Protect busbars | reduces distances

SRBB – a new heat-shrink tube up to 36kV

D611 | SAP-No. 206984 | 0706


Heat-shrink tube SRBB
for busbar insulation up to 36kV

Application
The insulating tubes SRBB permit clearance reduction between the
busbars and provide flashover protection against accidental bridging
in indoor and outdoor substations up to 36kV.

Properties
• Medium-wall
• Halogen-free
• Anti-tracking according to cold-flow
• UV-resistant
• Non corrosive
• Resistant to fungus and decay

Material
Cross-linked polyolefin

Colour
Red-brown

Ordering details

Inner Ø
Wall thickness
before after Length
Type recovered Art.-No.
shrinkage
mm mm m
SRBB 19-6 19 6 2.3 30 201942
35-11 35 11 2.5 30 201943
50-18 50 18 2.7 30 201944
80-26 80 26 2.8 30 201945
120-40 120 40 3.0 30 201946
Minimum allowance between the busbars
12kV 17.5kV 24kV 36kV
mm mm mm mm
Busbar (round shaped)
• without isolation Ph/Ph and Ph/E 120 160 220 320
• with isolation Ph/Ph 50 65 90 145
• with isolation Ph/E 60 80 120 200
Busbar (rectangular shaped)
• without isolation Ph/Ph and Ph/E 120 160 220 320
• with isolation Ph/Ph 60 80 110 195
• with isolation Ph/E 70 100 145 280

Selection chart
Recommended
application range Width (B) + Height (H)
Ø round rectangular
Type min. max. Art.-No.
min. max.
mm mm
SRBB 19-6 6.5 12 12 18 201942
35-11 13 25 22 36 201943
50-18 18 35 31 60 201944
80-26 28 65 55 95 201945
120-40 45 100 80 150 201946
Technical data Value Test
Physical properties
Densitiy ~ 1.15 g/cm3 IEC 60684-2
Hardness 89 Shore A DIN 53 505
Elongation at tear 500 % IEC 60684-2
Tensile strength 16 MPa IEC 60684-2
Longitudinal shrinkage +5 % / –10 % IEC 60684-2
Shrink ratio 3:1 IEC 60684-2
Concentricity expanded > 50 % IEC 60684-2
Concentricity recovered > 85 % IEC 60684-2
Thermal properties
Operating temperature range –40 °C up to +120 °C IEC 60684-2
Shrinking temperature > 125 °C CP-PM-1004*
Burning behaviour not self-extinguishing IEC 60684-2 Procedure C
Flexibility at low temperatures –40 °C IEC 60684-2
Thermal ageing (168 h at 150 °C) IEC 60684-2
• Elongation at tear > 250 %
• Tensile strength > 12 MPa
Electrical properties
Dielectric strength (23 °C) > 20kV/mm IEC 60684-2
Volume resistivity 1*E 13 IEC 60684-2
Tracking CTI 600 mm IEC 112 RWD Test
Chemical properties
Corrosion non-corrosive DIN IEC 15C/590/CD
Water absorption < 0.15 % DIN 53 495 1L
Resistance to fungus and decay Rate 1 DIN IEC 15C/590/CD

* Internal specification according to DIN ISO 9001


All measured values are minimum values. Alteration right reserved.