Nothing Special   »   [go: up one dir, main page]

Grundfosliterature 1258034 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

GRUNDFOS INSTRUCTIONS

CU 211 and CU 212


Installation and operating instructions
Declaration of conformity
Declaration of conformity

Declaration of Conformity
We Grundfos declare under our sole responsibility that the products
CU 211 and CU 212, to which this declaration relates, are in conformity
with these Council directives on the approximation of the laws of the EC
member states:
— Low Voltage Directive (2006/95/EC)
Standard used: EN 60335-1: 2002.
— EMC Directive (2004/108/EC)
Standards used: EN 61000-6-2: 2005 and EN 61000-6-3: 2007.

Bjerringbro, 15th September 2008

Jan Strandgaard
Technical Director

2
English (GB) Installation and operating instructions

English (GB)
CONTENTS 1. Symbols used in this document
Page
Warning
1. Symbols used in this document 3 If these safety instructions are not observed,
2. General description it may result in personal injury!
3
2.1 Control panel 4
2.2 DIP switch 4 If these safety instructions are not observed,
2.3 Dimensions Caution it may result in malfunction or damage to the
5
equipment!
3. Identification 5
3.1 Nameplate 5 Notes or instructions that make the job easier
3.2 Type key 5 Note
and ensure safe operation.
4. Application 5
Warning
5. Functions 6
5.1 Two float switches and parallel operation with three These instructions must be observed for
float switches 6 explosion-proof pumps. It is advisable also to fol-
5.2 Three float switches and parallel operation with four low these instructions for standard pumps.
float switches 8
5.3 Four float switches and parallel operation with 100 % 2. General description
standby operation 10
The control units CU 211 and CU 212 are designed for control of
5.4 Four float switches and parallel operation 12
pumps in wastewater, water supply and draining systems.
5.5 Two electrodes 14
5.6 Three electrodes 16 CU 211 is designed for control of one pump and CU 212 of two
5.7 Three electrodes and one float switch 18 pumps.
5.8 Flow switch 20 CU 211 and CU 212 have an alarm output for common alarm and
6. Installation 22 an alarm output for separate high-level alarm.
6.1 Location 22 Furthermore, the control units incorporate a buzzer.
7. Electrical connection 22
8. Overview of terminals 23 1 2 3 4 5 6
9. Wiring diagrams CU 211 24
9.1 CU 211, single-phase, inputs 24
9.2 CU 211, single-phase, outputs 25
9.3 CU 211, single-phase, inputs from IO 111 26
9.4 CU 211, single-phase, outputs for modem 27
9.5 CU 211, single-phase, outputs for CIU 270 28
CU 212
9.6 CU 211, three-phase, inputs 29 1
1 2
2
9.7 CU 211, three-phase, outputs 30 10
9.8 CU 211, three-phase, inputs from IO 111 31
9.9 CU 211, three-phase, outputs for modem 32
9.10 CU 211, three-phase, outputs for CIU 270 33
10. Wiring diagrams CU 212 34
10.1 CU 212, single-phase, inputs 34
10.2 CU 212, single-phase, outputs 35

TM04 2744 2908


10.3 CU 212, single-phase, inputs from IO 111 36 ON DIP

10.4 CU 212, single-phase, outputs for modem 37 1 2 3 4 5 6 7 8 9 10

10.5 CU 212, single-phase, outputs for CIU 270 38


10.6 CU 212, three-phase, inputs 39 7 8 9
10.7 CU 212, three-phase, outputs 40
10.8 CU 212, three-phase, inputs from IO 111 41 Fig. 1 CU 212
10.9 CU 212, three-phase, outputs for modem 42
10.10 CU 212, three-phase, outputs for CIU 270 43
Pos. Description
11. Maintenance 44
1 Input terminals for AC and DC level switches.
12. Service 44
13. Disposal 44 2 Input terminals for DC level switches.
Input terminals for alarm from pump sensors and motor
3
Warning protector.

Prior to installation, read these installation and 4 Terminals for accumulator.


operating instructions. Installation and operation Output terminals for high-level alarm with NO/NC
5
must comply with local regulations and accepted contact. See section 8. Overview of terminals.
codes of good practice. Output terminals for common alarm with NO/NC contact.
6
See section 8. Overview of terminals.
7 Input terminals for supply voltage.
Output terminals for pump 1 and pump 2.
8
For CU 211 there is only an output for one pump.
9 DIP switch. See section 2.2 DIP switch.
10 Control panel. See section 2.1 Control panel.

3
2.1 Control panel 2.2 DIP switch
English (GB)

CU 211 and CU 212 have a 10-pole DIP switch positioned in the


1 234 5 6 bottom right corner. See fig. 3.

When setting the DIP switch, the control unit


Caution
CU 212 1 must have been switched off for at least 1 minute.
1 2
2 Each individual switch (1 to 10) of the DIP switch can be set to
12
position OFF or ON.
11
10 The DIP switch must not be set to other switch
9 Note combinations than those described in section

TM01 6397 3902


8 5. Functions.

Fig. 2 Control panel CU 212

Key to the symbols in fig. 2:

Pos. Description
Green indicator lights for pumps 1 and 2; flashing for
1 start delay, shining for pump operation.
CU 211 has only one indicator light.
Red indicator lights for pumps 1 and 2;
flashing for thermo fault, shining for fault in motor
2
protector.
CU 211 has only one indicator light.

TM01 6870 23087


Red indicator light; indicating wrong phase sequence
3
(three-phase pumps only).
4 Red indicator light; shining for common alarm.
5 ON-OFF-AUTO selector switch for pump 1.
Fig. 3 DIP switch setting
ON-OFF-AUTO selector switch for pump 2.
6
CU 211 has no selector switch for pump 2.
Reset button. Push-button for manual resetting of
7 external alarm devices and the built-in buzzer.
See section 2.1.1 Resetting of alarm.
Orange indicator light; shining for liquid level 1.
8
See section 4. Application.
Orange indicator light; shining for liquid level 2.
9
See 4. Application.
Orange indicator light; shining for liquid level 3.
10
See section 4. Application.
Orange indicator light; shining for liquid level 4, flashing
11
for high-level alarm. See section 4. Application.
Green indicator light; shining when the power supply has
12
been switched on.

