PC ability
• One RS232 communication port
• 3 dry contact alarm relay outputs as standard (2 optional relay outputs)
• Improved remote monitoring panel system (optional)
• RS232 port multiplexer (optional)
• Direct network connection with optional SNMP support
• MODBUS Adapter (optional)
• Communication via Windows based T-MON software and remote monitoring and control of
UPS via modem
• Optional softwares compatible for most computer platforms
• Ability for labeling of UPSs by users
• Emergency power-off support
• Conformity to international and local standards
• AC input and output filters
• CE compliance
• Input, bypass phase order protection
• Enhanced accessory options
• 100.000 hours MTBF
• 2 years system warranty
• 10 years spare parts warranty
• Apple mobile device application for remote monitoring
• Small footprint area

5
6 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

1.2 Design Concept

S3

Maintenance
Bypass Switch

S2 SB
(F4-F5-F6)
Static
Bypass

3 PHASE
3 PHASE -
̃-
AC Output
MAINS I/P S1 K1 K2 S4
(F1-F2-F3)
Rectifier /
Charger
̃
Inverter
(F7-F8-F9)

S5
(F10-F11-F12)

Battery
(Dual Polarity)

S1 (F1-F2-F3) : Rectifier Input Switch / Fuse

S2 (F4-F5-F6) : Bypass Input Switch / Fuse

S3 : Maintenance Bypass Switch

S4 (F7-F8-F9) : Output Switch / Fuse

S5 (F10-F11-F12) : Battery Switch / Fuse

K1 : Rectifier Input relay

K2 : Inverter Output relay

7
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

1.2.1 DESCRIPTION OF BLOCKS

RECTIFIER: In DS300SHP Series UPSs, a DSP controlled IGBT rectifier with PWM technique is used to
increase input power factor (PFC) and to decrease input current harmonics (THDI).
The 3-level IGBT rectifier accepts 3-phase AC input and produces a dual polarity DC voltage for both
supplying the inverter and charging the batteries.

BATTERIES: Batteries are used as reserve DC power supply for the Inverter in case of mains failure. In
DS300SHP Series, batteries are connected in series with a center-tap output to obtain a dual polarity DC
supply.
Batteries are discharged by the inverter during mains failure. The discharged batteries are re-charged by
the IGBT Rectifier on a constant voltage / current limiting basis, if AC mains power is available.

INVERTER: It is manufactured by using the latest IPM and DSP (Digital Signal Processing) technologies,
and Pulse Width Modulation (PWM) technique. The Inverter converts the DC BUS voltage supplied by the
IGBT Rectifier and / or the batteries into a well regulated, fully digital controlled 3-phase AC voltage with
fixed voltage and frequency.
The output of the inverter is used to supply the critical loads connected to the UPS output.

STATIC TRANSFER SWITCH (STATIC BYPASS): This is an electronically controlled transfer switch,
which enables the critical load to be connected either to inverter output or to by-pass power source. During
normal operation, the load is supplied by the inverter output, but in case of an overload or a UPS failure it is
automatically transferred to the bypass source without any interruption.

MAINTENANCE BYPASS SWITCH (MBS): This is a manually controlled mechanical switch, which is used
to supply the critical load, using the bypass source, when the UPS is shut down for maintenance or
troubleshooting purposes.
The load is unprotected against mains supply disturbances and black-outs when it is connected to either
static or maintenance bypass supply.

1.2.2. OPERATING CONDITIONS OF UPS

UPS may be in one of the following operating conditions:

A. Normal Operation (If Mains supply is available):


All fuses and power switches are closed (except the Maintenance Bypass Switch), and the load is supplied
by the Inverter Output. During normal operation, the Rectifier supplies DC power to the Inverter and
charges the Batteries at the same time.
B. Battery Operation :
The Batteries are connected to the Rectifier output. In case of a mains failure (mains power outage or AC
input voltage out of tolerance), the Rectifier stops operating and the DC voltage necessary for the inverter
operation is supplied by the batteries. Therefore the AC voltage output supplying the critical load is not
interrupted, until the batteries are fully discharged. At the end of the discharging time the inverter is turned
off and it start again automatically, together with the rectifier, when the mains power is restored, and the
UPS returns o normal operation.
The Rectifier is also turned off and inverter operates on batteries during automatic or manual battery test
procedure.

C. By-Pass Operation :
If the Inverter output is overloaded or in case of a problem in the UPS, the static switch transfers the load to
the bypass supply without any interruption, provided that the bypass supply is available and within the
tolerated limits regarding voltage and frequency. At the end of the overloading period, if the fault condition
is restored, static switch transfers the critical load again to the inverter output. Note that, during operation
from the bypass supply, the critical load may be effected by any possible disturbances or power failure in
the bypass supply.

8 7 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

1.3 Front view of UPS Connection Panel

Repo Digital Bypass Aux2 Aux1


Input Input Relay Relay Relay
Output Output Output

Relay Output Contacts and Inputs

On / Off
Switch
RS232
Communication Socket

BATTERY

OUTPUT
SW
AC INPUT

BYPASS

MAINTENANCE
BYPASS

Figure 1.3.a 10-15 kVA Fuses and Switches Panel

8
9
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

Repo Digital Bypass Aux2 Aux1


Input Input Relay Relay Relay
Output Output Output

Relay Output Contacts and Inputs

RS232
On / Off Communication Socket
Switch

Parallel
Communication Socket
(Optional)

BATTERY

OUTPUT
SW
AC INPUT

BYPASS

MAINTENANCE
BYPASS

Figure 1.3.b 20 kVA Fuses and Switches Panel

10 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

1.4 Technical Specifications


SH MODELS / P.F = 0,9 DS310SH - DS310SH P DS315SH - DS315SH P DS320SH - DS320SH P
MODEL
TESCOM CODE UPS.0657 - UPS.0638 DS310HP DS315HP
UPS.0637 - UPS.0639 DS320HP
UPS.0634 - UPS.0640
SHB MODELS / P.F
Output =1
(KVA) DS310SHB - DS310SHB P DS315SHB - DS315SHB
10 kVA P
15 kVA DS320SH - DS320SHB P
20 kVA
TESCOM CODE Output (KW) UPS.0541 - UPS.0541 9 kW UPS.0637 - UPS.0635 13,5 kW 18 kW
UPS.0634 - UPS.0542
Power (kVA)Output Power Factor 10 15 0,9 20
INPUT
Voltage
INPUT 380/400 VAC 3P + N + G ± 20%   (415VAC +15%, -25% optional )
Frequency Number of Phases 3 Phases
50Hz / 60Hz, ± 5% + Neutral
Power factorInput Voltage 220/380, 230/400 or 240/415 Vac
≥ 0.99
Input
THDI (at 100% load)Voltage Tolerance ≤ 4% +20%
(depends ,on-25% (+15%
mains input at 240/415Vac)
conditions)
Input Power Factor (PF)
By-pass voltage 0,98+ -N 0,99
380/400 VAC 3 Phase (at± full
, 4 Wires, 10% load)
Input THDI
Voltage distortion ≤<=
10%4% (at full load)
Protection Input Frequency 50/60
Fuses, Voltage & Frequency Hz.
Tolerance
OUTPUT By-pass Voltage 220/380, 230/400 or 240/415 Vac 3 Phase + Neutral
Power (kW)By-pass Frequency SH Models = 9 / SHB Models =10 SH Models = 13.5 / SHB50/60 Models Hz.
= 15 SH Models = 18 / SHB Models = 20
Power factorRFI Level EN62040-2
SH Models = 0.9 / SHB Models = 1
Voltage OUTPUT 380/400 VAC 3P + N , ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Number of Phases 3 Phases + Neutral
Frequency tolerance Line synchronized: ± 2% / Free running: ± 0,1%
Output Voltage 220/380, 230/400 or 240/415 Vac
Efficiency 94%
Output Voltage Tolerance ±1%
Crest factor 3:1
Output Frequency 50/60 Hz.
Overload protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, -  > 150% load: by pass
Protection
Output Frequency Tolerance (Synchronous) ±2%
Fuses,Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
Voltage THDOutput Frequency Tolerance (Battery) < 2% (at 100% linear±0,2% load)
BATTERIESEfficiency (100% Load) up to 94%
Type Load Crest Factor VRLA AGM / GEL / NiCd 3:1
Output Voltage THD (linear load)
Number of batteries 60 (± 30) batteries<3%
Overload
Float charging voltage 125% ± 405 Load 10min. , 150% Load 1min.
VDC (adjustable)
BATTERY
End of discharge voltage ± 300 VDC (adjustable)
Battery cabinet External (attached cabinet at the bottom of UPS)
Total Number 60 blocks 12V (2x30 serial 60 batteries)
Battery ambient temperature 0 25°C
Float Charge Voltage (25 C) ± 405V DC
Battery protection 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
End of Discharge Voltage ± 300V DC
Automatic battery test Standard: every 72 hours (adjustable)
Battery Test Automatic and Manual
GENERAL
Boost Charge Available
Standards EN62040-1, EN62040-2, EN62040-3
COMMUNICATION INTERFACES
User interface 4 lines LCD panel, Mimic leds, 5 vector buttons, buzzer
Indicators RS232 Com Port P-N voltage, P-P voltage, Current, Power, 1 each
Crest Factor,standard
Frequency, PF, Service Time
Advanced External Temperature Measurement Input Self diagnostics, 3 maintenance time indicators, Available (standard)
Calibration over RS232,operating hour meter
RS485 Comm. Port
Communication RS232 serial port, 4 standard DRY Optional relays
contact alarm
Inputs Remote Monitoring Panel EPO input Optional
Genset kit SNMP Adapter Standard (programmable)Optional
Software Modbus Adapter Standard T-Mon UPS Management Software (3Optional clients + 1 server management)
Alarm logging 3 each outputs (load on bypass,
Standard: with time & date 512 events line failure, battery low)
Alarm Relay Contacts Power module2over
Protection each aux. outputs
temperature, Over current,(function
Temperature programmable)
high alarms
Digital Inputs
Operating temperature 0°C - 40°C 1 each
Emergency Power-Off Input
Protection degree Available
IP20 (standard)
Relative humidity 90% max. (non-condensing)
Altitude
ENVIRONMENT < 1000m. above sea level
0
Operating Temperature
Acoustic noise < 55 dBA 0 – 40 C< 57 dBA
Weight (kg)Operating Humidity 47,5 <= 49,5
%90 (non-condensing) 51
DimensionsAcoustic
(mm) HxWxDNoise 700x300x770 (without batt.)<55dB
/ 1000x300x800 (with 5ah<57dB <61dB
batt.) /1170x300x800 (with 7-9ah batt.)
OPTIONS Dimensions (WxDxH) (mm) 300 x 770 x 700
Adaptors Device Type and Protection Class SNMP, MODBUS, RS485, Class 1 –
Remote IP20
panel
Software Weight (Without Batteries) (app. kgs)T-Mon Admin Multi UPS monitoring42 10-50-100-200 clients, 46T-Mon Server 50-100-200 clients
50
Parallel operation Up to 8 units (Only SH P - SHB P models)

10
11
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

II. UPS INSTALLATION

2.1 Introduction
WARNING!!!

• Do not apply electrical power to the UPS equipment before the arrival of authorized service personnel.
• The UPS equipment should be installed only by qualified service personnel.
• The connection of the batteries and the maintenance should be done by qualified service personnel.
• Do not make any short- circuit to the battery poles. Because of high voltage and high short-circuit
current, there is risk of electrical shock or burn.
• Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches
and all metal objects. Only use tools with insulated handles. Wear rubber gloves.
This chapter contains location installation information of the UPS and the batteries. All the establishments
have their own specialties and needs. So in this part, the installation procedure is not being explained step
by step. Instead, general procedure and the applications are explained for the technical personnel.

2.2 Unpacking

The UPS is packed and enclosed in a structural cardboard carton to protect it from damage.
1) Inspect for damage that may have occurred during the shipment If any damage is noted, call the
shipper immediately and retain the shipping carton and the UPS.
2) Carefully open the carton and take the UPS out.
3) Retain the carton and packing material for future use.

Unit package contents:


1) A user manual and Guarantee certificate.
2) Battery cabinet and/or shelf (Optional)
3) Battery connection cables.

2.3 Equipment Positioning

ATTENTION: Units are designed to operate on the concrete floor.

1. The equipmentʼs installation place must be an easy serving place.


2. Install the UPS in a protected area with adequate air flow and free of excessive dust.
3. You must therefore allow for a minimum gap of 250 mm behind the unit to allow adequate air flow
4. Select a suitable place (temperature between 0°C and 40°C) and the relative humidity (%90 max)
5. It is recommended to place the equipment in an air-conditioned the room (24°C)
6. Temperature is a major factor in determining the battery life and capacity. Keep batteries away from
main heat sources or main air inlets etc.
7. In case of an operating the UPS in a dusty place, clean the air with a suitable air filtration system.
8. Keep out of your equipment from explosive and flammable items.
9. Avoid direct sunlight, rain, and high humidity.

WARNING!!! Check the capacity of the forklift if it is available for lifting.


DO NOT LEAN OR LIFT THE UPS CABINET AFTER THE BATTERIES HAVE BEEN
INSTALLED.

11

12 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

2.4 Connecting the UPS Power Cables

WARNING!!! A separate power line should be used to supply the UPS AC input. Never use the same
line to supply another electrical device. Do not use any additional cable to increase the
length of the UPSʼs input cable. It is advised to use an MCCB suitable for the input current
on the UPSʼs input line.

The connection of the electrical panel should be supplied by a grounded outlet. Otherwise, the UPS
and the load connected to the output will be left ungrounded. The grounding system must
be checked, and must be strengthen if required. Potential difference between ground and
neutral must be less than 3V AC.

Descriptions of the UPS input output cable connection terminals are shown in figure 2.1
Recommended input line cable and fuse ratings are given in the table below.

