CONTENTS PAGES
1. Description, use......................................... 1
2. Range ....................................................... 1
3. Overall dimensions .................................... 1
4. Preparation - Connection ........................... 1
5. General characteristics .............................. 3
6. Compliance and approvals ........................ 6
7. Curves ....................................................... 7
8. Auxiliaries and accessories ..................... 10
9. Safety ...................................................... 10
1. DESCRIPTION - USE
USE 3. OVERALL DIMENSIONS
Residual Current Circuit Breaker with Overload (RCBO) with positive
contact indication for control, protection against short-circuits and
overloads, and isolation of electrical circuits, protecting people from
direct and indirect contact and protecting installations from insulation
faults.
Symbol:
Technology:
. Electronic Residual Current Circuit Breaker voltage dependent
. Thermal-magnetic circuit breaker
. Limiting device
. Trip-Free mechanism
2. RANGE
Polarity:
. 2 poles including 1 protected pole and 1 neutral pole
Width:
. 1 module (17.8 mm)
1 / 10
R.C.B.O. Phase + Neutral / 1 module Cat. N°(s): 4111 21 / 22 / 24 / 25 / 26 / 27 / 28 / 29 / 31 / 32 /
33 / 34
Conductors
Conductors type:
. Copper cable
. Cable cross-section
Lift the clamp to Without ferrule With ferrule
the lowermost
position 1 x 0.75 to 16 mm²
Rigid cable -
2 x 0.75 to 6 mm²
1 x 0.75 to 10 mm²
Flexible cable 1 x 0.75 to 10 mm²
2 x 0.75 to 4 mm²
Unscrew . Prong busbar, alone or with a 10 mm² flexible wire (without ferrule)
completely both or a connection terminal in the same terminal.
upper terminals
Recommended tools:
. For the terminals, screwdriver with 5.5 mm blade or Pozidriv no. 2
screwdriver
. For fastening on or removing from a DIN rail, 5.5 mm blade
screwdriver or Pozidriv no. 2 screwdriver
Locking:
. Padlocking possible in open and closed positions with padlock
support (Cat. No. 4 063 03) and Ø5 mm padlock (Cat. No. 4 063 13)
or Ø6 mm padlock (Cat. No. 0 227 97)
Sealing:
. Possible in open or closed positions.
positions
2 / 10
R.C.B.O. Phase + Neutral / 1 module Cat. N°(s): 4111 21 / 22 / 24 / 25 / 26 / 27 / 28 / 29 / 31 / 32 /
33 / 34
Insulation test:
Only to be performed in the bottom terminals and with the device
switched off
Protection degree:
degree:
. Terminals protected
rotected against direct contact. Class of protection
against solid objects and liquids (wired device): IP20 in accordance
with standards IEC 60529
. Front panel protected against direct contact: IP40
. Class II in relation to metallicc conductive parts
. Class of protection against mechanical impacts IK02I in accordance
with standard IEC 62262.
Marking on the upper panel: Higher heating potential:
. By permanent ink pad printing . The heating potential is assessed at: 1.46
1. MJ
Mechanical endurance:
. 20,000 operations as per IEC 61009
1009-1
Electrical endurance:
. 10,000 operations with load (In x Cos ϕ 0.9) as per IEC 61009-1
Insulation voltage:
Product weight:
. Ui = 250V
. 0.125 kg
Rated impulse-
impulse-withstand voltage:
. Uimp = 4 kV
Performance at IΔm:
IΔm:
. 4.5 kA
3 / 10
R.C.B.O. Phase + Neutral / 1 module Cat. N°(s): 4111 21 / 22 / 24 / 25 / 26 / 27 / 28 / 29 / 31 / 32 /
33 / 34
Derating of RCBOs
RCBOs function of the number of devices placed side by side:
When several RCBOss are installed side by side and operate simultaneously, the heat dissipation of each pole is limited. This results in an
increased operating temperature for the circuit breakers which may cause false tripping. Applying the following coefficients to the operating
currents is recommended by the IEC 60439-1.