2.1.1 Resetting of alarm

The reset button is a push-button for manual


resetting of external alarm devices and the built-in
buzzer. The button is NOT for resetting of alarm
indications; do this by means of the ON-OFF-
AUTO selector switch.
Even if the fault condition still exists, the external
alarm devices and the built-in buzzer will be reset
when the reset button is pressed.

4
2.3 Dimensions

English (GB)
Min. 30 mm

66.5 mm 90 mm

CU 212
1
1 2
2

116 mm
ON DIP

1 2 3 4 5 6 7 8 9 10

Min. 30 mm

35 mm DIN rail (EN 50 022). Recommended depth: 7.5 mm

TM04 2745 2908


Fig. 4 Dimensional sketch of control unit and DIN rail

3. Identification 3.2 Type key

3.1 Nameplate Example CU 212 .230 .1


The nameplate is fitted on the side of the control unit. Grundfos control unit
Variant designation
1 Type CU212.230.1 P.c. 0751 10 211
212 1)
2 Product No. 96458113 V06 Serial No. 0003 9
Voltage [V]
3 UN 1 x 230 V~ 50/60 Hz VCONTACT MAX 400V 8
Phases:
4 PMAX 3W TMAX AMB: -30 to 50°C ICONTACT MAX 2A 7
1 = single-phase
TM04 2633 2808

IP20 3 = three-phase
Made in Denmark

1) 211 = single-pump control


5 6
212 = two-pump control.
Fig. 5 Nameplate, CU 212
4. Application
Key to the nameplate: CU 211 and 212 can be used for level control in a wide range of
industrial, private and public applications.
Pos. Description
Examples:
1 Type designation • tanks in industry
2 Product number • wastewater collection tanks
3 Rated voltage and frequency • lifting stations (with more than one pump).
4 Max. power
5 Enclosure class CU 211 can be set to operation/control in seven different
applications.
6 Max. ambient temperature
CU 212 can be set to operation/control in four different
7 Contact current applications.
8 Contact voltage See section 5. Functions for additional information.
9 Serial number
10 Production code (year-week code)

5
5. Functions
English (GB)

This section describes a number of systems for which CU 211 and CU 212 are designed and the associated DIP switch settings.

5.1 Two float switches and parallel operation with three float switches
Use CU 211 in systems with one pump and two float switches. Use CU 212 in systems with two pumps in parallel operation and
The pump is controlled by the liquid level in the tank. three float switches. The pumps are controlled by the liquid level
– When the float switch, pos. 1, is lifted up by the liquid, the in the tank.
pump is started. – When the float switch, pos. 1, is lifted up by the liquid, the
– When the float switch, pos. 1, is no longer lifted up by the first pump is started.
liquid, the settable stop delay sets in, and after that the – When the float switch, pos. 2, is lifted up by the liquid, the
pump is stopped. second pump is started.
– When the float switch, pos. 2, is lifted up by the liquid, the – When the float switch, pos. 1, is no longer lifted up by the
high-level alarm is activated. liquid, the settable stop delay sets in, and after that both
pumps are stopped.
– The pumps alternate automatically.
– When the float switch, pos. 3, is lifted up by the liquid, the
high-level alarm is activated.

2
1 3
TM04 2749 2908

TM04 2750 2908


2
1

Fig. 6 Systems with one pump and two float switches Fig. 7 Systems with two pumps in parallel operation and
three float switches

6
5.1.1 DIP switch setting

English (GB)
The DIP switch settings apply to both system types and to both CU 211 and CU 212.
• Switches 1, 2 and 3: System type

This setting encodes the system type.


CU 211: Two float switches.
CU 212: Parallel operation with three float switches.

• Switch 4: Start delay and automatic test run

This setting activates a start delay in the range from 0 to 255 sec. (random) after the power supply has been
switched on.
Automatic test run is carried out every 24 hours.

This setting causes the pump to start immediately after the mains supply has been switched on.
No automatic test run.

• Switches 5, 6 and 7: Stop delay

The stop delay is the time from the stop signal is given until the pump is stopped.
The pump must not run dry.

0 sec. 60 sec.

15 sec. 90 sec.

30 sec. 120 sec.

45 sec. 180 sec.

• Switch 8:

Switch 8 has no function in connection with these system types, but keep the setting in this position.

• Switch 9: Alarm resetting

This setting ensures that alarm signals from external alarm devices and the built-in buzzer are reset
automatically. However, an alarm signal will only be reset if the cause of the fault no longer exists.

At this setting, the alarm signal must be reset manually by means of the reset button.
See section 2.1.1 Resetting of alarm.

• Switch 10: Restarting

This setting enables automatic restarting after the motor PTC resistor/thermal switch has cut out the pump.
However, restarting will not happen until the motor has cooled off again.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.
This setting requires the pumps to be restarted manually after the motor PTC resistor/thermal switch has caused
the pump to be cut out. Reset by means of the ON-OFF-AUTO selector switch.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.

7
5.2 Three float switches and parallel operation with four float switches
English (GB)

Use CU 211 in systems with one pump and three float switches. Use CU 212 in systems with two pumps in parallel operation and
The pump is controlled by the liquid level in the tank. four float switches. The pumps are controlled by the liquid level in
– When the float switch, pos. 2, is lifted up by the liquid, the the tank.
pump is started. – When the float switch, pos. 2, is lifted up by the liquid, the
– When the float switch, pos. 1, is no longer lifted up by the first pump is started.
liquid, the pump is stopped. It is possible to set a stop delay – When the float switch, pos. 3, is lifted up by the liquid, the
which delays the stop of the pump. second pump is started.
– When the float switch, pos. 3, is lifted up by the liquid, the – When the float switch, pos. 1, is no longer lifted up by the
high-level alarm is activated. liquid, the settable stop delay sets in, and after that both
pumps are stopped.
– The pumps alternate automatically.
– When the float switch, pos. 4, is lifted up by the liquid, the
high-level alarm is activated.