2
Recommended cable size (mm )
UPS power Input / output Battery
(kVA) Bypass input / Cable connections connections
Line input External Battery
UPS output
U-V-W-N +&-
2 2
10 10 10 6 16mm terminal 16mm terminal
2 2
15 10 10 10 16mm terminal 16mm terminal
2 2
20 10 10 10 16mm terminal 16mm terminal

NOTES: The neutral conductor should be sized for 1,5 times the output/bypass phase current. These
recommendations are for guideline purposes only and are superceded by local regulations
and codes of practice.
2.5 Safety Earth

The safety earth cable must be connected to the earth BUS BAR and bonded to each cabinet in the system
and also the earthing and neutral bonding arrangements must be in accordance with the local laws.

ATTENTION!!! Failure to follow adequate earthing procedures can result in electric shock hazard to
personnel, or the risk of fire.

2.6 Cable connection procedure

WARNING!!! All connections of the UPS must be done by qualified service personnel

After positioning the UPS, the cables must be connected as described below:
1. Verify all switches and fuses in front of the UPS are at “0” position. (OFF)

2. Connect the 3 phase AC input coming from the mains distribution panel to the AC input terminals as
shown on the label. (Figure 2.1)

ATTENTION!!!: ENSURE CORRECT PHASE SEQUENCE.


If there is a phase sequence error, UPS doesnʼt transfer the load to INVERTER output. If
you canʼt see SYNC:OK in the INFORMATION MENU on LCD, then change the input phase sequence.

3. Connect the output of the UPS to the load distribution panel.

4. Connect the battery groups. Refer to battery installation section.

12
13
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

WARNING :
- CHECK BOTH OF THE BATTERY GROUPS FOR CORRECT POLARITY AND VOLTAGE
- DO NOT TURN ON THE BATTERY SWITCH (F5) BEFORE STARTING THE UPS

5. Connect the copper earth bus, to the safety earth of the mains distribution panel.

NOTE : The earth and the neutral connections must be in accordance with the local rules.
WARNING: Note that the Input Neutral (N1) MUST also be connected to K10 terminal

2.6.1 Description of connection terminals of the UPS :

Şekil 2.2 10-15-20 kVA Cable Connection

• As shown on the power connection label of the UPS, U1, V1 and W1 phase of the incoming 3 phase
supply are used as the bypass inputs under normal conditions.

13
14 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

2.7 Battery Installation


WARNING!!! Be careful while connecting batteries.

ATTENTION!!! Open the battery switch/fuse before making any connection on the batteries.

The batteries associated with the UPS equipment are usually contained in a purpose-built battery cabinet.
In DS300SHP Series 10-15 and 20 KVA UPSs, there is enough space for 60 pieces of 12V 5-7-9Ah
maintenance free batteries.

Where battery racks are used, they should be sited and assembled in accordance with the battery
manufacturerʼs recommendations. In general, batteries require a well-ventilated, clean and dry environment
at reasonable temperatures to obtain efficient battery operation.

In general a minimum space of 10 mm must be left on all vertical sides of the battery block. A minimum
clearance of 20 mm should be allowed between the cell surface and any walls. All metal racks and cabinets
must be earthed.

1. Unpack each battery and check its terminal voltage with a suitable load. Any battery with terminal
voltage less than 10,5V must be charged before installation.

2. Please check the battery connecting hardware and documents. (cables, trays, connection diagrams)

3. Please locate suitable number of batteries on each rack, according to the battery installation and
connection diagram given with the unit.

4. Start locating the batteries from top to the bottom on the racks.

5. Be careful about the connection between the racks and polarities.

6. After interconnecting the batteries, connect “+”, “0” and “-“ leads of the batteries to the battery input
terminals on the UPS. Be careful to connect the batteries correctly and do not turn on (S5) before
checking all connections and before starting the UPS. In DS300SHP Series UPS, 60 blocks of
batteries are connected in series, in such a way that they form two strings of batteries with opposite
polarity; with a center tap connection to the NEUTRAL (N1-N2) internally.

NOTE THAT SEPARATE CABLES FROM EACH BATTERY GROUP SHOULD BE CONNECTED TO K2
TERMINALS TO FORM THE MIDPOINT CONNECTION.

WARNING!!! NEVER TURN ON S5 (BATTERY FUSE) WITHOUT CENTER POINT CONNECTION TO K2.

14
15
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

+- 30x12V 30x12V +--


+- Batteries +-
+- Batteries +-
+- +-
+- +

Figure 2.3 External Battery Connections (60x12V)

15

16 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

Figure 2.3a DS300SHP Series, 10-15-20 KVA Internal Battery Connections ( 60x12V 5Ah )

16
17
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

Figure 2.3a DS300SHP Series, 10-15-20 KVA Internal Battery Connections ( 60x12V 7-9Ah )

17

18 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

III. FRONT PANEL

3.1 Input

The front panel of UPS, consisting of a 4 lines alphanumeric display, 7 status lamps, plus 5 function keys,
allows the complete monitoring of the UPS status. The mimic flow diagram helps to comprehend the
operating status of the UPS. By using the function keys operator can moves on menus and change some
parameters.

Figure 3.1 Control panel oft he UPS

L1 : Maintenance bypass switch on indicator lamp


L2 : Load on bypass indicator lamp
L3 : Input voltage indicator lamp
L4 : Rectifier run pilot lamp
L5 : Battery operation indicator lamp
L6 : Load on UPS indicator lamp
L7 : Output switch on indicator lamp

There are 5 control buttons on the UPS Front panel ,ENTER button provides selection decleration,up and
down buttons provides to surf on menus, (+) and (-) buttons are used for adjustments or option selection.

3.2 Front Panel Menu Descriptions :


By using (↑), (↓) and ENTER buttons you can access the following menus. At the end of each menu there
is <ENTER> EXIT message will be showed, if you press enter you will exit to upper menu. All menus have
3 or 4 levels.

18
19
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

Ana menu (1.seviye)

Menu Usage
1 STATUS → Enter Status menu
2 MEASUREMENTS → Enter Measurements menu
3 ALARM LOGS → Enter Alarm logs menu
4 INFORMATION → Enter Information menu
5 OPTIONS → Enter Options menu
6 COMMAND → Enter Command menu
7 TIME → Enter Time menu
8 SERVİCE → Enter Service menu
9 PASSWORD → Enter Password screen
10 ADJUST → Enter Adjust menu
Goto 1

Sub menus (Level 2)

Level 1 Level 2 Page Level 3


STATUS Status of the UPS
MEASUREMENTS INPUT Input measurements
BYPASS Bypass measurements
INVERTER Inverter measurements
OUTPUT Output measurements
DC DC measurements
GENERAL General measurements
ENTER - EXIT
ALARM LOGS UPS LOG RECORD Page1
ENTER CLEAR LOG Page1
ENTER - EXIT
INFORMATION RS232 Comm 1:-- 2:-- Page1
Maximum UPS power Page1
Nominal voltage and frequency Page1
Inverter firmware version Page2
PFC firmware version Page2
Panel firmware version Page2
UPS Model Page3
Communication protocol Page3
Chassis nr Page3
ENTER - EXIT
OPTIONS LCD OPTIONS LCD panel options
COMM.OPTIONS Communication options
ALARM OPTIONS Alarm options
BYPASS OPTIONS Bypass options
ENTER - EXIT
COMMAND By-pass transfer Page1
Boost charge start Page1
Short battery test start Page1
Relay check Page2
Dialup modem programming Page2
Alarm sound ON/OFF Page3
Warning sound interval Page3
ENTER - EXIT
TIME Current time Page1
Current date Page1
Set hour Page2
Set minute Page2
Set day Page3

20 19 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

Level 1 Level 2 Page Level 3


Set month Page3
Set year Page3
Update time and date Page4
ENTER - EXIT
SERVİCE Operating hourmeter Page1
Maximum load Page1
ENTER Fault reset Page1
Fan maintenance hourmeter Page2
Batt.maintenance hourmeter Page2
General maintenance hourmeter Page2
Logout command Page3
ENTER - EXIT
PASSWORD Getting service code Page1
Type service password Page1
Type user password Page1
ENTER - EXIT
ADJUST
(in English) Group adjustments Automatic settings
Inverter factory options Options list
Rectifier factory options Options list
Panel adjustments Options list
AC input adjustments AC input settings
AC Bypass adjustments AC bypass settings
AC output adjustments AC output settings
DC adjustments DC settings
Power adjustments Power settings
ENTER - EXIT

20

21
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

3.2.1 MEASUREMENTS menu


All mesasured values of the UPS can be monitored from this menu.
Use up and down buttons to move on submenu

MEASUREMENTS / INPUT (Level 2)


All rectifier input measurements are located in this menu, use up and down buttons to move on submenu

MEASUREMENTS / INPUT Page 1 (Level 3)


P-N L1 L2 L3 Page header
Vinp: 221/222/223 V Phase to neutral measured AC input voltages
Iinp: 000/000/000 A Measured RMS AC input phase currents
…………………………….. Current alarm messages
Up previous page ,down next page

MEASUREMENTS / INPUT Page 2 (Level 3)


P-P L13 L21 L32 Page header
Vinp: 381/382/383 V Phase to phase measured AC input voltages
Finp: 49.6 Hz Measured rectifier input frequency
…………………………….. Current alarm messages
Up previous page ,down next page

MEASUREMENTS / INPUT Page 3 (Level 3)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page, down next page

MEASUREMENTS / BYPASS (Level 2)


All by-pass input measurements are located in this menu, use up and down buttons to move on submenu

MEASUREMENTS / BYPASS Page 1 (Level 3)


P-N L1 L2 L3 Page header
Vbyp: 221/222/223 V Phase to neutral measured AC bypass input voltages
OK OK -- Bypass voltage status
…………………………….. Current alarm messages
Up previous page, down next page

MEASUREMENTS / BYPASS Page 2(Level 3)


P-P L13 L21 L32 Page header
Vbyp: 381/382/383 V Phase to phase measured AC bypass input voltages
Fbyp: OK / 50.0 Hz Measured bypass input frequency
…………………………….. Current alarm messages
Up previous page, down next page

MEASUREMENTS / BYPASS Page 3(Level 3)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page, down next page

21
22 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

MEASUREMENTS / INVERTER MENU (Level 2)


All inverter measurements are located in this menu, use up and down buttons to move on submenu

MEASUREMENTS / INVERTER Page 1 (Level 3)


P-N L1 L2 L3 Page header
Vinv: 221/222/223 V Phase to neutral measured AC Inverter output voltages
Finv: 50.0 Hz Measured Inverter output frequency
…………………………….. Current alarm messages
Up previous page, down next page

MEASUREMENTS / INVERTER Page 2 (Level 3)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page, down next page

MEASUREMENTS / OUTPUT MENU (Level 2)


All UPS output measurements are located in this menu, use up and down buttons to move on submenu

MEASUREMENTS / OUTPUT Page 1 (Level 3)


P-N L1 L2 L3 Page header
Vout: 221/222/223 V Phase to neutral measured AC UPS output voltages
Iout: 00.0/00.0/00.0 A Measured AC RMS load currents
…………………………….. Current alarm messages
Up previous page, down next page

MEASUREMENTS / OUTPUT Page 2 (Level 3)


P-P L13 L21 L32 Page header
Vout: 381/382/383 V Phase to phase measured AC UPS output voltages
Fout: 50.0 Hz Measured UPS output frequency
…………………………….. Current alarm messages
Up previous page, down next page

MEASUREMENTS / OUTPUT Page 3 (Level 3)


Load 000/000/000 % Measured load percentage
KW 000.0/000.0/000.0 Measured output watt power
KVA 000.0/000.0/000.0 Measured output KVA power
…………………………….. Current alarm messages
Up previous page, down next page

MEASUREMENTS / OUTPUT Page 4 (Level 3)


PF: ---- ---- ---- Load power factor
C.F: 0.0 / 0.0 / 0.0 Load crest factor

…………………………….. Current alarm messages


Up previous page, down next page

MEASUREMENTS / OUTPUT Page 5 (Level 3)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page, down next page

22
23
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

MEASUREMENTS / DC MENU (Level 2)


All DC measurements are located in this menu, use up and down buttons to move on submenu

MEASUREMENTS / DC Page 1 (Level 3)


Vbat 405/-405 V Measured battery voltages
Ichrg 00.0/00.0 A Measured battery charge currents
Idisch 00.0/00.0 A Measured battery discharge currents
…………………………….. Current alarm messages
Up previous page, down next page

MEASUREMENTS / DC Page 2 (Level 3)


Batteries : 30 x 2 Batteries in one group
Par.Batts : 1 Parallel battery groups
Batt. A/H : 007 Ah Battery amper / hour rating
…………………………….. Current alarm messages
Up previous page, down next page

MEASUREMENTS / DC Page 3 (Level 3)


Backup time 0000 min Calculated remaining time

…………………………….. Current alarm messages


Up previous page, down next page

MEASUREMENTS / DC Page 4 (Level 3)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page ,down next page

MEASUREMENTS / GENERAL MENU


Temperature measurements are located in this menu, use up and down buttons to move on submenu

MEASUREMENTS / GENERAL Page 1 (Level 3)


TH1: ---- C Measured external sensor temperature
TH2: 24.2 C Measured battery cabinet inside temperature
TH3: ---- C Measured internal sensor temperature
…………………………….. Current alarm messages
Up previous page, down next page

MEASUREMENTS / GENERAL Page 2 (Level 3)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page, down next page

23
24 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

3.2.2 ALARM LOGS MENU


Use this menu to see the alarm log records

ALARM LOGS Page 1 (Level 2)


UPS LOG RECORD Page header
>001>081110 14:33:26 Event no ,date and time (left and right buttons move)
ENTER CLEAR LOG ENTER buton clears all log memory
…………………………….. Current alarm messages
Up upper line, down next line

ALARM LOGS Page 2 (Level 2)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page, down next page

3.2.3 INFORMATION MENU


Some usefull informations are located in this menu , use up and down buttons to move on submenu

INFORMATION MENU Page 1 (Level 2)


RS232 Comm: 1:-- 2-- RS232 activity indicator for com1 and com2
MAX Power: 60000 VA Maximum ups output power as VA
Nom:220/050 220/050 Nominal input, output voltage and frequency
…………………………….. Current alarm messages
Up previous page, down next page

INFORMATION MENU Page 2 (Level 2)


Inv version: 00001 Inverter module firmware version
Pfc version:00001 PFC rectifier module firmware version
Lcd version:00001 Front panel modul firmware version
…………………………….. Current alarm messages
Up previous page, down next page

INFORMATION MENU Page 3 (Level 2)


Model:CL360D Model name of the UPS
Protocol:TX301 Communication protocol version
Chassis nr: 123456 UPS chassis nr
…………………………….. Current alarm messages
Up previous page, down next page

INFORMATION MENU Page 4 (Level 2)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page, down next page

24
25
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

3.2.4 OPTIONS MENU

Use up and down buttons to move cursor on submenu at the end of page you move to next page. Menu
has 3 level structure, if user password is enabled some parameters requires user password.

