Dali XC Control Module With 4 Freely Programmable Inputs: Data Sheet 09/18-CO070-9

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

luxCONTROL lighting control system

DALI control units

DALI XC
Control module with 4 freely programmable inputs

Product description
DALI input controller
• 4 independent inputs for floating contacts
• For connecting standard momentary-action switch or switches
• Adjustable operating mode and range via 2 rotary selector
• Multiple DALI XCs possible on the DALI line
• Power supply via DALI line
• Connection wires according to the terminal colours
with 25 cm length included
• 5-year guarantee

14,6
Technical data
Supply via DALI cable
47,7 28,2
Current draw 6 mA
Input 4 momentary-action switches or relais
Output DALI

28,2
Operating temperature 0 ... +60 °C
Storage temperature -25 ... +80 °C
Turn on time ≤6s
Humidity 20 ... 90 % (non-condensing)
Type of protection IP20
Mounting Mounting box 60 x 61 mm (ø x D) Ordering data
Casing material PC, halogen-free polycarbonate, non-flammable Type Article number Packaging, carton Weight per pc.

Dimension L x W x H 47.7 x 28.2 x 14.6 mm DALI XC 28001716 125 pc(s). 0.035 kg

È
Standards, page 2
Wiring diagrams and installation examples, page 2

Data sheet 09/18-CO070-9


Subject to change without notice. www.tridonic.com 1
luxCONTROL lighting control system
DALI control units

1. Standards DA
16 V
DA

IEC CISPR 15
IEC 61547
DA
IEC 61347-2-11 DA
IEC 61347-1 DALI XC T4
A Mode Config
T3
12 T2
1.1 DALI standard

8 10

14
T1

E F G

A B

0 2
COM

6
C D 4

DALI XC is designed to control control gear with DALI standard IEC 60929
(DALI V0) and IEC 62386 (DALI V1).

1.2 Glow wire test

according to IEC 61347-1 passed. DA


DA
DALI XC T4
2. Installation B Mode Config
T3
12 T2

8 10

14
E F G
• The DALI XC can be inserted into the mounting box for the momentary T1

A B

0 2
6
C D
COM
4
switch.
• The DALI XC must not be connected to the mains. It is supplied directly via
the DALI signal line.
• The momentary switches are connected directly to the DALI XC (potential
free contacts) and must not be connected to the mains.
• DALI signals are not SELV. Therefore the same procedures should be
applied as working with mains voltage. DA
• Only one momentary switch each DALI XC output. DA
• DALI XC modules allow multi master operation. Multiple control modules DALI XC T4
can be used on the same proDIM DALI network. C Mode Config
T3
• Short press < 500 ms < long press 12 T2
8 10

14
E F G

T1
A B

0 2
6

C D
COM
4

2.2 Wiring type and cross section

The wiring can be solid wire or stranded wire with end sleeve with a
cross-section of 0.5 mm² to 1.5 mm².
Maximum cable length between momentary-action switch and DALI XC is
Terminals
50 cm.
Connecting wires are supplied inside the package.

wire preparation:
„Config“ rotary selector switch
��� – ��� mm²
„Mode“ rotary selector switch

��� – ��� mm
2.1 Connection diagrams

L
N

DALI
PCA EXCEL one4all LCAI ECO
PS2

DALI

DALI XC DALI XC DALI XC DALI


GC Mode GC Mode SC Mode
USB

Data sheet 09/18-CO070-9


Subject to change without notice. www.tridonic.com 2
luxCONTROL lighting control system
DALI control units

3. Operating modes • The GC operating mode also allows luminaires to be grouped using the
momentary-action switches.
Changing the operating mode • Connection diagram: A, B or C
• The operating mode can be changed using the “Mode” rotary selector • Different groups can be assigned to inputs T1 and T2 and inputs T3 and T4
switch. using the „Config“ rotary selector switch.

MC operating mode „Mode“ rotary selector switch position A Rotary selector Group
• Programmed functions can be recalled via single momentary-action switch „Config“ Input T1 and T2 Input T3 and T4
switches and/or double momentary-action switches and/or standard 0 All 0
switches. 1 0 1
• The MC operating mode is only configured using the 2 1 2
masterCONFIGURATOR software. 3 2 3
• Connection diagram: A, B or C 4 3 4
5 4 5
SC-A operating mode „Mode“ rotary selector switch position B and SC 6 5 6
operating mode „Mode“ rotary selector switch position C 7 6 7
• Scenes can be recalled via single momentary-action switches. 8 7 8
• The SC operating mode also allows scenes to be saved using the single 9 8 9
momentary-action switches. 10 9 10
• Connection diagram: A or B 11 10 11
• Different scenes can be assigned to inputs T1–T4 using the „Config“ rotary 12 11 12
selector switch. 13 12 13
14 13 14
15 14 15
Rotary selector Scene
switch „Config“ Input T1 Input T2 Input T3 Input T4 Tunable White operating mode „Mode“ rotary selector switch position G
0 0 1 2 3 • The intensity of a group can be set via a double momentary-action switch
1 1 2 3 4 (Inputs T1 and T2).
2 2 3 4 5 Commands send out:
3 3 4 5 6 T1 ... short press = DALI Command 0 = OFF
4 4 5 6 7 long press = DALI Command 2 = DOWN
5 5 6 7 8 T2 ... short press = DALI Command 5 = Recall max. level
6 6 7 8 9 long press = DALI Command 1 = UP
7 7 8 9 10 T3 ... DALI Command 233 = tc step warmer
8 8 9 10 11 T4 ... DALI Command 232 = tc step cooler
9 9 10 11 12 • The colour temperature (Colour temperature Tc) of the Tunable white
10 10 11 12 13 luminaires in a group can be set using the other double momentary-action
11 11 12 13 14 switch (Inputs T3 and T4).
12 12 13 14 15 • Connection diagram: A or B
13 13 14 15 0 • Different groups can be assigned to the DALI XC using the „Config“ rotary
14 14 15 0 1 selector switch.
15 15 0 1 2
Rotary selector
Group
Acoustic signal switch „Config“
Three times 0.2 s on/off ............ supply voltage was connected 0 All
Once after aprrox. 1 s ............... rotary selector switch position was changed 1 0
Different acoustic signals ........... configuration steps were carried out 2 1
3 2
4 3
„Prog“ operating mode rotary selector switch position F 5 4
• Commissioning or a system extension can be started and completed in this 6 5
operating mode. 7 6
• The lighting system is in programming mode while these processes are 8 7
ongoing. 9 8
10 9
11 10
GC-A operating mode „Mode“ rotary selector switch position D and GC 12 11
operating mode „Mode“ rotary selector switch position E 13 12
• Groups can be switched on and off and dimmed and brightened via single 14 13
momentary-action switches and/or double momentary-action switches. 15 14
Commands send out:
T1 ... short press = DALI Command 0 = OFF
long press = DALI Command 2 = DOWN 4. Miscellaneous
T2 ... short press = DALI Comannd 5 = Recall max. level
long press = DALI Command 1 = UP 4.1 Additional information
T3 ... short press = DALI Command 0 = OFF
long press = DALI Command 2 = DOWN Additional technical information at www.tridonic.com → Technical Data
T4 ... short press = DALI Command 5 = Recall max. level
long press = DALI Command 1 = UP Guarantee conditions at www.tridonic.com → Services

Life-time declarations are informative and represent no warranty claim.


No warranty if device was opened.

Data sheet 09/18-CO070-9


Subject to change without notice. www.tridonic.com 3