3
4
4
2 3
3
TM04 2746 2908

TM04 2748 2908


2
1 2
1
1

Fig. 8 Systems with one pump and three float switches Fig. 9 Systems with two pumps in parallel operation and four
float switches

8
5.2.1 DIP switch setting

English (GB)
The DIP switch settings apply to both system types and to both CU 211 and CU 212.
• Switches 1, 2 and 3: System type

This setting encodes the system type.


CU 211: Three float switches.
CU 212: Parallel operation with four float switches.

• Switch 4: Start delay and automatic test run

This setting activates a start delay in the range from 0 to 255 sec. (random) after the power supply has been
switched on.
Automatic test run is carried out every 24 hours.

This setting causes the pump to start immediately after the mains supply has been switched on.
No automatic test run.

• Switches 5, 6 and 7: Stop delay

The stop delay is the time from the stop signal is given until the pump is stopped.
The pump must not run dry.

0 sec. 60 sec.

15 sec. 90 sec.

30 sec. 120 sec.

45 sec. 180 sec.

• Switch 8:

Switch 8 has no function in connection with these system types, but keep the setting in this position.

• Switch 9: Alarm resetting

This setting ensures that alarm signals from external alarm devices and the built-in buzzer are reset
automatically. However, an alarm signal will only be reset if the cause of the fault no longer exists.

At this setting, the alarm signal must be reset manually by means of the reset button.
See section 2.1.1 Resetting of alarm.

• Switch 10: Restarting

This setting enables automatic restarting after the motor PTC resistor/thermal switch has caused the pump to cut
out. However, restarting will not happen until the motor has cooled off again.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.
This setting requires the pumps to be restarted manually after the motor PTC resistor/thermal switch has caused
the pump to be cut out. Reset by means of the ON-OFF-AUTO selector switch.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.

9
5.3 Four float switches and parallel operation with 100 % standby operation
English (GB)

Use CU 211 in systems with one pump and four float switches. Use CU 212 in systems with two pumps in parallel operation and
The pump is controlled by the liquid level in the tank. four float switches with 100 % standby operation. The pumps are
– When the float switch, pos. 3, is lifted up by the liquid, the controlled by the liquid level in the tank.
pump is started. – When the float switch, pos. 2, is lifted up by the liquid, the
– When the float switch, pos. 2, is no longer lifted up by the first pump is started.
liquid, the pump is stopped. It is possible to set a stop delay – When the float switch, pos. 3, is lifted up by the liquid, the
which delays the stop of the pump. second pump is started.
– When the float switch, pos. 4, is lifted up by the liquid, the – When the float switch, pos. 1, is no longer lifted up by the
high-level alarm is activated. liquid, the settable stop delay sets in, and after that both
– When the float switch, pos. 1, is no longer lifted up by the pumps are stopped.
liquid, the dry running alarm is activated. – The pumps alternate automatically.
– When the float switch, pos. 4, is lifted up by the liquid, the
high-level alarm is activated.

4 4
3 3
TM04 2747 2908

TM04 2746 2908


2 2
1 1

Fig. 10 Systems with one pump and four float switches Fig. 11 Systems with two pumps in parallel operation with
100 % standby operation and four float switches

10
5.3.1 DIP switch setting

English (GB)
The DIP switch settings apply to both system types and to both CU 211 and CU 212.
• Switches 1, 2 and 3: System type

This setting encodes the system type.


CU 211: Four float switches.
CU 212: 100 % standby operation.

• Switch 4: Start delay and automatic test run

This setting activates a start delay in the range from 0 to 255 sec. (random) after the power supply has been
switched on.
Automatic test run is carried out every 24 hours.

This setting causes the pump to start immediately after the mains supply has been switched on.
No automatic test run.

• Switches 5, 6 and 7: Stop delay

The stop delay is the time from the stop signal is given until the pump is stopped.
The pump must not run dry.

0 sec. 60 sec.

15 sec. 90 sec.

30 sec. 120 sec.

45 sec. 180 sec.

• Switch 8:

Switch 8 has no function in connection with these system types, but keep the setting in this position.

• Switch 9: Alarm resetting

This setting ensures that alarm signals from external alarm devices and the built-in buzzer are reset
automatically. However, an alarm signal will only be reset if the cause of the fault no longer exists.

At this setting, the alarm signal must be reset manually by means of the reset button.
See section 2.1.1 Resetting of alarm.

• Switch 10: Restarting

This setting enables automatic restarting after the motor PTC resistor/thermal switch has caused the pump to cut
out. However, restarting will not happen until the motor has cooled off again.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.
This setting requires the pumps to be restarted manually after the motor PTC resistor/thermal switch has caused
the pump to be cut out. Reset by means of the ON-OFF-AUTO selector switch.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.

11
5.4 Four float switches and parallel operation
English (GB)

Use CU 212 in systems with two pumps and four float switches in
socalled "full-control operation". The pumps are controlled by the
liquid level in the tank.
– When the float switch, pos. 3, is lifted up by the liquid, the
first pump is started.
– When the float switch, pos. 4, is lifted up by the liquid, the
second pump is started.
– When the float switch, pos. 2, is no longer lifted up by the
liquid, the second pump is stopped.
– When the float switch, pos. 1, is no longer lifted up by the
liquid, the first pump is stopped.
It is possible to set a stop delay which delays the stop of the
pumps.
– The pumps alternate automatically.

4
3
TM04 2748 2908

2
1

Fig. 12 Systems with two pumps and four float switches in


parallel, full-control operation

12
5.4.1 DIP switch setting

English (GB)
The DIP switch settings apply to CU 212.
• Switches 1, 2 and 3: System type

This setting encodes the system type.