Level 3 LCD panel options group


Panel language selection Page1
Button click ON/OFF Page1
LCD backlight brigthness Page2
Backlight delay Page2
Backlight dim.delay Page2
ENTER - EXIT Page3

OPTIONS / LCD OPTIONS Page 1 (Level 3)


>LANGUAGE:ENGLISH Left and right change panel language (P3330)
CLICK: ON/OFF Left and right buton click sound ON/OFF

…………………………….. Current alarm messages


Up upper line, down next line ,(+) or (-) options ,ENTER select an option

OPTIONS / LCD OPTIONS Page 2 (Level 3)


>BACKLIGHT:XXXXXXXXX Left and right LCD backlight brightness adjust
BL DELAY:CLOSED Backlight delay
BL DIM:CLOSED Back light half option selection
…………………………….. Current alarm messages
Up upper line, down next line ,(+) or (-) options ,ENTER select an option

OPTIONS / LCD OPTIONS Page 3 (Level 3)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page, down next page

Level 3 – Communication options


Remote control ON/OFF Page1
COM2 port function Page1
SNMP internal/external Page1
Relay 1 function selection Page2
Relay 2 function selection Page2
Relay 3 function selection Page2
Relay 4 function selection Page3
Relay 5 function selection Page3 Optional
Relay 6 function selection Page3 Optional
Relay 7 function selection Page4 Optional
Relay 8 function selection Page4 Optional
Relay 9 function selection Page4 Optional
Relay 10 function selection Page5 Optional
Relay 11 function selection Page5 Optional
Relay 12 function selection Page5 Optional
REPO input ON/OFF Page6
ENTER - EXIT Page7

25
26 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

OPTIONS / COMMUNICATION OPTIONS Page 1 (Level 3)


REMOTE CNTRL: ON/OFF Left and right remote control ON/OFF
>COM2:SERVICE PORT Com 2 serial port function selection
SNMP : INTERNAL/EXTERNAL SNMP adaptor location
…………………………….. Current alarm messages
Up upper line, down next line ,(+) or (-) options ,ENTER select an option

OPTIONS / COMMUNICATION OPTIONS Page 2 (Level 3)


>RELAY1: Left and right buton relay function selection
RELAY 2: Left and right buton relay function selection
RELAY 3: Left and right buton relay function selection
…………………………….. Current alarm messages
Up upper line, down next line ,(+) or (-) options, ENTER select an option

OPTIONS / COMMUNICATION OPTIONS Page 3 (Level 3)


> RELAY 4: Left and right buton relay function selection
RELAY 5: Left and right buton relay function selection (option)
RELAY 6: Left and right buton relay function selection (option)
…………………………….. Current alarm messages
Up upper line, down next line ,(+) or (-) options, ENTER select an option

OPTIONS / COMMUNICATION OPTIONS Page 4 (Level 3)


> RELAY 7: Left and right buton relay function selection (option)
RELAY 8: Left and right buton relay function selection (option)
RELAY 9: Left and right buton relay function selection (option)
…………………………….. Current alarm messages
Up upper line, down next line ,(+) or (-) options, ENTER select an option

OPTIONS / COMMUNICATION OPTIONS Page 5 (Level 3)


> RELAY 10: Left and right buton relay function selection (option)
RELAY 11: Left and right buton relay function selection (option)
RELAY 12: Left and right buton relay function selection (option)
…………………………….. Current alarm messages
Up upper line, down next line ,(+) or (-) options, ENTER select an option

OPTIONS / COMMUNICATION OPTIONS Page 6 (Level 3)


REPO : ON / OFF Emergency stop input enabled or disabled

…………………………….. Current alarm messages


Up upper line, down next line ,(+) or (-) options, ENTER select an option

OPTIONS / COMMUNICATION OPTIONS Page 7 (Level 3)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page, down next page

Level 3 Alarm options


Warning beep interval Page1
Warning log ON/OFF Page1
Status log ON/OFF Page1
ALF restart ON/OFF Page2
ENTER - EXIT Sayfa3

26 27
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

OPTIONS / ALARM OPTIONS Page 1 (Level 3)


>WARNING INTRVL:10 sc Warning beep interval adjustment in seconds
WARNING LOG:ON/OFF Left and right warning LOG record ON/OFF
STATUS LOG:ON/OFF Left and right status log record ON/OFF
…………………………….. Current alarm messages
Up upper line, down next line ,(+) or (-) options, ENTER select an option

OPTIONS / ALARM OPTIONS Page 2 (Level 3)


>ALF RESTART: USER/AUTO During mains restore start USER/AUTO (R1174/2)

…………………………….. Current alarm messages


Up upper line, down next line ,(+) or (-) options, ENTER select an option

OPTIONS / ALARM OPTIONS Page 3 (Level 3)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page, down next page

Level 3 - Bypass options


VAT transfer ON/OFF Page1
Gen set bypass ON/OFF Page1
Gen set synchron ON/OFF Page1
ENTER - EXIT Page2

OPTIONS / BYPASS OPTIONS Page 1 (Level 3)


VAT TRANSFER:ON/OFF Left and right VAT transfer system ON/OFF (R1174/3)
>GEN SET BYP:FORBID/FREE Left and right bypass to generator FORBID/FREE (R1174/5)
GEN SET SYNC:XTAL/SYNC Left and right generator synchron XTAL/SYNC (R1174/6)
…………………………….. Current alarm messages
Up upper line ,down next line ,(+) or (-) options ,ENTER select an option

OPTIONS / BYPASS OPTIONS Page 2 (Level 3)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page ,down next page

27
28 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

3.2.5 COMMAND MENU


This menu contains UPS commands be carefull while using commands.
Use up and down buttons to move cursor on submenu at the end of page you move to next page.
<ENTER> button applies the related command.

COMMAND MENU Page 1 (Level 2)


> ENTER <BYPASS> ENTER transfer the load to bypass
ENTER <BOOST> ENTER start boost charge mode
ENTER B.TEST > 405 ENTER start short battery test
…………………………….. Current alarm messages
Up upper line ,down next line ,(+) or (-) options ,ENTER apply command

COMMAND MENU Page 2 (Level 2)


> RELAY TEST:OFF Left and right test dry contact relays
ENTER : MODEM INIT ENTER initialize dialup modem

…………………………….. Current alarm messages


Up upper line ,down next line ,(+) or (-) options ,ENTER apply command

COMMAND MENU Page 3 (Level 2)


> ALARM SOUND: ON/OFF Left and right disable alarm buzzer
MIMIC LED TEST ENTER lamp test

…………………………….. Current alarm messages


Up upper line ,down next line ,(+) or (-) options ,ENTER apply command

COMMAND MENU Page 4 (Level 2)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page ,down next page

3.2.6 TIME MENU


You can see Time and date information of the RTC clock in the UPS ,also you can set date and time from
this menu.

TIME MENU Page 1 (Level 2)


>TIME : 15:47:20 Time of UPS RTC
DATE: 31/12/2010 Date of UPS RTC

…………………………….. Current alarm messages


Up previous page ,down next page

TIME MENU Page 2 (Level 2)


>SET HOURS : 15 Left and right set hours
SET MINS : 47 Left and right set minutes

…………………………….. Current alarm messages


Up upper line ,down next line ,(+) or (-) adjust

TIME MENU Page 3 (Level 2)


>SET DAY : 31 Left and right set day of month
SET MONTH : 12 Left and right set month
SET YEAR : 11 Left and right set year
…………………………….. Current alarm messages
Up upper line ,down next line ,(+) or (-) adjust

28
29
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

TIME MENU Page 4 (Level 2)


ENTER <UPDATE> ENTER apply new time and date settings

…………………………….. Current alarm messages


Up previous page ,down next page ,ENTER apply new time and date settings

TIME MENU Page 5 (Level 2)


ENTER - EXIT ENTER exit to upper menu

…………………………….. Current alarm messages


Up previous page ,down next page

3.2.7 SERVICE MENU


This menu contains some helpfull service information and some commands.
Use up and down buttons to move cursor on submenu at the end of page you move to next page.

SERVİCE MENU Page 1 (Level 2)


>HOURMETER:00075 Total operating hour of the UPS
MAXLOAD:015 020 025 % From power on recorded maximum power
ENTER<FAULT RESET> ENTER fault reset
…………………………….. Current alarm messages
Up upper line ,down next line

SERVİCE MENU Page 2 (Level 2)


FAN MAINT: 01000 Remaining hours to FAN maintenance
BAT MAINT :01200 Remaining hours to battery maintenance
GEN.MAINT: 00500 Remaining hours to general maintenance
…………………………….. Current alarm messages
If maintenance counters are disabled CANCEL word is shown.

SERVİCE MENU Page 3 (Level 2)


>LOGOUT: -- ENTER Exit from service login status

…………………………….. Current alarm messages


Up previous page ,down next page ,ENTER Logout from login status

SERVİCE MENU Page 4 (Level 2)


ENTER - EXIT ENTER to EXIT from menu and return to upper level

…………………………….. current alarms appears sequentially

3.2.8 ADJUST MENU


This menu is prepared for service purposes there is no user adjustable parameter in this menu.

29
30 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

3.2.9 USER PASSWORD


Some commands or some option selections are required user password, if menu position is required
password window comes to screen and UPS asks for user password. If you lost user password our service
personnel will recover your user password.
User password is 4 digits numbers, move cursor with left and right buttons, select digit and adjust the
number with up and down buttons. Do this for all digits and if password is typed completely press ENTER
button. If the password is correct A43 USER LOGIN message will be shown on the LCD panel of the UPS.

Password screen
-USER PASSWORD-
***************
* XXXX *
***************
Only authorized service personel has the useful password. Therefore it is hidden at above display.

3.3 Alarms and warning messages


The internal structure of the DS300SHP Series UPS is modular, these are:
-PFC Rectifier module
-Inverter module
-Front panel module

Module alarms and warnings are cathegorized according to modules at the front of the Alarm or warning
message module information is added:
-RXX Rectifier alarms and warnings
-AXX Inverter alarms and warnings
-LXX LCD front panel alarms and warnings

More then one alarm can be shown on the UPS front panel with time shared order. If 4 alarms are occurred
at the same time every 2 seconds 1 message will be showed, next 2 seconds 2.message will be showed
etc..

If A00 or R00 Alarm is shown on the LCD panel we understand that there is a system fault at the related
module. We saw the message in the A00 INV FAULT = XXXX or R00 PFC FAULT = XXXX format.
Numbers shown in X determines the status code which tells the problem to us. See status code table for
details of codes.

Rectifier module alarm codes


REC CODE = XXXX XXXX SYSTEM fault occured at the rectifer module
R00 REC FAULT = XXXX Fault Rectifier AC input voltage is high
CALL SERVICE !
R01 AC INPUT HIGH Alarm Rectifier AC input voltage is low
R02 LINE FAILURE Alarm Rectifier DC output voltage is high
R03 DC BUS HIGH Alarm The rectifier DC output voltage is high, rectifier stop
R05 FREQ TOLER Alarm Rectifier input frequcny out of tolerant
R06 OVERTEMPERATURE Alarm Rectifier heatsink temperature high
R07 BLACKOUT Alarm Short voltage blackout at rectifier AC input
R08 I/P OVERCURRENT Alarm Rectifier IGBT saturation alarm
R09 ROTATE PHASE Alarm Rectifier input phase sequency incorrect
R14 PFC MANUAL STOP Alarm Inverter module stopped rectifier
R15 DC LOW Alarm DC BUS voltage is lower then DC rectifier start voltage
R17 BATTERY TEST Warning Currently battery test is performing
R18 BOOST CHARGE Warning Currently rectifier is in boost charge mode
R19 AC HIGH Alarm AC Peak voltage is bigger then 20% of nominal range
R20 INPUT CB OPEN Warning Input CB is off
R21 PFC STOP Warning Currently Rectifier module stop
R22 POS CHG LIMIT Warning (+)Battery charge current limited
R23 NEG CHG LIMIT Warning (-)Battery charge current limited

30 31
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

R24 WAITING DC BUS Warning Rectifier is waiting DC BUS to raise for startup
R25 BATTERY FAILURE Warning Battery test failed
R26 BATT TEMP SENSOR Warning Battery temperature sensor is defected or not connected
R27 BATT TEMP HIGH Warning Battery ambient temperature is high
R29 PFC RESET Warning Rectifier module power on
R30 PLEASE WAIT Warning Rectifier waits as adjusted startup delay
R31 RECTIFIER START Warning Rectifier is in soft start stage

Panel module alarm codes


L01 TH1 TEMP HIGH Warning TH1 temperature is high
L02 TH2 TEMP HIGH Warning TH2 temperature is high
L03 TH1 TEMP LOW Warning TH1 temperature is low
L04 TH2 TEMP LOW Warning TH2 temperature is low
L05 FAN MAINT Warning FAN maintenance time
L06 BATTERY MAINT Warning Battery maintenance time
L07 OPT MAINTENANCE Warning Optional maintenance time
L08 TH1 SENSOR FAIL Warning TH1 temperature sensor failure
L09 TH2 SENSOR FAIL Warning TH2 temperature sensor failure
L10 ENTER FAULT RESET Warning UPS is waiting fault reset for startup
L11 BATT CB OPEN Warning External interactive battery switch is off
L12 GENERAL MAINT Warning General maintenance time
L13 PFC CAN COMM ERR Warning PFC module CAN communication timeout
L14 INV CAN COMM ERR Warning INV module CAN communication timeout