2-3 0.9
4-5 0.8
6-9 0.7
≥ 10 0.6
In order to avoid having to use these coefficients there must be good ventilation and the devices must be kept apart using the spacing elements
Cat. No. 4 063 07 (0.5 module).
Impact of height:
≤2,000 m 3,000 m 4,000 m 5,000 m
Dielectric
2,000 V 1,750 V 1,500 V 1,250 V
strength
Maximum
operating 240 V 240 V 240 V 240 V
voltage
Power (W)
2.9 1.9
1.9 3.2 4 2.7 3.5
Phase pole
Power (W)
0.4
0.4 0.6
0.6 1.1 1.4
1. 4 1.5
1.5 1.9
1.9
Neutral pole
4 / 10
R.C.B.O. Phase + Neutral / 1 module Cat. N°(s): 4111 21 / 22 / 24 / 25 / 26 / 27 / 28 / 29 / 31 / 32 /
33 / 34
In (A) - 25 °C - 10 °C 0 °C 10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C
20 25 24 23 22 21 20 19 18 17 16
5 / 10
R.C.B.O. Phase + Neutral / 1 module Cat. N°(s): 4111 21 / 22 / 24 / 25 / 26 / 27 / 28 / 29 / 31 / 32 /
33 / 34
Plastic materials:
. Halogen free plastic materials.
. Labelling of parts compliant with ISO 11469 and ISO 1043.
Packaging:
. Design and manufacture of packaging compliant with decree 98-638 of 20/07/98 and Directive 94/62/EC
Approvals obtained:
6 / 10
R.C.B.O. Phase + Neutral / 1 module Cat. N°(s): 4111 21 / 22 / 24 / 25 / 26 / 27 / 28 / 29 / 31 / 32 /
33 / 34
7. CURVES
Thermal-
Thermal-magnetic tripping range typical of C curve RCBOs:
RCBOs:
7 / 10
R.C.B.O. Phase + Neutral / 1 module Cat. N°(s): 4111 21 / 22 / 24 / 25 / 26 / 27 / 28 / 29 / 31 / 32 /
33 / 34
7. CURVES (continued)
Average thermal-
thermal-magnetic tripping curves range typical of C curve RCBOs:
RCBOs:
8 / 10
R.C.B.O. Phase + Neutral / 1 module Cat. N°(s): 4111 21 / 22 / 24 / 25 / 26 / 27 / 28 / 29 / 31 / 32 /
33 / 34
7. CURVES (continued)
9 / 10
R.C.B.O. Phase + Neutral / 1 module Cat. N°(s): 4111 21 / 22 / 24 / 25 / 26 / 27 / 28 / 29 / 31 / 32 /
33 / 34
Wiring accessories:
. Supply busbar:
- Single-pole
pole universal supply busbar (Cat. No. 4 049 26 / 37)
. Connection terminals (Cat. No. 4 049 05)
. Sealable screw cover (Cat. No. 4 063 04)
Signalling auxiliaries:
. Auxiliary contact (0.5 module, Cat. No. 4 062 58)
. Fault signalling contact (0.5 module, Cat. No. 4 062 60)
. Auxiliary contact that can be changed into fault signalling contact (0.5 module, Cat. No. 4 062 62)
. Auxiliary contact + fault signalling contact that can be changed into 2 auxiliary contacts (1 module, Cat. No. 4 062 66)
Control auxiliaries:
. Current shunt
hunt trip (1 module, Cat. No. 4 062 78)
. Undervoltage release (1 module, Cat. No. 4 062 82)
Locking options:
. Via padlock 5 mm in diameter (Cat. No. 4 063 13) or padlock 6 mm in diameter (Cat. No. 0 227 97) and padlock support (Cat. No. 4 063 03)
9. SAFETY:
For your safety your electrical installation is equipped with residual current protection which must be tested periodically.
In the absence of any national regulations on the time period required for this, Legrand recommends that this test be carried out every month:
press the " T " test button, the device should trip. If the device doesn’t trip; please
lease call an electrician immediately ; the safety level of your
installation might have been reduced.
The presence of residual current protection does not remove the need to observe all the precautions associated with using electrical energy.
10 / 10