CU 212: Four float switches in parallel, full-control operation.

• Switch 4: Start delay and automatic test run

This setting activates a start delay in the range from 0 to 255 sec. (random) after the power supply has been
switched on.
Automatic test run is carried out every 24 hours.

This setting causes the pump to start immediately after the mains supply has been switched on.
No automatic test run.

• Switches 5, 6 and 7: Stop delay

The stop delay is the time from the stop signal is given until the pump is stopped.
The pump must not run dry.

0 sec. 60 sec.

15 sec. 90 sec.

30 sec. 120 sec.

45 sec. 180 sec.

• Switch 8:

Switch 8 has no function in connection with this system type, but keep the setting in this position.

• Switch 9: Alarm resetting

This setting ensures that alarm signals from external alarm devices and the built-in buzzer are reset
automatically. However, an alarm signal will only be reset if the cause of the fault no longer exists.

At this setting, the alarm signal must be reset manually by means of the reset button.
See section 2.1.1 Resetting of alarm.

• Switch 10: Restarting

This setting enables automatic restarting after the motor PTC resistor/thermal switch has caused the pump to cut
out. However, restarting will not happen until the motor has cooled off again.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.
This setting requires the pumps to be restarted manually after the motor PTC resistor/thermal switch has caused
the pump to be cut out. Reset by means of the ON-OFF-AUTO selector switch.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.

13
5.5 Two electrodes
English (GB)

Use CU 211 for systems with two electrodes. The pump is


controlled by the liquid level in the borehole.
– The electrode, pos. 1, is a reference electrode.
– When the electrode, pos. 2, registers liquid, the settable
start delay sets in, and after that the pump is started.
– When the electrode, pos. 2, no longer registers liquid, the
pump is stopped.
– The pressure switch, pos. 3, will stop the pump if the pump
discharge pressure exceeds the pressure switch cut-out
pressure. The pump will restart automatically when the
pressure falls to the pressure switch cut-in pressure if the
electrode, pos. 2, also registers liquid.

2
TM04 2751 2908

Fig. 13 System with one pump and two electrodes

14
5.5.1 DIP switch setting

English (GB)
The DIP switch settings apply to CU 211.
• Switches 1, 2 and 3: System type

This setting encodes the system type.


CU 211: Two electrodes.

• Switch 4: Start delay and automatic test run

This setting activates a start delay in the range from 0 to 255 sec. (random) after the power supply has been
switched on.
Automatic test run is carried out every 24 hours.

This setting causes the pump to start immediately after the mains supply has been switched on.
No automatic test run.

• Switches 5, 6, 7 and 8: Stop delay

The stop delay is the time from the stop signal is given until the pump is stopped.
The pump must not run dry.

1 min. 30 min.

2 min. 35 min.

3 min. 40 min.

5 min. 45 min.

10 min. 50 min.

15 min. 55 min.

20 min. 60 min.

25 min. 65 min.

• Switch 9: Alarm resetting

This setting ensures that alarm signals from external alarm devices and the built-in buzzer are reset
automatically. However, an alarm signal will only be reset if the cause of the fault no longer exists.

At this setting, the alarm signal must be reset manually by means of the reset button.
See section 2.1.1 Resetting of alarm.

• Switch 10: Restarting

This setting enables automatic restarting after the motor PTC resistor/thermal switch has caused the pump to cut
out. However, restarting will not happen until the motor has cooled off again.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.
This setting requires the pumps to be restarted manually after the motor PTC resistor/thermal switch has caused
the pump to be cut out. Reset by means of the ON-OFF-AUTO selector switch.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.

15
5.6 Three electrodes
English (GB)

Use CU 211 for systems with three electrodes. The pump is


controlled by the liquid level in the borehole.
– The electrode, pos. 1, is a reference electrode.
– When the electrode, pos. 3, registers liquid, the pump is
started.
– When the electrode, pos. 2, no longer registers liquid, the
pump is stopped. It is possible to set a stop delay which
delays the stop of the pump.
– The pressure switch, pos. 4, will stop the pump if the pump
discharge pressure exceeds the pressure switch cut-out
pressure. The pump will restart automatically when the
pressure falls to the pressure switch cut-in pressure if the
electrode, pos. 3, also registers liquid.

2
TM04 2752 2908

Fig. 14 System with one pump and three electrodes

16
5.6.1 DIP switch setting

English (GB)
The DIP switch settings apply to CU 211.
• Switches 1, 2 and 3: System type

This setting encodes the system type.


CU 211: Two electrodes.

• Switch 4: Start delay and automatic test run


This setting activates a start delay in the range from 0 to 255 sec. (random) after the power supply has been
switched on.
Automatic test run is carried out every 24 hours.

This setting causes the pump to start immediately after the mains supply has been switched on.
No automatic test run.

• Switches 5, 6 and 7: Stop delay

The stop delay is the time from the stop signal is given until the pump is stopped.
The pump must not run dry.

0 sec. 60 sec.

15 sec. 90 sec.

30 sec. 120 sec.

45 sec. 180 sec.

• Switch 8:

Switch 8 has no function in connection with this system type, but keep the setting in this position.

• Switch 9: Alarm resetting

This setting ensures that alarm signals from external alarm devices and the built-in buzzer are reset
automatically. However, an alarm signal will only be reset if the cause of the fault no longer exists.

At this setting, the alarm signal must be reset manually by means of the reset button.
See section 2.1.1 Resetting of alarm.

• Switch 10: Restarting

This setting enables automatic restarting after the motor PTC resistor/thermal switch has caused the pump to cut
out. However, restarting will not happen until the motor has cooled off again.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.
This setting requires the pumps to be restarted manually after the motor PTC resistor/thermal switch has caused
the pump to be cut out. Reset by means of the ON-OFF-AUTO selector switch.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.