Inverter module alarm codes


INV CODE = 0XXX Current inverter modüle status code
A00 INV FAULT = XXXX Hata XXXX fault occured at the inverter module
CALL SERVICE !
A01 O/P OVERCURRENT Alarm IGBT saturation alarm on inverter module
A02 OVERTEMP SHUT Alarm Overtemperature at inverter power module
A03 BATT HIGH Alarm Inverter module measured battery voltage high
A04 OUTPUT V.LOW Alarm Inverter output voltage is low
A05 OUTPUT V.HIGH Alarm Inverter output voltage is high
A06 OVERLOAD SHUT Alarm Overload at UPS output
A07 SHORT CIRCUIT Alarm Short circuit at UPS output
A08 ON MAINTENANCE Alarm Maintenance by-pass switch on
A09 MANUAL BYPASS Alarm Load is transferred to by-pass from front panel
A10 BATTERY LOW SHUT Alarm Inverter measured battery voltage is low (shutdown level)
A11 REPO STOP Alarm External REPO input signal sensed
A12 DC BALANCE BAD Alarm Before inverter start fitler capacitors dont discharged
A13 PEAK CURRENT Alarm Very high current at the UPS output
A14 INV NOT START Alarm Inverter module start failed
A17 BYPASS FAILURE Warning By-pass input voltage failure
A18 BYPASS VOLT Warning By-pass input voltage out of tolerance
A19 BYP FREQ.TOLER Warning By-pass input frequency out og tolerance
A20 OVERLOAD Warning Currently the load exceeded 100% capacity
A21 OVERTEMP Warning Currently inverter power modul heatsink temperature is high
A22 OUTPUT OFF Warning There is no UPS output voltage
A23 ON BYPASS Warning Load is on bypass
A24 REVERSE CURRENT Warning Regenerative backfeed to UPS output

31
32 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

A25 INV RESET Warning Inverter module power on


A26 BATTERY LOW Warning Batteries are going to full discharge
A27 GENERATOR MODE Warning Generator set is running
A28 O/P PHASE LOSS Warning Anyone of the UPS output phases there is no voltage
A29 SYNCHRON BAD Warning Inverter is not synchron to by-pass input
A30 SHORT CIRCUIT Warning Short circuit occured at the UPS output currenty normal
A31 OUTPUT SWITCH Warning Output switch of the UPS is off
A32 SERVICE LOGIN Warning Service login active
A34 BYP ROTATE PHASE Warning By-pass phase sequency incorrect
A35 INV STOP Warning Inverter module interrupted
A36 INV DC DOWN Warning DC BUS voltage is less then 120 volts DC
A37 AC CURR LIMIT Warning Inverter output current limited
A38 FUSE FAILURE Warning Any fuse in UPS is blowned
A39 PSP FAILURE Alarm Inverter control board power supply out of tolerant
A40 INVERTER START Warning Inverter is in soft start stage wait for finish
A43 USER LOGIN Warning User logged in to UPS
A45 SERV.PASSWORD Fault For UPS startup service password required

If any alarm shown on the LCD panel without A00 and R00 message UPS will start automatically if the
conditions are normal. But if you see A00 or R00 code with any alarm together you must CALL SERVICE !
If the message is warning UPS continues to run there is no problem.

To support technical service status cods are used, each status code tells different event to us.

32
33
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

3.4 STATUS CODES

Inverter module status codes

INV L1-L2-L3 phase status codes


163 During soft start at the end of 4 seconds L1 output voltage is less then 30 volts AC
263 During soft start at the end of 4 seconds L2 output voltage is less then 30 volts AC
363 During soft start at the end of 4 seconds L3 output voltage is less then 30 volts AC
164 During soft start at the end of 4 seconds L1 output voltage is bigger then (output high/2) value
264 During soft start at the end of 4 seconds L2 output voltage is bigger then (output high/2) value
364 During soft start at the end of 4 seconds L3 output voltage is bigger then (output high/2) value
165 During inverter run the L1 phase AC output voltage is bigger then output high alarm level
265 During inverter run the L2 phase AC output voltage is bigger then output high alarm level
365 During inverter run the L3 phase AC output voltage is bigger then output high alarm level
166 During inverter run the L1 phase AC output voltage is less then output low alarm level
266 During inverter run the L2 phase AC output voltage is less then output low alarm level
366 During inverter run the L3 phase AC output voltage is less then output low alarm level
167 L1 phase by-pass SCR must be off but at there is AC voltage at the L1 output of the UPS
267 L2 phase by-pass SCR must be off but at there is AC voltage at the L2 output of the UPS
367 L3 phase by-pass SCR must be off but at there is AC voltage at the L3 output of the UPS
168 L1 phase overload shutdown
268 L2 phase overload shutdown
368 L3 phase overload shutdown
169 Overcurrent occured on L1 phase longer then allowed time
269 Overcurrent occured on L2 phase longer then allowed time
369 Overcurrent occured on L3 phase longer then allowed time
170 On L1 phase momentary short circuit conditions occured but now inverter is running
270 On L2 phase momentary short circuit conditions occured but now inverter is running
370 On L3 phase momentary short circuit conditions occured but now inverter is running
171 On L1 phase output short circuit occured output shutdown
271 On L2 phase output short circuit occured output shutdown
371 On L3 phase output short circuit occured output shutdown
172 Within time window 4 times L1 phase output is less then output low alarm level
272 Within time window 4 times L2 phase output is less then output low alarm level
372 Within time window 4 times L3 phase output is less then output low alarm level
173 Within time window 4 times L1 phase output is higher then output high alarm level
273 Within time window 4 times L2 phase output is higher then output high alarm level
373 Within time window 4 times L3 phase output is higher then output high alarm level
174 On L1 phase UPS output at last 100 milliseconds the alternance don't changed
274 On L2 phase UPS output at last 100 milliseconds the alternance don't changed
374 On L3 phase UPS output at last 100 milliseconds the alternance don't changed
175 On L1 bypass input phase at last 100 milliseconds the alternance don't changed
275 On L2 bypass input phase at last 100 milliseconds the alternance don't changed
375 On L3 bypass input phase at last 100 milliseconds the alternance don't changed
176 On L1 inverter output phase at last 100 milliseconds the alternance don't changed
276 On L2 inverter output phase at last 100 milliseconds the alternance don't changed
376 On L3 inverter output phase at last 100 milliseconds the alternance don't changed
177 L1 phase output current sensor open
277 L2 phase output current sensor open
377 L3 phase output current sensor open

33
34 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

INV L1-L2-L3 phase status codes


178 Inverter stopped but on inverter L1 phase output still DC voltage sensed
278 Inverter stopped but on inverter L2 phase output still DC voltage sensed
378 Inverter stopped but on inverter L3 phase output still DC voltage sensed
179 During inverter run at last 25 milliseconds the L1 phase output alternance is not changed
279 During inverter run at last 25 milliseconds the L2 phase output alternance is not changed
379 During inverter run at last 25 milliseconds the L3 phase output alternance is not changed
180 At the end of 4 times retry During soft start after 4 seconds still the L1 phase output voltage is
less then 30 volts AC
280 At the end of 4 times retry During soft start after 4 seconds still the L2 phase output voltage is
less then 30 volts AC
380 At the end of 4 times retry During soft start after 4 seconds still the L3 phase output voltage is
less then 30 volts AC
181 At the end of 4 times retry During soft start at the end of 4 seconds L1 output voltage is bigger
then (output high/2) value
281 At the end of 4 times retry During soft start at the end of 4 seconds L2 output voltage is bigger
then (output high/2) value
381 At the end of 4 times retry During soft start at the end of 4 seconds L3 output voltage is bigger
then (output high/2) value
182 During power on L1 phase bypass SCR must be off but at the L1 phase output there is AC
voltage
282 During power on L2 phase bypass SCR must be off but at the L2 phase output there is AC
voltage
382 During power on L3 phase bypass SCR must be off but at the L3 phase output there is AC
voltage
183 L1 phase by-pass SCR must be on but there is only positive alternance at the UPS output
283 L2 phase by-pass SCR must be on but there is only positive alternance at the UPS output
383 L3 phase by-pass SCR must be on but there is only positive alternance at the UPS output
184 L1 phase by-pass SCR must be on but there is only negative alternance at the UPS output
284 L2 phase by-pass SCR must be on but there is only negative alternance at the UPS output
384 L3 phase by-pass SCR must be on but there is only negative alternance at the UPS output
185 L1 phase by-pass SCR must be on but there is no output voltage at the UPS output
285 L2 phase by-pass SCR must be on but there is no output voltage at the UPS output
385 L3 phase by-pass SCR must be on but there is no output voltage at the UPS output
186 Output CB is energized but at the L1 phase output there is only positive alternance
286 Output CB is energized but at the L2 phase output there is only positive alternance
386 Output CB is energized but at the L3 phase output there is only positive alternance
187 Output CB is energized but at the L1 phase output there is only negative alternance
287 Output CB is energized but at the L2 phase output there is only negative alternance
387 Output CB is energized but at the L3 phase output there is only negative alternance
188 Output CB is energized but at the L1 phase output there is no AC voltage
288 Output CB is energized but at the L2 phase output there is no AC voltage
388 Output CB is energized but at the L3 phase output there is no AC voltage
189 During load on by-pass on the L1 output short circuit sensed
289 During load on by-pass on the L2 output short circuit sensed
389 During load on by-pass on the L3 output short circuit sensed
190 On L1 phase output reverse current sensed
290 On L2 phase output reverse current sensed
390 On L3 phase output reverse current sensed
191 During load on inverter ,on L1 phase by-pass line leakage current sensed
291 During load on inverter ,on L2 phase by-pass line leakage current sensed
391 During load on inverter ,on L3 phase by-pass line leakage current sensed

34
35
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

INV DC status codes


400 DC bus voltage high
401 Inverter controller board power supply 1 out of tolerant
402 Inverter controller board power supply 2 out of tolerant
404 Inverter stop because (+)DC bus voltage is low
405 Inverter stop because (-)DC bus voltage is low
406 Inverter within time window 4 times DC bus voltage is high

INV General status codes tablosu


500 Inverter received remote power off signal from RS232
501 Inverter received remote power off signal from CAN interface
502 Inverter sensed IGBT fault alarm 4 times within time window (30 minutes)
503 Inverter sensed Overtemperature alarm 4 times within time window (30 minutes)
504 Inverter sensed 3 phase AC O/P voltage low alarm 4 times within time window (30 minutes)
505 Inverter sensed 3 phase AC O/P voltage high alarm 4 times within time window (30 minutes)
506 Inverter Timeout error during eprom read or write
507 Inverter Memory checksum error
508 Inverter 3 output phases overloaded output shutdown
509 Inverter maintenance by-pass switch closed
510 Inverter IGBT fault error
511 Inverter overtemperature shutdown
512 Inverter 3 phase AC output voltage low
513 Inverter 3 phase AC output voltage high
514 Inverter output CB energized but still it looks like not energized
515 Inverter output CB not energized but stil it looks like energized
516 Inverter fault occured for restart password required
517 Inverter output CB energized but at the UPS output there is no 3 phase AC voltage
518 Inverter By-pass voltage is OK but at the UPS output there is no 3 phase AC voltage

INV Control activity status codes


612 INV Over RS232 interface battery quantity updated
613 INV Over CAN1 interface battery quantity updated
614 INV Over RS232 interface by-pass and output frequency updated
615 INV Over CAN1 interface by-pass and output frequency updated
616 INV Over RS232 interface By-pass and output voltage updated
617 INV Over CAN1 interface By-pass and output voltage updated
618 INV Over RS232 interface factory options updated
619 INV Over CAN1 interface factory options updated
620 INV Over RS232 interface user options updated
621 INV Over CAN1 interface user options updated
622 INV Over RS232 interface general test command received
623 INV Over CAN1 interface general test command received
624 INV Over RS232 interface transfer load to by-pass command received
625 INV Over CAN1 interface transfer load to by-pass command received
626 INV Over RS232 interface transfer load to UPS command received
627 INV Over CAN1 interface transfer load to UPS command received
628 INV Over RS232 interface Copy operating RAM to Factory settings zone command received
629 INV Over CAN1 interface Copy operating RAM to Factory settings zone command received
630 INV Over RS232 interface Copy factory settings to operating RAM command received
631 INV Over CAN1 interface Copy factory settings to operating RAM command received
632 INV Over RS232 interface Copy operating RAM to User settings zone command received
633 INV Over CAN1 interface Copy operating RAM to User settings zone command received
634 INV Over RS232 interface regenerative back feed activated
635 INV Over CAN1 interface regenerative back feed activated

35
36 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

636 INV Over RS232 interface fault reset command received


637 INV Over CAN1 interface fault reset command received
638 INV Over RS232 interface short battery test command received
639 INV Over CAN1 interface short battery test command received
640 INV Over RS232 interface long battery test command received
641 INV Over CAN1 interface long battery test command received
642 INV Over RS232 interface battery test cancel command received
643 INV Over CAN1 interface battery test cancel command received
644 INV Over RS232 interface start boost charge command received
645 INV Over CAN1 interface start boost charge command received
646 INV Over RS232 interface stop boost charge command received
647 INV Over CAN1 interface stop boost charge command received
648 INV Over RS232 interface PFC short stop command received
649 INV Over CAN1 interface PFC short stop command received
650 INV Over RS232 interface generator mode start command received
651 INV Over CAN1 interface generator mode start command received
652 INV Over RS232 interface start sleep mode command received
653 INV Over CAN1 interface start sleep mode command received
654 INV Over RS232 interface exit sleep mode command received
655 INV Over CAN1 interface exit sleep mode command received
656 INV Over RS232 interface service login command received
657 INV Over CAN1 interface service login command received
658 INV Over RS232 interface logout command received
659 INV Over CAN1 interface logout command received
660 INV Over RS232 interface user login command received
661 INV Over CAN1 interface user login command received
662 INV over RS232 service level fault reset command received
663 INV over CAN1 service level fault reset command received
664 INV over RS232 delete fault profile memory command received
665 INV over CAN1 delete fault profile memory command received
666 INV over RS232 start regenerative mode command received
667 INV over CAN1 start regenerative mode command received
668 INV over RS232 user level fault reset command received
669 INV over CAN1 user level fault reset command received

