PROFINET

Commissioning & Testing

Peter Thomas – Control Specialists Ltd


Chairman PROFIBUS & PROFINET International Training Centre's
PROFINET - Overview 2

PROFINET is a member of a family providing industrial


communications over Ethernet.
PROFINET is:
completely standard Ethernet (IEEE802.3).
High speed, operating at 100Mbit/s or faster over copper or fibre-optic
cables,
makes use of existing IT standards. But, is “real-time” and deterministic,
PROFINET is very well thought out to incorporate all the requirements of
automation and control systems.
PROFINET is totally compatible with PROFIBUS but is NOT PROFIBUS
over Ethernet.

September 2017 PI UK 2
PROFIBUS v PROFINET 3

Feature PROFIBUS DP PROFINET

Network size 126 devices max. Effectively unlimited

Data Rate Up to 12M bit/s 100 Mbit/s

All devices have same


Update rate and prioritisation Different update rates and priorities
update rate and priority
Controlling Station Class 1 Master IO Controller

IO Equipment Slave IO Device

Diagnostic / Configuration Tool Class 2 Master IO Supervisor

PROFINET RT, ARP, DCP,


Protocols DPV0, DPV1, DPV2 SNMP, LLDP, TCP/IP, HTTP,
MRP
IT services Not possible Integrated in devices

Real-Time Yes Yes

September 2017 PI UK 3
PROFIBUS v PROFINET 4

Feature PROFIBUS DP PROFINET


Typically linear bus but tree and ring
Topology Linear, star, tree and ring
possible
Redundancy Possible but manufacturer specific Simple and standardised
Changes possible but needs Possible without disrupting
Engineering access
network restart operation
Standard Diagnostics Yes Yes

Alarms Only on DPV1 Yes, with priority

Addressing By switch or over bus Over network

Network Devices Repeaters, Hubs, OLM’s Switches

Termination Switch-selectable Built into RJ45 connector

Cable 2 core shielded twisted pair 4 core shielded twisted pair

September 2017 PI UK 4
PROFINET – In operation 5

PROFINET
Real-Time
HTTP SNMP Socket PROFINET
PC RT IRT
IRT Field devices
Internet Explorer
TCP / UDP
IP

Ethernet

PROFINET
RT Field devices
Sensor system

PC
SNMP/OPC server

September 2017 PI UK 5
PROFINET – Topology 6

Star

Line

Tree
Ring

September 2017 PI UK 6
PROFINET – IO Devices 7

IO-Controller PROFINET Supervisor


E.g. PLC running application E.g. PC or laptop running
program. engineering tool application.
(Compare with PROFIBUS Class-1 (Compare with PROFIBUS Class-2
master) master)
Ethernet

 Configuration  Diagnosis
 Control/monitoring  Status/Control
 Alarms IO-Device  Parameters

E.g. Field device with


inputs/outputs
(Compare with PROFIBUS Slave
device)

September 2017 PI UK 7
PROFINET – Commissioning Guideline 8

• This is one of several free-to-download guidelines


documents available to members.
• It provides guidance on how to verify the installation
aspects of the network as well as how to commission
the live system.
• These tests are additional to the application-specific,
System Acceptance Testing that would usually be
performed.

Failure to follow these guidelines puts you at risk of


having your application tests pass without a detailed
knowledge of the underlying performance of your
network !

September 2017 PI UK 8
PROFINET – Installation Acceptance 9

• Visual Checking of the cabling.


• Point-to-Point electrical testing of the cabling using a
simple line tester.
• Point-to-point acceptance testing of the cabling using an
Ethernet Function tester.

Installation Acceptance tests should ideally be performed by


individuals who have Certified PROFINET Installer
accreditation.

September 2017 PI UK 9
PROFINET – Installation Acceptance – Visual Checks 10

The guideline lists 23 individual checks that should be


performed on each cable. Examples are
• Cable laid according to plan?
• Maximum length of 100m observed?
• Cable screen earthed at both ends to a previously
proven earthing system.
• Cable separation rules followed?

September 2017 PI UK 10
PROFINET – Installation Acceptance – Cable Testing 11

The main criteria for the simple electrical


testing of PROFINET cables are:

• There are no short-circuits between any


wires.
• There are no short-circuits between any
wire and the screen
• There are no wire breaks.
• The shield is connected at both ends.
• The wire pairing has been observed
correctly.

September 2017 PI UK 11
PROFINET – Installation Acceptance – Cable Certification 12

• Simple line testers are designed to test the


electrical aspects of the cable.
• The more advanced function and acceptance
testers establish the ability of that cable to
successfully transmit predefined data
packages as well as determine cable length,
attenuation and cross-talk.

September 2017 PI UK 12
PROFINET – Operational Qualification 13

• Checking that the addressing and naming of all IO devices


are in conformance with the design specification.
• Determining other device-related information such as MAC
addresses, Firmware versions etc.
• Establishing that the topology is in conformance with the
design specification.
• Establishing the absence of discarded and error telegrams.
• Establishing operational characteristics and absence of
telegram errors.

September 2017 PI UK 13
PROFINET – IO Device Identification 14

• Every PROFINET device has a world-wide unique MAC


address assigned by the manufacturer.
• The MAC address is unique to that particular device and
will change if the device is replaced with a spare.
• Before a device can take part in communications with an
IO Controller, it must have been configured with a
PROFINET Device Name.
• When the IO Controller initialises communication with the
IO Device, it will allocate an IP address to it.
MAC Address: 00: 0E:CF:04:68:7A • Note - All real-time communications takes place using MAC
Device Name: MySensorName123 addresses.
IP Address: 192.168.1.23
HW Version: 1.0
FW Version: 1.24

September 2017 PI UK 14
PROFINET – Topology – Line Depth 15

• Line depth is the number of forwarding switches between an IO Controller and an IO


Device.
• The line depth will affect the cycle time that the device can be polled at.

September 2017 PI UK 15
Operational Quality Criteria 16

September 2017 PI UK 16
PROFINET – EMC Criteria 17

• EMC (Electromagnetic Compatibility) and


Protective Earth (PE) issues are acknowledged
as being the cause of a significant number of
problems on Fieldbuses and Industrial
networks like PROFIBUS and PROFINET.
• This is because of the ever-increasing
frequencies that such systems operate at.
• Simply ensuring that the cable screen is
connected to earth at both ends serves no
purpose if the earth loop impedance at
“typical” frequencies is too high.

September 2017 PI UK 17
PROFINET – Monitoring Tools 18

Volt-Free Contact to PLC

24v

This permanent monitoring solution


can be used during qualification and
on-going support.
Internet Browser It has no effect on the PROFINET
network which will continue to
operate even if power to the monitor
is removed.
TO PROFINET NETWORK

September 2017 PI UK 18
PROFINET – Acceptance Specification 19

• A document like this acts as a formal record of the


installation and operational qualification tests.
• It should clearly define roles and responsibilities.
• Define the type of tools required to perform the tests and
typical specifications.
• Each test should cross-reference back to the appropriate
section in the relevant design specification.
• Have clear descriptions of the tests and unambiguous
acceptance criteria.
• There should be space available for the tester to
sign/date each test and make notes.

September 2017 PI UK 19
PROFINET – Questions?

Peter Thomas Peter Thomas


(Control Specialists Ltd)
Control Specialists Ltd
Chairman of the
PROFINET & PROFIBUS
International Training Centres
(PITC‘s)

September 2017 PI UK 20
Thankyou

Peter Thomas
Chairman of PI Training Centres