17
5.7 Three electrodes and one float switch
English (GB)

Use CU 211 in systems with three electrodes and one float switch
in applications such as tank filling. The pump is controlled by the
liquid level in the tank.
– The electrode, pos. 1, is a reference electrode.
– When the electrode, pos. 2, no longer registers liquid, the
pump is started.
– When the electrode, pos. 3, registers liquid, the pump is
stopped. It is possible to set a stop delay which delays the
stop of the pump.
– When the float switch, pos. 4, is lifted up by the liquid, the
high-level alarm is activated.
– The pump can be stopped by means of the manual on/off
switch, pos. 5.

The three electrodes may be replaced by float


Note
switches.

3
2
1
TM04 2753 2908

Fig. 15 One pump, three electrodes and one float switch in a


tank filling system

18
5.7.1 DIP switch setting

English (GB)
The DIP switch settings apply to CU 211.
• Switches 1, 2 and 3: System type

This setting encodes the system type.


CU 211: Three electrodes and one float switch in a tank filling system.

• Switch 4: Start delay and automatic test run

This setting activates a start delay in the range from 0 to 255 sec. (random) after the power supply has been
switched on.
Automatic test run is carried out every 24 hours.

This setting causes the pump to start immediately after the mains supply has been switched on.
No automatic test run.

• Switches 5, 6 and 7: Stop delay

The stop delay is the time from the stop signal is given until the pump is stopped.
The pump must not run dry.

0 sec. 60 sec.

15 sec. 90 sec.

30 sec. 120 sec.

45 sec. 180 sec.

• Switch 8:

Switch 8 has no function in connection with this system type, but keep the setting in this position.

• Switch 9: Alarm resetting

This setting ensures that alarm signals from external alarm devices and the built-in buzzer are reset
automatically. However, an alarm signal will only be reset if the cause of the fault no longer exists.

At this setting, the alarm signal must be reset manually by means of the reset button.
See section 2.1.1 Resetting of alarm.

• Switch 10: Restarting

This setting enables automatic restarting after the motor PTC resistor/thermal switch has caused the pump to cut
out. However, restarting will not happen until the motor has cooled off again.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.
This setting requires the pumps to be restarted manually after the motor PTC resistor/thermal switch has caused
the pump to be cut out. Reset by means of the ON-OFF-AUTO selector switch.
Warning
When the pump(s) connected is (are) used in potentially explosive environments,
switch 10 must not be set to this position.

19
5.8 Flow switch
English (GB)

Use CU 211 in systems controlled by a flow switch in applications


such as draining systems. The pump is controlled by the flow in
the discharge line.
– The pump is stopped when the flow switch, pos. 2, registers
that there is no liquid flow.
– When the pump has stopped, a settable start delay sets in,
and after that the pump will try to restart. The restart attempt
will be interrupted when the settable dry running time has
elapsed if the flow switch still does not register flow.
– The pump can be restarted manually by means of the
switch, pos. 1.

TM04 2754 2908

Fig. 16 Flow switch in a draining system

20
5.8.1 DIP switch setting

English (GB)
The DIP switch settings apply to CU 211.
• Switches 1, 2 and 3: System type

This setting encodes the system type.


CU 211: Flow switch in a draining system.

• Switches 4, 5 and 6: Dry running time

The dry running time is the time the pump is allowed to run after start even if the flow switch registers no flow.
The pump is stopped again if the flow switch still does not register flow.

10 sec. 2 min.

20 sec. 3 min.

40 sec. 4 min.

1 min. 5 min.

• Switches 7, 8, 9 and 10: Start delay

The start delay is the time from the pump stopped until the pump attempts to restart.

No restart * 15 min.

1 min. 17 min.

2 min. 20 min.

3 min. 25 min.

5 min. 30 min.

7 min. 50 min.

10 min. 70 min.

12 min. 90 min.

* If the DIP switch was set to "no restart", the pump kan only be restarted by means of the switch.

21
6. Installation Mounting and removal
English (GB)

Before installation, check these points: CU 211 and CU 212 are designed for mounting on a 35 mm DIN
rail (EN 50 022).
• does the variant correspond to the one ordered?
Mount CU 211 and CU 212 in this way:
• does CU 211/CU 212 match the supply voltage and frequency
of the installation site? 1. Hold the bottom of the control unit up against the DIN rail.
• has CU 211/CU 212 been damaged during the transport? 2. Push the unit upwards.
3. Tip the unit into place. See fig. 17.
Warning
CU 211 and CU 212 must not be used for other
purposes than the ones specified.

Warning
Before installing CU 211 and CU 212, make sure
that the power supply has been switched off and
that it cannot be accidentally switched on.

TM04 3069 3608


The installation must be carried out by
authorized personnel in accordance with local
regulations.
All safety regulations must be observed on the
installation site. Fig. 17 Mounting of CU 211 and CU 212

6.1 Location Remove CU 211 and CU 212 in this way:


Enclosure 1. Push the unit upwards.
CU 211 and CU 212 have enclosure class IP20. In order to 2. Tip the unit free of the DIN rail.
reduce the pollution level to 2, CU 211 and CU 212 must be
installed in a protective enclosure with minimum IPX4 enclosure 7. Electrical connection
class according to IEC 60529. The enclosure must be made of
Supply voltage: Single-phase = 230 V +/–10 % 50/60 Hz
fire retardant material.
Three-phase = 400 V +/–10 % 50/60 Hz.
Ambient temperature Supply current: Maks. 250 mA. See also section 8. Overview
Ambient temperature: –30 °C to +50 °C. of terminals.
CU 211 and CU 212 must not be exposed to direct sunlight.
Installation altitude 1 2 3 4 5 6
CU 211 and CU 212 must be installed max. 2000 m above sea
level.

Warning
Do not install CU 211 and CU 212 in potentially
explosive environments.
If the controlled pumps are in potentially
explosive environments, CU 211 and CU 212 must CU 212
be used in combination with float switches. 1
1 2
2
Float switches located in potentially explosive
environments must be connected via an EEx
barrier, such as Grundfos no. 96440300. The EEx
barrier itself must not be installed in potentially
explosive environments.
Equipment/material located in potentially
explosive environments must be approved for
this in each individual situation.
Likewise the cabling into potentially explosive ON DIP
TM04 3133 3808

environments must be made according to current


1 2 3 4 5 6 7 8 9 10
regulations.