36
37
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

PFC rectifier status codes

PFC L1-L2-L3 phase status codes


1101 PFC L1 phase AC input current LEM sensor error
1201 PFC L2 phase AC input current LEM sensor error
1301 PFC L3 phase AC input current LEM sensor error
1102 L1 phase AC input voltage sample is irregular or DC
1202 L2 phase AC input voltage sample is irregular or DC
1302 L3 phase AC input voltage sample is irregular or DC
1103 PFC AC rectifier input voltage is lower then R2187 on L1 phase input
1203 PFC AC rectifier input voltage is lower then R2187 on L2 phase input
1303 PFC AC rectifier input voltage is lower then R2187 on L3 phase input
1104 PFC AC rectifier input voltage is higher then R2186 on L1 phase input
1204 PFC AC rectifier input voltage is higher then R2186 on L2 phase input
1304 PFC AC rectifier input voltage is higher then R2186 on L3 phase input
1105 PFC L1 phase AC peak input voltage is bigger 20% from nominal range value
1205 PFC L2 phase AC peak input voltage is bigger 20% from nominal range value
1305 PFC L3 phase AC peak input voltage is bigger 20% from nominal range value
1106 PFC L1 phase AC input current limited
1206 PFC L2 phase AC input current limited
1306 PFC L3 phase AC input current limited

PFC DC status codes


1400 PFC +DC bus voltage is higher then R2131 adjustment
1401 PFC -DC bus voltage is higher the R2131 adjustment
1402 PFC DC LEM current sensor error
1403 PFC module +DC BUS voltage high alarm repeated 4 times within R2166 time window
1404 PFC module -DC BUS voltage high alarm repeated 4 times within R2166 time window
1405 PFC board isolated power supply voltage failure
1406 PFC rectifier power component DC leakage sensed

PFC General status codes


1500 PFC remote emergency power off command received from RS232 or CAN interface
1501 PFC IGBT saturation alarm
1502 PFC overcurrent alarm
1503 PFC input CB not energized but still it looks like energized
1504 PFC input CB energized but still it looks like not energized
1505 PFC eeprom timeout error
1506 PFC eeprom memory error
1507 PFC modul IGBT fault alarm repeated 4 times within R2165 time window
1508 PFC modul overtemperature alarm repeated 4 times within R2167 time window
1509 PFC 3 phase AC power failure on UPS input (2.5 seconds later after mains failure)
1510 PFC 3 phase AC rectifier input voltage is high (2.5 seconds later after mains failure)
1511 PFC AC power failure on L1-L2 phases(phase to phase)
1512 PFC AC power failure on L1-L3 phases(phase to phase)
1513 PFC AC power failure on L2-L3 phases(phase to phase)
1514 PFC AC input voltage high on L1-L2 phases(phase to phase)
1515 PFC AC input voltage high on L1-L3 phases(phase to phase)
1516 PFC AC input voltage high on L2-L3 phases(phase to phase)

37
38 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

PFC Control activity status codes


1612 PFC Battery quantity updated over RS232 interface
1613 PFC Battery quantity updated over CAN interface
1614 PFC rectifier Input frequency range updated over RS232 interface
1615 PFC rectifier Input frequency range updated over CAN interface
1616 PFC factory settings updated over RS232 interface
1617 PFC factory settings updated over CAN interface
1618 PFC rectifier Input AC voltage range updated over RS232 interface
1619 PFC rectifier Input AC voltage range updated over CAN interface
1626 PFC over RS232 interface Test AC input signals command received
1627 PFC over CAN interface Test AC input signals command received
1628 PFC over RS232 interface copy operating RAM to Factory settings memory command received
1629 PFC over CAN1 interface copy operating RAM to Factory settings memory command received
1630 PFC over RS232 interface Copy factory settings to operating RAM command received
1631 PFC over CAN1 interface Copy factory settings to operating RAM command received
1632 PFC over RS232 interface Copy operating RAM to User settings memory command received
1633 PFC over CAN1 interface Copy operating RAM to User settings memory command received
1636 PFC over RS232 memory checksum lock command received
1637 PFC over CAN1 memory checksum lock command received
1638 PFC over RS232 interface start short battery test command received
1639 PFC over CAN1 interface start short battery test command received
1640 PFC over RS232 interface start long battery test command received
1641 PFC over CAN1 interface start long battery test command received
1642 PFC over RS232 interface cancel battery test command received
1643 PFC over CAN1 interface cancel battery test command received
1644 PFC over RS232 interface start boost charge mode command received
1645 PFC over CAN1 interface start boost charge mode command received
1646 PFC over RS232 interface stop boost charge command received
1647 PFC over CAN1 interface stop boost charge command received
1648 PFC over RS232 interface short stop command received
1649 PFC over CAN1 interface short stop command received
1650 PFC over RS232 interface start generator mode command received
1651 PFC over CAN1 interface start generator mode command received
1652 PFC over RS232 interface enter sleep mode comman received
1653 PFC over CAN1 interface enter sleep mode comman received
1654 PFC over RS232 interface exit from sleep mode command received
1655 PFC over CAN1 interface exit from sleep mode command received
1656 PFC over RS232 interface service login command received
1657 PFC over CAN1 interface service login command received
1658 PFC over RS232 interface logout command received
1659 PFC over CAN1 interface logout command received
1660 PFC over RS232 interface user login command received
1661 PFC over CAN1 interface user login command received
1662 PFC over RS232 interface service level fault reset command received
1663 PFC over CAN1 interface service level fault reset command received
1664 PFC over RS232 delete fault profile memory command received
1665 PFC over CAN1 delete fault profile memory command received
1666 PFC over RS232 interface backfeed regenerative energy to mains input command received
1667 PFC over CAN1 interface backfeed regenerative energy to mains input command received
1668 PFC over RS232 user level fault reset command received
1669 PFC over CAN1 interface user level fault reset command received

For detailed description of the status codes please refer to servic manual

38

39
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

3.5 Alarm messages and quick troubleshooting

Alarm codes and messages are showed at the 4.line of the LCD panel various messages tells different
events at some messages user can make some simple controls and they can decide that they must call
service or not.

NOTE : If R00 REC FAULT = XXXX or A00 INV FAULT = XXXX message is shown on the LCD
panel the other alarm or warning messages will not be shown.

R00 REC FAULT = XXXX


Call service

R01 AC INPUT HIGH


The input voltage of the UPS is very high check the AC input voltage if really high wait until the voltage is
normal.

R02 LINE FAILURE


The input voltage of the UPS is very low ,check the AC input voltage if the input voltage is low wait until the
AC input voltage is normal.

R03 DC BUS HIGH


Call service

R05 FREQ TOLER


The AC input voltage frequency of the UPS is out of tolerance wait until the input frequency is normal.

R06 OVERTEMPERATURE
Overtemperature at rectifier module call service.

R07 BLACKOUT
There is a short blackout at the AC input voltage of the UPS, this is temporary wait until the AC input voltage
is normal.

R08 I/P OVERCURRENT


Call service

R09 ROTATE PHASE


The phase sequency at the UPS input is reverse please refer to a technical personnel to provide correct
phase sequency

R14 PFC MANUAL STOP


This message shows that rectifier is stopped for any alarm reason check the other alarm shown together
with this alarm.

R15 DC LOW
DC BUS voltage or battery voltage is very low wait 10 minutes then call service

R17 BATTERY TEST


For 30 seconds UPS is performing battery test at the end of the test UPS decides batries are OKEY or not,
then UPS returns to normal operation automatically.

R18 BOOST CHARGE


For 10 hours boost charge mode is activated from UPS, at the end of 10 hours UPS returns to normal
charge mode

R19 AC HIGH
The AC input votage of the UPS is 20% higher then nominal input votage, wait until the AC input voltage is
normal.

39
40 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

R20 INPUT CB OPEN


The input of the UPS is isolated from mains power with contactor ,this message will be shown with another
alarm always. Check the other alarm code.

R21 PFC STOP


Rectifier is stopped itself wait it must start again, another alarm code shows the reason of the rectifier stop.
Wait for 1 minute if alarm continues call service.

R22 POS CHG LIMIT, R23 NEG CHG LIMIT


This message is normal if the battery charge current is rached to limit value during battery charge.

R24 WAITING DC BUS


The DC BUS voltage of the UPS is not enough to startup wait 2 minutes if message continues call service.

R25 BATTERY FAILURE


At the last battery test one or more defected batteries found, call service.

R26 BATT TEMP SENSOR


Battery temperature sensor mulfunction, call service.

R27 BATT TEMP HIGH


If batteries are located at the outside of the UPS cabinet check battery ambient temperature if hot use air
cooling system. If batteries are internal check the UPS ambient temperature if normal call service.

L02 TH2 TEMP HIGH, L04 TH2 TEMP LOW


UPS TH2 cabinet inside temperature is out of tolerance check the followings:
-If UPS air inlets and outlets covred by dust clean
-If any material prevents air flow at UPS air inlets or outlets take the material
-If UPS ambient temperature is high then 45 C ,use air cooling system

L05 FAN MAINT


Maintenance due of the cooling fans of the UPS, call service.

L06 BATTERY MAINT


Maintenance due of the UPS batteries, call service.

L08 TH1 SENSOR FAIL, L09 TH2 SENSOR FAIL


TH1 or TH2 temperature measurement sensors are defected, call service.

L10 ENTER FAULT RESET


Call service

L11 BATT CB OPEN


The battery switch of the UPS is OFF, in this case UPS runs normally but if mains failure alarm occures the
output voltage of the UPS shutdown. Please turn ON the battery switch.

L12 GENERAL MAINT


Maintenance due of the general maintenance, call service.

L13 PFC CAN COMM ERR


Call service.

L14 INV CAN COMM ERR


Call service.

A00 INV FAULT = XXXX


Call service.

40
41
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

A01 O/P OVERCURRENT


Check the new load which are connected to UPS nowadays the total load power maybe exceeds maximum
power of the UPS. Otherwise call service.

A02 OVERTEMP SHUT


Inverter modüle heatsink temperature is out of tolerance check the followings:
-If UPS air inlets and outlets covred by dust clean
-If any material prevents air flow at UPS air inlets or outlets take the material
-If UPS ambient temperature is high then 45 C, use air cooling system

A03 BATT HIGH


DC BUS voltage or battery voltage of the UPS is high, if inductive load is used this event sometimes
occures if alarm continues call service.

A04 OUTPUT V.LOW


The output voltage of the inverter is low call service

A05 OUTPUT V.HIGH


The output voltage of the inverter is high call service

A06 OVERLOAD SHUT


The total load which is connected to the UPS is exceeded 100% capacity of the UPS if message continues
call service they will check UPS, but probably you need higher power range UPS.
Note: Some load inrush curents causes overload event then current is normal.

A07 SHORT CIRCUIT


There is short circuit at the output of the UPS check installation and loads.

A08 ON MAINTENANCE
The maintenance by-pas switch of the UPS is ON <1>position, there is a lock on this switch which prevents
unauthorized personnel use.

A09 MANUAL BYPASS


Load is transferred to by-pass from UPS command menu, transfer the load to the inverter.

A10 BATTERY LOW SHUT


The DC BUS or battery voltage of the UPS is low. If the mains is OKEY call service.
If the there is nomains voltage wait until mains OKEY UPS will start automatically.

A11 REPO STOP


External repo button pressed, to restart turn off and on the UPS

A12 DC BALANCE BAD


Call service

A13 PEAK CURRENT


Very high curent measured at the UPS output, check loads

A14 INV NOT START


Call service

A17 BYPASS FAILURE, A18 BYPASS VOLT, A19 BYP FREQ.TOLER


The input of the UPS or by-pass input of the UPS voltage or frequency is out of tolerance ,wait until the
voltage is normal if message continues long time check input fuses ,switches etc. at the distrubution panel.

A20 OVERLOAD
UPS is currently running but the load percentage exceede 100% capacity of the UPS ,if this situation
continues inverter will stop after a delay.Check the loads at the UPS output.

41
42 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

A21 OVERTEMP
Inverter module heatsink temperature is highcheck the followings:
-If UPS air inlets and outlets covred by dust clean
-If any material prevents air flow at UPS air inlets or outlets take the material
-If UPS ambient temperature is high then 45 C, use air cooling system

A22 OUTPUT OFF


During mains failure if the battery backup time is finished this message is normal ,there is no energy so the
UPS shutdown the output voltage.
If this message is permanent call service, otherwise wait until the message is deleted automatically from
LCD screen.

A23 ON BYPASS
From any reason UPS transferred the load to bypass, check the other alarm code which shown together
with this alarm it shows the by-pass reason.
If the UPS stays at this position for a long time call service.

A24 REVERSE CURRENT


Any load such as motorsa are connected to UPS output and the load in regenerative mode ,it is applying
reverse energy to the UPS output. Call service

A25 INV RESET


This is the power on indicator of the inverter modüle, during ower on for 10 seconds this message will be
shown at the end of 10 seconds the mesage will be cleared.

A26 BATTERY LOW


The DC BUS or battery voltage of the UPS is low, still UPS is running but DC voltage is going down.
If this alarm occures during mains failure it means that there is no energy from batteries this is normal.
But if this alarm occures during mains OKEY call service.

A27 GENERATOR MODE


UPS is running in generator mode when generator set stops UPS returns to normal operating mode
automatically.

A28 O/P PHASE LOSS


Call service

A29 SYNCHRON BAD


This is only warning that showa the inverter and by-pass voltages are not synchron to each other ,there is
nothing to do wait until they matches.

A30 SHORT CIRCUIT


Shorter then 4 alternance (40 milliseconds) short circuit occured at theoutput of the UPS, now UPS
isrunning but you must check the installation and loads.

A31 OUTPUT SWITCH


The output switch of the UPS is OFF <0>position, turn on <1>position the output switch

A32 SERVICE LOGIN


Service ersonnel logged in to UPS this is only warning.

A34 BYP ROTATE PHASE


The phase sequency of the by-pass source is not match the UPS output phase sequency. Please check
the by-pass phase sequency if wrong change phases.

A35 INV STOP


The message shows that the inverter modüle stopped from any reason ,check the other alarm code which
is shown together with this mesage.

42
43
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

A36 INV DC DOWN


Call service

A37 AC CURR LIMIT


Alarm shows us the output current is very high (higher then 150%) the UPS limited the output current. This
status is temporary but if continues call service.

A38 FUSE FAILURE


Call service

A39 PSP FAILURE


Call service

A43 USER LOGIN


User logged in to UPS this is only warning

A45 SERV.PASSWORD
Call service , UPS start impossible

43
44 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

IV. OPERATING INSTRUCTIONS

4.1 INTRODUCTION

After all the electrical connections of UPS have been made and while all the circuit breakers and switchtes
of the device are turned OFF (at “0” position);

1. Check the polarities of battery connections:


K1 : + V (nominal voltage +360V, float charge voltage +405V)
K2-K2 : 0 V (common terminal for ʻʼ+ʼʼ and ʻʼ-ʻʼ battery groups)
K3 : - V (nominal voltage -360V, float charge voltage -405V)
2. Check 3-phase AC input and neutral connections (care should be taken fort he phase order).

ATTENTION!!! TWO CABLES FOR EACH BATTERY GROUP SHOULD BE USED FOR EXTERNAL
BATTERY CONNECTION, AND THE COMMON POINT CONNECTION SHOULD BE MADE ON K2
TERMİNAL BLOCK!
WARNING ! : UPS should never be operated without neutral connection.

3. Check the output load connections of UPS.

4.2 OPERATING UPS IN ONLINE MODE

4.2.1 Starting UPS from a completely shut down position:

1. Turn ON S1 (AC Input) switch (switch to ʻʼ1ʼʼ position)


2. Turn ON S2 (Bypass) switch (switch to ʻʼ1ʼʼ position)
3. Turn ON S4 (AC Output) switch (switch to ʻʼ1ʼʼ position)

ATTENTION!!! BYPASS VOLTAGE WILL BE CONNECTED TO THE OUTPUT TERMINALS OF


UPS WHEN THE ON/OFF SWITCH (S7) IS SWITCHED ON !

4. Turn on S7 (On/Off) switch (to ʻʼ1ʼʼ position). LCD panel activates, and ʻʼINV RESET” or “PFC RESETʼʼ
message appears on the display meaning that the rectifier starts to operate.

5. A few seconds later red bypass light (L2) on front panel turns off and gren inverter light (L6) turns on.
L6 light indicates that the UPS has started normal operation and generating uninterruptable power for
the critical load.

6. Turn on S5 switch (to “1” position) to connect the battery group to UPS.

7. UPS is ready and in normal operation now.

4.2.2 Shutting down the UPS

After closing all the critical loads supplied by the UPS output:

1. Turn off S4 (AC Output) switch (to ʻʼ0ʼʼ position).


2. Turn off S7 (On/Off) switch (to ʻʼ0ʼʼ position).
3. Turn off S5 (Battery) switch (to ʻʼ0ʼʼ position).
4. Turn off S2 (Bypass) switch (to ʻʼ0ʼʼ position).
5. Turn off S1 (AC Input) switch (to ʻʼ0ʼʼ position).

After performing the above procedure, UPS is completetely shut-down. In this case PFC rectifier and
inverter is not operating and the batteries are not being charged.

45
44
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

4.2.3 Switching the UPS from a Normal Operation to Maintenance Bypass Condition

1. Enter COMMANDS menu by using UP and DOWN buttons on front panel during normal operation.
Select ENTER<BYPASS> command by using again the UP and DOWN buttons and pres ENTER
button. The critical load is transferred to bypass supply in this case and it is shown at LCD display with
“A09 MANUAL BYPASS” message. Besides L6 (load on UPS) light on front panel will be off and L2
light (bypass) will be on.
2. Turn on S3 (Maintenance Bypass) switch (after unlocking and taking away the padlock on it) to ʻʼ1ʼʼ
position.
3. Turn off S7, S5, S1, S2 and S4 switches (to ʻʼ0ʼʼ position).

In this case, bypass voltage is connected directly to the output of UPS and the critical load is supplied via
maintenance bypass switch. No AC or DC supply is connected to the inside and the circuits of UPS.

4.2.4 Switching the UPS from a Maintenance Bypass Condition to Normal Operation

1. Turn on S1 (AC Input) switch (to ʻʼ1ʼʼ position).


2. Turn on S2 (Bypass) switch (to ʻʼ1ʼʼ position).
3. Turn on S4 (AC Output) switch (to ʻʼ1ʼʼ position).
4. Turn on S7 (On/Off) switch (to ʻʼ1ʼʼ position). LCD panel activates, and main menu will appear at the
display. Also “A08 ON MAINTENANCE” message shown and the inverter will not start yet.
5. Turn off S3 (Maintenance Bypass) switch (to ʻʼ0ʼʼ position). Inverter will start automatically following the
turning off of S3 switch.
6. Connect the batteries by turning on S5 (Battery) switch (to ʻʼ1” position).

Now UPS is ready for uninterruptable operation.

46 45 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

4.3 UPS Behavior During Mains Outage

When the mains voltage is not available " R02 LINE FAILURE " message appears on LCD display. Sound
warning on and off is heard at the same time. UPS continues to supply the critical loads by converting the
battery voltage to AC voltage and provides operation without data losses or any other fault. Battery
autonomy time may be prolonged by shutting down the unnecessary loads for that moment.

But do not turn on these loads again during battery operation.

After a short period of time when the line voltage is available again, UPS returns to normal operation
automatically and the alarm message on the display disappears.

Shut down the critical loads in a period of minimum possible autonomy time (depends on the Ah capacity,
charge status, age of the batteries, actual load percentage of UPS and the ambient temperature).
Otherwise critical loads will be out of power at the end of battery autonomy time.

“A26 BATTERY LOW” message appears first on front panel display during battery operation if battery
voltage drops below a defined level.

“A10 BATTERY LOW SHUT” message appears on front panel display when the battery voltage drops to
the end of discharge voltage and UPS shuts itself down. Critical loads will be out of electrical power.

If a reserved generator in the system and if itʼs available, that will start to supply the necessary electrical
power to UPS input and batteries start to be charged immediately. By means of using UPS together with a
immediately available generator system, battery discharge time decreases and so they will be charged
quickly after a mains outage.

46
47
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

V. PARALLEL OPERATION (DS - SHP MODELS)


5.1 Introduction

Two (or more) identical DS300SHP series UPSs can be interconnected for parallel operation.
The main purposes for parallel use of DS300SHP series UPSs are:

-Redundancy for Increased Reliability


-Power Increase

Although recent UPS designs are perfect and have high MTBF figures, a second (or more) UPS can be
used in parallel with the first one, for supplying the critical load in case of any possible failure of the first
UPS. In such an application the faulty UPS is isolated automatically from the parallel system and the other
UPS (or UPSs) continues to supply the critical load. Use of Redundant UPSs in parallel, therefore, provides
increased reliability for the critical load connected to the parallel system output.

If power demand increases in a certain UPS application exceeding the power rating of an already
installed stand-alone UPS, a second (or more) UPS of the same model and power rating can be added in
parallel to the existing UPS to increase the output power capacity.

Schematic diagram of parallel connection of two DS300SHP series UPS units is shown in Figure 4.1

S3

Maintenance
Bypass
Switch SB
S2
(F4-F5-F6) Static
Bypass
-
S1
(F1-F2-F3)
K1 ̃-
Rectifier / Inverter ̃
K2 S4
(F7-F8-F9)
Charger S5
(F10-F11-F12)

Battery
(Dual Polarity)
3 PHASE
3 PHASE
AC
MAINS I/P S3 Output

Maintenance
Bypass
SB
S2
(F4-F5-F6) Static
Bypass
-
S1
(F1-F2-F3)
K1 ̃
Rectifier /
-
Inverter ̃
K2 S4
(F7-F8-F9)
Charger S5
(F10-F11-F12)

Battery
(Dual Polarity)

Figure 4.1 Parallel Connection of two UPSs

48 www.tescom-ups.gr

47
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

The AC inputs of all UPSs in the parallel system are connected to the same mains, and all the AC
outputs are connected to each other. Each UPS has its own battery group. The critical load is connected to
the common output of the parallel system. There are also some signal cable connections between the UPS
units necessary for parallel operation, and will be described later.

5.2 Parallel Operation Mode settings of DS300SHP Series UPSs

NOTE: Parallel operation hardware (parallel communication board) are not installed in a
standard DS300SHP series UPS, but parallel operation option is available and can easily
be added to all UPSs.

N+1 REDUNDANT parallel operation

For parallel operation some parameters must be given by the service personnel these are:
1- Select Parallel mode must be selected from ADJUST MENU (ADJUST MENU/INV FACTORY
OPTIONS/OPERATING MODE:)
2- A unique UPS network no must be given from ADJUST MENU(ADJUST MENU/INV FACTORY
OPTIONS/UPS NO:) (each UPS must be assigned a unique UPS number)
3- Minimum UPS quantity requirement must be given from ADJUST MENU (ADJUST MENU/INV
FACTORY OPTIONS/N+1 MINIMUM:) (N number in the system)
Shown parameters can not be adjust by the user, these parameters are located on ADJUST MENU also
adjust menu is password protected only authorized service personnel can access this menu.

PARALLEL mode

This mode is used for operation of at least two (1+1 configuration) UPS units connected in parallel for
increased reliability. If this mode is selected, the load is shared equally by each UPS available in the
parallel system (N+1 numbers of UPS units), during normal operation.

In case of a failure of any one of the UPS units, the faulty UPS is isolated from the parallel system and
the critical load is supplied by the remaining N number of UPSs. If any one of those UPS units fails too,
then the critical load is transferred to bypass supply via the static bypass switches of the parallel connected
UPSs. If the faulty UPS returns to normal operation, it joins the parallel system again and starts sharing the
load.

In parallel mode, the total VA rating of the parallel system is equal to the VA rating of a single UPS
multiplied by N.

In parallel mode, you will see ʻʼPARALLEL MODE /MSʼʼ(master UPS) or ʻʼPARALLEL MODE /slʼʼ (slave
UPS) message on the LCD panels of all the all UPS units.

More detailed diagrams for two (or more) DS300SHP series UPSs connected in parallel are given in
Figures 4.2 and 4.3

Communication between parallel UPSs are provided over one pair cable (PCC06). The length of the cable
is limited up to six meters.
A link cable is used for connecting the first UPS to the last UPS ,this cable is redundant for normal
communication cables.
If communication is lost on SLAVE UPS the UPS will shutdown but the MASTER UPS will go on running if
the communication is provided at SLAVE UPS it will start automatically again.

49
48
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

Figure 4.2 DS300SHP Series Parallel UPS Signal Cable


(PCC06) Connections

Parallel Parallel Parallel Parallel


Port 1 Port 2 Port 1 Port 2

Figure 4.2.a 2 units in parallel if port2 jumper is


not shorted

Parallel Parallel Parallel Parallel Parallel Parallel


Port 1 Port 2 Port 1 Port 2 Port 1 Port 2

Figure 4.2.b

3 units in
parallel

Parallel Parallel Parallel Parallel Parallel Parallel Parallel Parallel


Port 1 Port 2 Port 1 Port 2 Port 1 Port 2 Port 1 Port 2

Figure 4.2.c 4 units in parallel


All the units must be set for the same operation mode and must have a different UPS number.

CAUTION !!! You must never set the operation modes of parallel connected UPS units to
“ONLINE”, otherwise serious damage may occur in UPSs.

49
50 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

MAIN AC INPUT
U1
V1
W1
N1
BYPASS AC INPUT
U2
V2
W2
N2

K11
K11

K11

K10
K10

K10

K4
K4

K4

K5
K6
K7
K5
K6
K7

K5
K6
K7

K8
K9
K8
K9

K8
K9
+ K1 + K1 + K1

- K2 - K2 - K2
UPS1 UPS2 +
UPS3
+ K2 + K2 K2

- K3 - K3 - K3

AC OUTPUT1 BATTERIES AC OUTPUT2 AC OUTPUT3


BATTERIES BATTERIES K12 K13 K14
K12 K13 K14 K12 K13 K14

U V W N U V W N U V W N

FUSES FUSES FUSES

AC
LOAD BRAKE
SWITCH

AC DISTRIBUTION
U V W N
LOAD

Figure 4.3 DS300SHP Series Parallel UPS Power Connections

Note: As seen in the figure, the outputs of parallel UPS units should be connected to each other
using an AC distribution board.

50

51
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

ATTENTION!!!

The cables from input distrubution panel to the UPS by-pass input must be of the same size and
length for proper bypass load sharing.

The cables from each UPS output to the load distribution panel must be of the same size and length
for proper load sharing during parallel operation.