Use EEx approved float switches, such as


Note 7 8
Grundfos no. 96003332 or 96003695.

Fig. 18 CU 212 with overview of terminals

22
8. Overview of terminals

English (GB)
The designations of the terminals refer to the wiring diagrams on the following pages.

Pos. Terminal Description Electrical data Function Diagram


Supply output for 13-18 AC /
1 AC
level 1 and 2 12 VDC
1 1 Terminal for level 1
The level 1 and 2 inputs are designed for either
AC or DC transmitters, such as electrodes or
1 mA float switches.
1 2 Terminal for level 2

Earth (GND) for


2 G 0V
level 3 and 4
2 3 Terminal for level 3
The level 3 and 4 inputs are designed for DC
transmitters, such as float switches. A max.
5 V output cable length of 100 metres is recommended.
2 4 Terminal for level 4 max. 0.5 mA

Frame connection
3 G 0V
for S1-2 and T1-2
Terminal for motor 5 V output
3 S1 S1 is input for alarm from overload relay.
protector max. 0.5 mA
Terminal for thermal 5 V output T1 is input from a thermal switch fitted inside
3 T1
circuit breaker max. 2.2 mA the pump.
Terminal for motor 5 V output S2 only applies to two-pump systems;
3 S2
protector max. 0.5 mA otherwise the same as S1.
Terminal for thermal 5 V uoutput T2 only applies to two-pump systems;
3 T2
circuit breaker max. 2,2 mA otherwise the same as T1.
Teminal for NC-
5 H3 contact for high-level
alarm
Depending on the application and the DIP
Frame connection Max 230 VAC
5 H2 switch setting, one of the level inputs can trip
for high-level alarm 2A
the high-level alarm.
Terminal for NO-
5 H1 contact for high-level
alarm
Terminal for NC-
6 GA1 contact for common
alarm
Frame connection Max. 230 VAC
6 GA2 All alarms trip the alarm relay.
for common alarm 2A
Terminal for NO-
6 GA3 contact for common
alarm
Supply input. Only
7 L1 400 V
three-phase version
Mains supply input.
7 L2/L Supply input 400 V/230 V
In three-phase versions the rated voltage is
400 V on L1, L2 and L3.
In single-phase versions the rated voltage is
7 L3/N Supply input 400 V/230 V 230 V on L and N.

Terminal for start/ P1 is an NO-contact designed for start and


8 CP1
stop of pump stop of pump 1. Depending on the DIP switch
Terminal for start/ Max. 400 V setting, the relay will close according to the
8 P1 signals from the level inputs.
stop of pump 1 2A
Terminal for start/
8 CP2
stop of pump P2 only applies to two-pump systems;
Terminal for start/ Max. 400 V otherwise the same as P1.
8 P2
stop of pump 2 2A

23
English (GB)

24
For FLOAT switches For FLOAT switches
or ELECTRODES or REMOTE input
9. Wiring diagrams CU 211
9.1 CU 211, single-phase, inputs

250 mA AC 1 2 G 3 4
L L
N N

CU211.230.1
Input
G S1 T1

Motor 1
Thermal switch

1 3 5

1K5

2 4 6

1F2

M
1~

Pumpe 1

TM04 2724 2908


9.2 CU 211, single-phase, outputs

L
N

CU211.230.1
output
H1
H2
H3

P1
GA2

CP1
GA1
GA3

1F2

1K5

Thermal Switch
Pump 1

TM04 2740 2908

25
English (GB)
English (GB)

26
For FLOAT switches For FLOAT switches
or ELECTRODES or REMOTE input

+
24 V -

250 mA
AC 1 2 G 3 4
L L
N N

CU 211.230.1
Input
G S1 T1
9.3 CU 211, single-phase, inputs from IO 111

1F2

1 3 5

1K5
-OF F 1K5 -OFF
2 4 6

1F2

Insulation Contactor Auto Supply Alarm


status reset voltage relay

M IO 111 Pumpe 1
1~

P1-P5
Pumpe 1

Pump
Sensor cable

TM04 2726 2908


L
N

CU 211.230.1
output
9.4 CU 211, single-phase, outputs for modem

P1
H2
H3

H1

CP1
GA 1
GA 2
GA 3
1A

1K5

1F2

1K5 ln 1 ln 2 ln 3 ln 4 24 V N L

Com

O1
SMS modul
Batt 1A
O2

Thermal Switch
Pump 1

TM04 2727 2908

27
English (GB)
English (GB)

28
L
N

CU 211.230.1
output
9.5 CU 211, single-phase, outputs for CIU 270

H1
H2
H3

P1
GA 1
GA 2
GA 3

CP1
GRM
1F2
1K5

1K5 N L
GND

GND

DI 3_IN
DI 4_IN

24 VS_2

24 VS_1
AI 2/DI 2_IN

AI 1 /DI 1_IN

CIU 270
NO
COM Relay
Output GENIbus
NC
A Y B

Thermal Switch
Pump 1

A Y B

GENIbus

IO 111 PUMPE 1

TM04 2725 2908


For FLOAT switches For FLOAT switches
or ELECTRODES or REMOTE input

L3 L3 AC 1 2 G 3 4
9.6 CU 211, three-phase, inputs

L2 L2
L1 L1
N 250 mA
CU 211.400.3
Input
G S1 T1

1F2

Motor 1
Thermal switch

1 3 5

1K5

2 4 6

1F2

M
3~

Pumpe 1

TM04 2728 2908

29
English (GB)
English (GB)

30
L3
L2
L1
N
9.7 CU 211, three-phase, outputs

CU 211.400.3
output
H1
H2
H3

P1
CP1
GA 1
GA 2
GA 3

1F2

1K5

Thermal Switch
Pump 1

TM04 2729 2908


For FL OA T switches For FLO AT switche s
or EL ECTRODE S or REMO TE input

+
24 V
-

L3 L3 AC 1 2 G 3 4
L2 L2
L1 L1
N 250 mA
CU 211.400.3
Input
G S1 T1
9.8 CU 211, three-phase, inputs from IO 111