5.3 Parallel mode status codes of the UPS

801 Status code


Status Inverter system fault
Description The UPS number of this UPS is same with MASTER UPS in parallel system
Restart Change UPS number and Restart UPS again
Returning to fault Directly fault
In parallel system each UPS must have a unique UPS number. If the UPS number is used in system ,the last
UPS joined to parallel system produces this status code

802 Status code


Status Inverter system fault
Description The Operation mode of this UPS is different with MASTER UPS in parallel system
Restart Change operating mode and Restart UPS again
Returning to fault Directly fault

In parallel UPS system master and slave UPS operating modes must be same

803 Status code


Status Inverter system fault
Description Parallel Operation mode is selected but there is no paralleling board
Restart Install parallel communication board and Restart UPS again
Returning to fault Directly fault

804 Status code


Status Inverter system fault
Description Parallel communication connector disconnected in slave mode inverter down
Restart Connect parallel communication cable and Restart UPS again
Returning to fault Directly fault

Check the followings


- Parallel or synchron mode selected but parallel data cable unplugged
- Call service

805 Status code


Status Inverter warning
Description Parallel communication connector disconnected in master mode inverter continues
to run
Restart Connect parallel communication cable and wait
Returning to fault --

Check the followings


- Parallel or synchron mode selected but parallel data cable unplugged
- Call service

52 www.tescom-ups.gr

51
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

806 Status code


Status Inverter system fault
Description In parallel system SLAVE UPS started but the output voltage is not match to my
inverter output voltage
Restart Restart UPS again
Returning to fault Directly fault

Check the followings


- Check the UPS nominal voltage ratings
- Call service

807 Status code


Status Inverter system fault
Description In parallel system UPS decided to be master but there is AC voltage at the UPS
output
Restart Restart UPS again
Returning to fault Directly fault

Check the followings:


-Turn off all UPSs in parallel system and restart again
-If the code is still showned call service

820 Status code


Status Inverter alarm
Description In parallel system while in slave mode , MASTER communication lost for 8
periodes ,inverter stopped
Restart Wait until UPS provide MASTER communication
Returning to fault --
Fault code --

821 Status code


Status Inverter alarm
Description MASTER syncron failed while SLAVE UPS ,inverter stopped
Restart Wait until UPS provide MASTER synchronization
Returning to fault --
Fault code --

822 Status code


Status Inverter alarm
Description MASTER frequency exceeded minimum limit ,inverter stopped
Restart İf master frequency is okay automatic
Returning to fault --

Check the followings:


-Check each UPS output frequency selection in parallel system

52
53
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

823 Status code


Status Inverter alarm
Description MASTER frequency exceeded maximum limit ,inverter stopped
Restart İf master frequency is okay automatic
Returning to fault --

Check the followings:


-Check each UPS output frequency selection in parallel system

824 Status code


Status Inverter alarm
Description MASTER DC voltage zone 7,My DC voltage zone 1 inverter down
Restart İf mains input voltage is okay automatic
Returning to fault --

Check the followings:


-Check the mains input power of the UPS
- If input power is OK wait until batteries are fully charged
- If the mains input power is shurdown check the other UPSs mains input power (in parallel system if the
same A/H rating batteries are used at each UPS the battery discharge timebe same for each UPS) If the
other UPS is continue to run check the batteries of this UPS.
-Call service

825 Status code


Status Inverter alarm
Description SLAVE DC voltage zone 7,My DC voltage zone 1 inverter down
Restart İf mains input voltage is okay automatic
Returning to fault --

Check the followings:


-Check the mains input power of the UPS
- Check the battery status of this UPS
- Call service

826 Status code


Status Inverter alarm
Description MASTER DC voltage zone 7,My DC voltage zone 1 trying to join system
Restart İf mains input voltage is okay automatic
Returning to fault --

827 Status code


Status Inverter alarm
Description SLAVE DC voltage zone 7,My DC voltage zone 1 trying to join system
Restart İf mains input voltage is okay automatic
Returning to fault --

53
54 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

831 Status code


Status Inverter warning
Description SLAVE UPS L1 phase output is not connected to load
Restart --

Possible causes of this status code:

-Check L1 phase UPS output fuse


-Check L1 phase output switch LEG
-Check the SLAVE UPS L1 phase output terminal for bad
connection
- Check the SLAVE UPS L1 phase output cable to load L1 phase
- Call service

832 Status code


Status Inverter warning
Description SLAVE UPS L2 phase output is not connected to load
Restart --

831 Status code causes are valid for L2 phase

833 Status code


Status Inverter warning
Description SLAVE UPS L3 phase output is not connected to load
Restart --

831 Status code causes are valid for L3 phase

841 Status code


Status Inverter warning
Description MASTER UPS L1 phase output is not connected to load
Restart --

Possible causes of this status code:

-Check L1 phase UPS output fuse


-Check L1 phase output switch LEG
-Check the SLAVE UPS L1 phase output terminal for bad
connection
-Check the SLAVE UPS L1 phase output cable to load L1 phase
-Call service

54
55
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

842 Status code


Status Inverter warning
Description MASTER UPS L2 phase output is not connected to load
Restart --

841 Status code causes are valid for L2 phase

843 Status code


Status Inverter warning
Description MASTER UPS L3 phase output is not connected to load
Restart --

841 Status code causes are valid for L3 phase

850 Status code


Status Inverter warning
Description MASTER UPS send by-pass transfer command
Restart --
Returning to fault --

851 Status code


Status Inverter warning
Description MASTER UPS send transfer the load to UPS command
Restart --
Returning to fault --

852 Status code


Status Inverter warning
Description Enter to sleep mode command received from parallel system
Restart --
Returning to fault --

853 Status code


Status Inverter warning
Description Exit from sleep mode command received from parallel system
Restart --
Returning to fault --

854 Status code


Status Inverter warning
Description REPO (remote emergency power off) command received from parallel system
Restart --
Returning to fault --

855 Status code


Status Inverter warning
Description Enter to MASTER mode command received from parallel system
Restart --
Returning to fault --

55
56 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

856 Status code


Status Inverter warning
Description UPS is currently in SLAVE mode ,MASTER function transferred to another UPS
Restart --
Returning to fault --

857 Status code


Status Inverter warning
Description In parallel system there is no MASTER communication packages ,output switch
turned on after 2 seconds MASTER mode started
Restart --
Returning to fault --

858 Status code


Status Inverter warning
Description In parallel system there is no MASTER communication packages ,output switch
turned on after 2 seconds MASTER mode started during on bypass
Restart --
Returning to fault --

859 Status code


Status Inverter alarm
Description In parallel system transfer the load to maintenance bypass command received
Restart --
Returning to fault --

56
57
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

VI. PARALLEL OPERATING INSTRUCTIONS (DS - SHP MODELS)

6.1 INTRODUCTION

After all the electrical connections of UPS have been made and while all the circuit breakers and switchtes
of the device are turned OFF (at “0” position);

4. Check the polarities of battery connections:


K1 : + V (nominal voltage +360V, float charge voltage +405V)
K2-K2 : 0 V (common terminal for ʻʼ+ʼʼ and ʻʼ-ʻʼ battery groups)
K3 : - V (nominal voltage -360V, float charge voltage -405V)
5. Check 3-phase AC input and neutral connections (care should be taken fort he phase order).

ATTENTION!!! TWO CABLES FOR EACH BATTERY GROUP SHOULD BE USED FOR EXTERNAL
BATTERY CONNECTION, AND THE COMMON POINT CONNECTION SHOULD BE MADE ON K2
TERMİNAL BLOCK!
WARNING ! : UPS should never be operated without neutral connection.

6. Check the output load connections of UPS.

6.2 OPERATING INSTRUCTIONS FOR PARALLEL CONNECTED UPSs.

6.2.1 Starting UPSs from a completely shut down position:

8. Turn ON S1 (AC Input) switch (switch to ʻʼ1ʼʼ position)


9. Turn ON S2 (Bypass) switch (switch to ʻʼ1ʼʼ position)

10. Turn on S7 (On/Off) switch (to ʻʼ1ʼʼ position). LCD panel activates, and ʻʼINV RESET” or “PFC RESETʼʼ
message appears on the display meaning that the rectifier starts to operate.
11. Turn ON S4 (AC Output) switch (switch to ʻʼ1ʼʼ position)

12. A few seconds later red bypass light (L2) on front panel turns off and gren inverter light (L6) turns on.
L6 light indicates that the UPS has started normal operation and generating uninterruptable power for
the critical load.

13. Turn on S5 switch (to “1” position) to connect the battery group to UPS.

14. UPS is ready and in normal operation now.

6.2.2 Shutting down the UPS

After closing all the critical loads supplied by the UPSs output:

6. Turn off S4 (AC Output) switch (to ʻʼ0ʼʼ position).


7. Turn off S7 (On/Off) switch (to ʻʼ0ʼʼ position).
8. Turn off S5 (Battery) switch (to ʻʼ0ʼʼ position).
9. Turn off S2 (Bypass) switch (to ʻʼ0ʼʼ position).
10. Turn off S1 (AC Input) switch (to ʻʼ0ʼʼ position).

After performing the above procedure, UPSs is completetely shut-down. In this case PFC rectifier and
inverter is not operating and the batteries are not being charged.

57
58 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

6.2.3 Switching the UPS from a Normal Operation to Maintenance Bypass Condition

4. Enter COMMANDS menu by using UP and DOWN buttons on front panel during normal operation.
Select ENTER<BYPASS> command by using again the UP and DOWN buttons and pres ENTER
button. The critical load is transferred to bypass supply in this case and it is shown at LCD display with
“A09 MANUAL BYPASS” message. Besides L6 (load on UPS) light on front panel will be off and L2
light (bypass) will be on.
5. Turn on S3 (Maintenance Bypass) switch (after unlocking and taking away the padlock on it) to ʻʼ1ʼʼ
position.
6. Turn off S7, S5, S1, S2 and S4 switches (to ʻʼ0ʼʼ position).

In this case, bypass voltage is connected directly to the output of UPSs and the critical load is supplied via
maintenance bypass switch. No AC or DC supply is connected to the inside and the circuits of UPSs.

6.2.4 Switching the UPS from a Maintenance Bypass Condition to Normal Operation

7. Turn on S1 (AC Input) switch (to ʻʼ1ʼʼ position).

8. Turn on S2 (Bypass) switch (to ʻʼ1ʼʼ position).

9. Turn on S7 (On/Off) switch (to ʻʼ1ʼʼ position). LCD panel activates, and main menu will appear at the
display. Also “A08 ON MAINTENANCE” message shown and the inverter will not start yet.

10. Turn on S4 (AC Output) switch (to ʻʼ1ʼʼ position).

11. Turn off S3 (Maintenance Bypass) switch (to ʻʼ0ʼʼ position). Inverter will start automatically following the
turning off of S3 switch.

12. Connect the batteries by turning on S5 (Battery) switch (to ʻʼ1” position).

Now UPSs is ready for uninterruptable operation.

58
59
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

VII. NORMAL OPERATING INSTRUCTIONS (DS - SH MODELS)

7.1 OPERATING UPS IN ONLINE MODE

7.1.1 Starting UPS from a completely shut down position:

1. Turn ON S1 (AC Input) switch (switch to ʻʼ1ʼʼ position)


2. Turn ON S2 (Bypass) switch (switch to ʻʼ1ʼʼ position)
3. Turn ON S4 (AC Output) switch (switch to ʻʼ1ʼʼ position)

ATTENTION!!! BYPASS VOLTAGE WILL BE CONNECTED TO THE OUTPUT TERMINALS OF


UPS WHEN THE ON/OFF SWITCH (S7) IS SWITCHED ON !

4. Turn on S7 (On/Off) switch (to ʻʼ1ʼʼ position). LCD panel activates, and ʻʼINV RESET” or “PFC
RESETʼʼ message appears on the display meaning that the rectifier starts to operate.

5. A few seconds later red bypass light (L2) on front panel turns off and gren inverter light (L6) turns
on. L6 light indicates that the UPS has started normal operation and generating uninterruptable
power for the critical load.

6. Turn on S5 switch (to “1” position) to connect the battery group to UPS.

7. UPS is ready and in normal operation now.

7.1.2 Shutting down the UPS

After closing all the critical loads supplied by the UPS output:

1. Turn off S4 (AC Output) switch (to ʻʼ0ʼʼ position).


2. Turn off S7 (On/Off) switch (to ʻʼ0ʼʼ position).
3. Turn off S5 (Battery) switch (to ʻʼ0ʼʼ position).
4. Turn off S2 (Bypass) switch (to ʻʼ0ʼʼ position).
5. Turn off S1 (AC Input) switch (to ʻʼ0ʼʼ position).

After performing the above procedure, UPS is completetely shut-down. In this case PFC rectifier and
inverter is not operating and the batteries are not being charged.
7.1.3 Switching the UPS from a Normal Operation to Maintenance Bypass Condition

1. Enter COMMANDS menu by using UP and DOWN buttons on front panel during normal operation.
Select ENTER<BYPASS> command by using again the UP and DOWN buttons and pres ENTER
button. The critical load is transferred to bypass supply in this case and it is shown at LCD display
with “A09 MANUAL BYPASS” message. Besides L6 (load on UPS) light on front panel will be off
and L2 light (bypass) will be on.
2. Turn on S3 (Maintenance Bypass) switch (after unlocking and taking away the padlock on it) to ʻʼ1ʼʼ
position.
3. Turn off S7, S5, S1, S2 and S4 switches (to ʻʼ0ʼʼ position).

In this case, bypass voltage is connected directly to the output of UPS and the critical load is supplied via
maintenance bypass switch. No AC or DC supply is connected to the inside and the circuits of UPS.

60 www.tescom-ups.gr
59
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

7.1.4 Switching the UPS from a Maintenance Bypass Condition to Normal Operation

1. Turn on S1 (AC Input) switch (to ʻʼ1ʼʼ position).


2. Turn on S2 (Bypass) switch (to ʻʼ1ʼʼ position).
3. Turn on S4 (AC Output) switch (to ʻʼ1ʼʼ position).
4. Turn on S7 (On/Off) switch (to ʻʼ1ʼʼ position). LCD panel activates, and main menu will appear at the
display. Also “A08 ON MAINTENANCE” message shown and the inverter will not start yet.
5. Turn off S3 (Maintenance Bypass) switch (to ʻʼ0ʼʼ position). Inverter will start automatically following
the turning off of S3 switch.
6. Connect the batteries by turning on S5 (Battery) switch (to ʻʼ1” position).

Now UPS is ready for uninterruptable operation.