1F2

1 3 5

1K5
-OF F 1K5 -OFF
2 4 6

Insulation Contactor Auto Supply Alarm


status reset voltage relay

M IO 111 Pumpe 1
3~

Pumpe 1 P 1– P 5

Pump
Sensor cable

TM04 2730 2908

31
English (GB)
English (GB)

32
L3
L2
L1
N

CU 211.400.3
output
9.9 CU 211, three-phase, outputs for modem

P1
CP1
H2
H3

H1
GA 1
GA 2
GA 3
1A

1K5

1F2

1K5 ln 1 ln 2 ln 3 ln 4 24 V N L

Com

O1 +
Batt
1A
O2 -

Thermal Switch
Pump 1

TM04 2731 2908


L
N

CU 211.230.1
output
9.10 CU 211, three-phase, outputs for CIU 270

H1
H2
H3

P1
GA 1
GA 2
GA 3

CP1
GRM
1F2
1K5

1K5 N L
GND

GND

DI 3_IN
DI 4_IN

24 VS_2

24 VS_1
AI 2/DI 2_IN

AI 1 /DI 1_IN

CIU 270
NO
COM Relay
Output GENIbus
NC
A Y B

Thermal Switch
Pump 1

A Y B

GENIbus

IO 111 PUMPE 1

TM04 2741 2908

33
English (GB)
English (GB)

34
For FLOAT switches For FLOAT switches
or ELECTRODES or REMOTE input
10. Wiring diagrams CU 212
10.1 CU 212, single-phase, inputs

250 mA AC 1 2 G 3 4
L L
N N

CU 212.230.1
Input
G S1 T1 S2 T2

1F2 1F3

Motor 1 Motor 2
Thermal switch Thermal switch

1 3 5 1 3 5

1K5 1K6

2 4 6 2 4 6

1F2 1F3

M M
1~ 1~

Pumpe 1 Pumpe 2

TM04 2732 2908


L
N

CU 212.230.1
10.2 CU 212, single-phase, outputs

output
H1
H2
H3

P1
P2
CP2

CP1
GA 1
GA 2
GA 3

1F2 1F3

1K5 1K6

Thermal Switch Thermal Switch


Pump 1 Pump 2

TM04 2733 2908

35
English (GB)
English (GB)

36
For FLOAT switches For FLOAT switches
or ELECTRODES or REMOTE input

+
24 V -

250 mA
AC 1 2 G 3 4
L L
N N
CU 212.230.1
Input
G S1 T1 S2 T2
10.3 CU 212, single-phase, inputs from IO 111

1F2 1F3

1 3 5 1 3 5

1K5 1K6
-OFF 1K5 -OFF -OF F 1K6 -OFF
2 4 6 2 4 6

1F2 1F3

Insulation Contactor Auto Supply Alarm Insulation Contactor Auto Supply Alarm
status reset voltage relay status reset voltage relay

M M
IO 111 Pumpe 1 IO 111 Pumpe 2
1~ 1~

P1– P5 P1 – P5
Pumpe 1 Pumpe 2

Pump
Sensor cable

Pump
Sensor cable

TM04 2734 2908


L
N

CU 212.230.1
output
10.4 CU 212, single-phase, outputs for modem

H1
H2
H3

P1
P2

CP2

CP1
GA 1
GA 2
GA 3
1A

1K5 1K6

1F2 1F3

1K5 1K6 ln 1 ln 2 ln 3 ln 4 24 V N L

Com
SMS modul +
O1
Batt 1A
O2 -

Thermal Switch Thermal Switch


Pump 1 Pump 2

TM04 2735 2908

37
English (GB)
English (GB)

38
L
N

CU 212.230.1
output

H1
H2
H3

P1
GA 1
GA 2
GA 3

P2

CP1
CP2
10.5 CU 212, single-phase, outputs for CIU 270

GRM
1F2 1F3
1K5 1K6

1K5 1K6 N L
GND

GND

DI 3_IN
DI 4_IN

24 VS_2

24 VS_1

AI 1/DI1_IN
AI 2/DI 2_IN

CIU 270
NO
Relay
Com
Output GENIbus
NC
A Y B
Thermal Switch Thermal Switch
Pump 1 Pump 2

A Y B A Y B

GENIbus GEN Ibus

IO111 PUMPE 1 IO111 PUMPE 2

TM04 2742 2908


For FLOAT switches For FLOAT switches
or ELECTRODES or REMOTE input

L3 L3 AC 1 2 G 3 4
L2 L2
10.6 CU 212, three-phase, inputs

L1 L1
N
250 mA
CU 212.400.3
Input
G S1 T1 S2 T2

1F2 1F3

Motor 1 Motor 2
Thermal switch Thermal switch

1 3 5 1 3 5

1K5 1K6

2 4 6 2 4 6

1F2 1F3

M M
3~ 3~

Pumpe 1 Pumpe 2

TM04 2736 2908

39
English (GB)
English (GB)

40
L3
L2
L1
N

CU 212.400.3
10.7 CU 212, three-phase, outputs

output
H1
H2
H3

P1
P2

CP1
CP2
GA 1
GA 2
GA 3

1F2 1F3

1K5 1K6

Thermal Switch Thermal Switch


Pump 1 Pump 2

TM04 2737 2908


For FLOAT switches For FLOAT switches
or ELETRODES or ELETRODES

+
24 V
-

L3 L3 AC 1 2 G 3 4
L2 L2
L1 L1
N
250 mA CU 212.400.3
Input
G S1 T1 S2 T2
10.8 CU 212, three-phase, inputs from IO 111