7.2 UPS Behavior During Mains Outage

When the mains voltage is not available " R02 LINE FAILURE " message appears on LCD display. Sound
warning on and off is heard at the same time. UPS continues to supply the critical loads by converting the
battery voltage to AC voltage and provides operation without data losses or any other fault. Battery
autonomy time may be prolonged by shutting down the unnecessary loads for that moment.

But do not turn on these loads again during battery operation.

After a short period of time when the line voltage is available again, UPS returns to normal operation
automatically and the alarm message on the display disappears.

Shut down the critical loads in a period of minimum possible autonomy time (depends on the Ah capacity,
charge status, age of the batteries, actual load percentage of UPS and the ambient temperature).
Otherwise critical loads will be out of power at the end of battery autonomy time.

“A26 BATTERY LOW” message appears first on front panel display during battery operation if battery
voltage drops below a defined level.

“A10 BATTERY LOW SHUT” message appears on front panel display when the battery voltage drops to
the end of discharge voltage and UPS shuts itself down. Critical loads will be out of electrical power.

If a reserved generator in the system and if itʼs available, that will start to supply the necessary electrical
power to UPS input and batteries start to be charged immediately. By means of using UPS together with a
immediately available generator system, battery discharge time decreases and so they will be charged
quickly after a mains outage.

60
61
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

VIII. MAINTENANCE

ATTENTION !!! There are no parts inside the UPS or battery group that needs service or maintenance
work that should be done by user. Therefore DO NOT OPEN THE COVER OF UPS. Never
touch on any terminal of battery group. There is risk of electric shock inside the UPS even
when it is completely turned off (because of energy storage components). Therefore
unauthorized openning of the UPS cabinet for repairment, maintenance etc. is not
recommended and forbidden. Otherwise serious injuries may happen.

8.1 Scheduled Maintenance

Some parts and components used inside UPS requires periodic maintenance by service personnel.
Besides, some power equipment inside the UPS need good air circulation for cooling functions. In this
case, the UPS should be cleaned against dust periodically. Cooling fans are mechanical and moving parts
and they should be checked periodically for this reason. Also the batteries should be checked periodically
that if they are in good condition or not.

DS300SHP Series UPS informs the user about these procedures when the maintenance time is up with its
3 independent hour counter as warnings:
FAN MAINTENANCE counter
BATTERY MAINTENANCE counter
GENERAL MAINTENANCE counter

This type of protective maintenance prevents small problems turning up to big failures.

DS300SHP Series UPS has been designed to require very low user maintenance work. User should
only make below maintenance procedure for long years of trouble-free operation.

8.2 Daily Checks

Observe the UPS daily and check the following:

Examine the operator control panel (front panel). Ensure that all LED indicators and parameter
measurements are normal and there is no warning or alarm messages on LCD display.
Examine that there is any sign of overheating the UPS or not.
Check the rotation of cooling fans visually.
Check if there is a remarkable change in the sound of UPS or not.
Check if air inlets of the cabinet cooling system are not congested with dust or any other foreign object.
Clean them with a vacuum cleaner if any present.
Take care not to leave any object on the UPS cabinet.

8.3 Weekly Checks

1. Examine the front panel and record the results.


2. Measure (from Measurements Menu) each of three phase voltages and record the values.
3. Measure (from Measurements Menu) UPS output current values and record the values.
4. Perform a Manual Battery Test (from Commands Menu) and check the status oft he batteries.
5. Cabinet covers may be cleaned with a soft damped (not wet) cloth.

62 www.tescom-ups.gr
61
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

Take notes if possible when you are examining the UPS. Compare the notes with previous ones and try to
determine if there is a change or not. If there is a difference between the previous notes and the new ones,
search for and record any new load added to UPS output between two records and the magnitude, place
and type of the new load, if possible. This information may help to technical authority who will search for
the cause of event in case of a failure.
If there is a remarkable difference between the records without any obvious reason, call technical service
immediately.

8.4 Annual Maintenance


Annual maintenance by authorized service should be done at least two times a year in order to provide
safe and efficient operation your UPS and battery group. UPS generates a warning message when the
maintenance time has expired.

8.5 Storage Conditions and Transportation of UPS

1- Check battery charge status by performing a manual battery test before living the UPS in a storage
place. If charge level is not high enough, leave the UPS for at least 12 hours to charge the batteries.

2- Disconnection oft he cables should be done by an authorized service personnel.

3- Batteries should be recharged once every 6 months during storage.

4- Store the UPS and the batteries in a cool and dry place.
0 0
Ideal storage temperature for UPS: 0 C to 40 C max.
0 0
Ideal storage temperature for batteries:10 C to 35 C max.

5- UPS should be fixed on its pallet for transporting. It should be carried by a forklift with ist pallet.

63
62
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

IX. FAULTS AND TROUBLESHOOTING

9.1 General Procedure For Fault Checking And Troubleshooting

UPS contains complicated electronic control circuits. In order to locate any fault occurring circuits, an
advanced knowledge about the circuitry and its operation principles must be known. The aim of this section
is to give the knowledge required at the first intervention.

There is no practical way to locate any possible fault. Most of the faults do not occur as a performance
decrement. Generally, the UPS operates normally or switches into by-pass mode. But in order to determine
any change in load or the system the parameters must be recorded regularly as mentioned previously.

Generally, the output voltage can deviate %2 from the predefined values. If values differ more than this
percentage then reasons must be investigated.

The following general structure must be systematically followed while trying to indicate the error:

Fault determination: First step is to record the messages, indicator panel LEDs, operating parameter
values and last status of switches. This must be done before

Fixing interventions: After recording all indications, check the meaning of the fault and alarm
messages using “The operator control indicator panel”. If anything related, follow the related procedure.

Reporting the fault: Service personal must clearly report the work done. Hence, if any other error
occurs there will be enough information to fix it.

9.2 Before Calling Service

Please check and note the following:

1- Did you read the user manual carefully and applied the procedures accordingly?
2- Are the switches and circuit breakers of UPS in their normal position?
3- Is there electric power at the UPS line connection distribution panel?
4- Did you turn the battery switch on (to “1“ position) when UPS started to operate in normal mode?
5- Which of the warning lights on front panel is (are) on?
6- Is there any change in the load level at the output of UPS?
7- Did any overload condition happen or not?

64 www.tescom-ups.gr
63
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

X. UPS REMOTE MONITORING AND CONTROL


Following external connections are available for DS300SHP Series UPSs.
• Communication by serial port connection.
• Dry contact (interface board) connections.
• Remote monitoring panel.

Using one of above communication options is satisfactory for remote monitoring and control in most of the
systems. But in some systems may use 2 or 3 of above options at the same time. In this case accessories
group produced by Tescom may help to make appropriate solutions.

10.1 Using Serial Port


One serial communication port is available on DS300SHP Series UPS cabinet (com1 and com2). This port
may be used for user communication. But in service status duty of this com port is changed and set as
service port in Options Menu.
All data of UPS can be accessed by this communication way. All the voltage and current values measured
by UPS, alarms, warning and status messages can be monitored.
Because the communication system is designed in an interactive manner, UPS may get commands from
monitoring and control units. These commands are listed below:

• Switch to BYPASS
• Switch to INVERTER
• SOUND on/off
• Adjust UPS time and date
• Quick BATTERY TEST
• BATTERY TEST until battery low alarm
• CANCEL battery test
• Turn off UPS output voltage immediately (SHUTDOWN)
• Turn off UPS output voltage after delay (WAITING SHUTDOWN)
• Turn off UPS output voltage (SHUTDOWN) and turn on UPS output voltage (WAITING RESTART)
• CANCEL SHUTDOWN
• RENAME UPS

These commands are evaluated only if REMOTE CNTRL: ON option is selected in


OPTİONS/COMMUNICATION OPTIONS menu and if user password is sent from this (com2) port.
Otherwise UPS doesnʼt perform these commands and only information can be obtained from the ports.

Special softwares are required in order to use the serial communication ports. Some of the commands
above have special functions and they can only be activated and used by operating TMON program groups
on a PC that is serially connected to UPS.

TMON program group includes softwares developed by TESCOM.

Additionally, remote monitoring and control is provided in every kind of operating systems, by using
worldwide known and continuously devoloping software programs. These softwares can be supplied from
TESCOM.

10.2 Serial Communication Port Connection Cable


The maximum length for RS232 communication cable should be 25 meters. For remote panel and UPS
connection the same pin configuration is valid. Connection terminals of RS232 cable is shown below for
com1 and com2 ports:

UPS Side Panel Side


9 Tx 2 Rx
7 Gnd 5 Gnd
6 Rx 3 Tx

64 65
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

10.3 Modem Connection

A DS300SHP Series UPS can be controlled through a normal telephone line by means of a remote
operator connected through a PC with modem device, who performs a phone call to the UPS connected
number. So the operator can see all parameters and control the UPS (if permitted from OPTIONS MENU).

10.3.1 Hardware Configuration

All requirements for modem connection are as follows:


• PC with modem
• WINDOWS 98
• Available UPS control software (T-MON)
• NULL modem which is connected to UPS

UPS has its command set to set NULL modem to auto answer mode. In order to do this, press ENTER
button for 3 seconds in ENTER: MODEM INIT item in COMMAND MENU after the hardware is installed.
A short beep sound warning is heard after pressing the buton. RX and TX lights of the connected modem
activates. Modem is set after this to answer external calls by telephone line. To test this, call the telephone
number that the modem is connected with another phone and listen the modem sound.

NOTE : Not all the modems are compatible with the command set on UPS. In such a case modem
should be set by connecting a PC.

10.3.2 Functioning Principle

The remote operator, by means of a PC and a modem device and using the remote connection function of
the control software, calls the UPS through the number to which this is connected.
The NULL modem device, connected to the UPS, will answer the call and convert the data coming from
UPSʼs serial port on to the telephone line. This way all measurements and controls allowed by the RS232
serial port can be carried out.

10.3.3 Modem Programming Procedure

Smart modem (SM) is the one connected to PC, and NULL Modem (NM) is the one connected to the UPS.
Standard Hayes AT programming language is the suitable language for modems. In usual applications a
modem which uses AT command set should be selected.

10.3.3.1 Smart Modem (SM) Programming

The connected modem to PC (smart modem) will be programmed from UPS control software (T-Mon)
automatically.
B0 E1 F1 M1 Q0 V1 X3
BAUD = 2400 PARITY = N WORDLEN = 8
DIAL = TONE (TONE which can be programmed)

&A3 &B1 &C1 &D0 &H1 &I0 &K1 &M4


&N0 &R2 &S0 &T5 &Y1

65
66 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

10.3.4 Modem – UPS Connection Cable

Connection of Smart Modem device to UPS is made with standard modem cable and itʼs supplied as
standard accessory for smart modem. This cable is required if an external modem will be used, and not
necessary for internal modems.

Connection cable between NULL Modem and UPS should be installed as follows:

UPS MODEM
DB9 Female DB25 Male
6 3
7 7
9 2

10.4 Dry Contact (Interface) Connections

Some important events of the UPS can be monitored or controlled by these connections. These functions
are listed below:

Function Description
AUX1 RELAY (OPTIONAL) Function selectable (NO-NC programmable)
AUX2 RELAY (OPTIONAL) Function selectable (NO-NC programmable)
BYPASS RELAY(OPTIONAL) Standard connection to RS232 connector (NO-NC programmable)
DIGITAL INPUT OPTIONAL (Reserved for special applications)
REPO INPUT Standard Remote Emergency Power Off input (NO-NC
programmable)

ATTENTION: Maximum 42Vac or 60Vac voltage may be applied to the dry contacts of the
interface. Dry contact relay outputs are NO (Normally Open) type, ie. the relay is
not activated if alarm is not present and the contacts are open circuit.

10.5 Remote Monitoring Panel Connection of UPS

This panel is used to control and monitor UPS remotely up to 400 m. distance from it. Panel is located in
monitoring and control room. If the distance is not longer than 25 m. RS232, if longer RS485
communication protocol is used. RS485 requires additional adapter.

Remote monitoring panel communicates UPS in a serial way and transfers information to user. Remote
panel requires 220Vac 50Hz supply voltage and it is recommended to get this supply from UPS output.

66 67
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

XI. EFFICIENT USAGE OF UPS IN TERMS OF ENERGY CONSUMPTION

Products should be used according to the conditions and procedures defined in the manual. When this is
made the most efficient usage of the product is guaranteed.

1. Energy efficiency means, decreasing consumed energy amount to the minimum level possible in
every step of living activities, without a decrease in quality or amount of produced work or product, and
keeping this principle permanent.

An efficiency value is said in operation of every energy consuming device. Roughly, efficiency can be
defined as the ratio of work or power -we obtain- at the output of a system, to that of -we give- at the input
of same system.

Keeping below recommendations during the selection and operation of an electric powered product,
provide more useful, economical and long-lasting usage in terms of energy efficiency. Therefore, user
profits economically, as well as supporting to create a cleaner environment and protecting our world
sources.

2. Every electric powered device is designed appropriate to a defined power level. Device capacity
should be selected according to its load requirement for an efficient operation.

3. Ensure to operate your device in convenient electrical conditions defined in technical specifications
table. It will work more efficiently in those conditions.

4. Check that operating environment is compatible to defined conditions.


5. Check if the place of installation is suitable as per the conditions mentioned in the relevant section of
the manual.

6. By means of the periodically maintenance work, faulty or unefficient components of the device may
be detected before the major failures. This results in more efficient operation and prevention of failures.

7. Usage of recyclable materials is one of a remarkable keys to more efficient energy consumption in
total. Users should dispose the expired recyclable materials (batteries, electronic components etc.)
according to local directions and laws.

68 67 www.tescom-ups.gr
USER MANUAL DS 300 SH - SHP Series � 3/3 � 10-20 kVA � DSP CONTROLLED UPS

AGKK12630 04/2017

69
Βόλου 7, 183 46 Μοσχάτο +30 210 9590080 www.tescom-ups.gr
Volou 7, 18 346, Moschato, Greece info@tescom-ups.gr

You might also like