1F2 1F3

1 3 5 1 3 5

1K5 1K6
-OFF 1K5 -OFF -OF F 1K6 -OFF
2 4 6 2 4 6

1F3 1F3

Insulation Contactor Auto Supply Alarm Insulation Contactor Auto Supply Alarm
status reset voltage relay status reset voltage relay

M M
IO 111 Pumpe 1 IO 111 Pumpe 2
3~ 3~

P1 – P5 P1– P5
Pumpe 1 Pumpe 2

Pump
Sensor cable

Pump
Sensor cable

TM04 2738 2908

41
English (GB)
English (GB)

42
L3
L2
L1
N

CU 212.400.3
output
10.9 CU 212, three-phase, outputs for modem

P2

P1
H1
H2
H3

CP2

CP1
GA 1
GA 2
GA 3
1A

1K5 1K6

1F2 1F3

1K5 1K6 In1 In 2 In3 In 4 24V N L

Com

O1
SMS modul +
Batt 1A
O2 - +

-
Thermal Switch Thermal Switch
Pump 1 Pump 2

TM04 2739 2908


L3
L2
L1
N

CU 212.400.3
output
10.10 CU 212, three-phase, outputs for CIU 270

H1
H1
H1

P2

P1
CP2
GA 3

CP1
GA 1
GA 2

GRM
1F2 1F3
1K5 1K6

1K5 1K6 N L
GND

GND
DI 4_IN

DI 3_IN

24VS_1
24VS_2

AI 1/DI 1_IN
AI 2/DI 2_IN

CIU 270
NO
Relay
Com Output
NC
GENIbus
A Y B

Thermal Switch Thermal Switch


Pump 1 Pump 2

A Y B A Y B

GENIbus GENIbus
IO 111 PUMPE 1 IO 111 PUMPE 2

TM04 2743 2908

43
English (GB)
11. Maintenance
English (GB)

CU 211 and CU 212 require no maintenance. CU 211 and CU 212


may only be cleaned with a dustless cloth.

12. Service
CU 211 and CU 212 cannot be serviced. In case of faults in the
control unit, replace it.

13. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.

Subject to alterations.

44
45
46
Argentina Estonia Latvia Slovenia

Grundfos companies
Bombas GRUNDFOS de Argentina S.A. GRUNDFOS Pumps Eesti OÜ SIA GRUNDFOS Pumps Latvia GRUNDFOS d.o.o.
Ruta Panamericana km. 37.500 Lote 34A Peterburi tee 92G Deglava biznesa centrs Šlandrova 8b, SI-1231 Ljubljana-Črnuče
1619 - Garin 11415 Tallinn Augusta Deglava ielā 60, LV-1035, Rīga, Phone: +386 1 568 0610
Pcia. de Buenos Aires Tel: + 372 606 1690 Tālr.: + 371 714 9640, 7 149 641 Telefax: +386 1 568 0619
Phone: +54-3327 414 444 Fax: + 372 606 1691 Fakss: + 371 914 9646 E-mail: slovenia@grundfos.si
Telefax: +54-3327 411 111
Finland Lithuania South Africa
Australia OY GRUNDFOS Pumput AB GRUNDFOS Pumps UAB Corner Mountjoy and George Allen Roads
GRUNDFOS Pumps Pty. Ltd. Mestarintie 11 Smolensko g. 6 Wilbart Ext. 2
P.O. Box 2040 FIN-01730 Vantaa LT-03201 Vilnius Bedfordview 2008
Regency Park Phone: +358-3066 5650 Tel: + 370 52 395 430 Phone: (+27) 11 579 4800
South Australia 5942 Telefax: +358-3066 56550 Fax: + 370 52 395 431 Fax: (+27) 11 455 6066
Phone: +61-8-8461-4611 E-mail: lsmart@grundfos.com
Telefax: +61-8-8340 0155 France Malaysia
Pompes GRUNDFOS Distribution S.A. GRUNDFOS Pumps Sdn. Bhd. Spain
Austria Parc d’Activités de Chesnes 7 Jalan Peguam U1/25 Bombas GRUNDFOS España S.A.
GRUNDFOS Pumpen Vertrieb 57, rue de Malacombe Glenmarie Industrial Park Camino de la Fuentecilla, s/n
Ges.m.b.H. F-38290 St. Quentin Fallavier (Lyon) 40150 Shah Alam E-28110 Algete (Madrid)
Grundfosstraße 2 Tél.: +33-4 74 82 15 15 Selangor Tel.: +34-91-848 8800
A-5082 Grödig/Salzburg Télécopie: +33-4 74 94 10 51 Phone: +60-3-5569 2922 Telefax: +34-91-628 0465
Tel.: +43-6246-883-0 Telefax: +60-3-5569 2866
Telefax: +43-6246-883-30 Germany Sweden
GRUNDFOS GMBH México GRUNDFOS AB
Belgium Schlüterstr. 33 Bombas GRUNDFOS de México S.A. de Box 333 (Lunnagårdsgatan 6)
N.V. GRUNDFOS Bellux S.A. 40699 Erkrath C.V. 431 24 Mölndal
Boomsesteenweg 81-83 Tel.: +49-(0) 211 929 69-0 Boulevard TLC No. 15 Tel.: +46(0)771-32 23 00
B-2630 Aartselaar Telefax: +49-(0) 211 929 69-3799 Parque Industrial Stiva Aeropuerto Telefax: +46(0)31-331 94 60
Tél.: +32-3-870 7300 e-mail: infoservice@grundfos.de Apodaca, N.L. 66600
Télécopie: +32-3-870 7301 Service in Deutschland: Phone: +52-81-8144 4000 Switzerland
e-mail: kundendienst@grundfos.de Telefax: +52-81-8144 4010 GRUNDFOS Pumpen AG
Belorussia Bruggacherstrasse 10
Представительство ГРУНДФОС в Greece Netherlands CH-8117 Fällanden/ZH
Минске GRUNDFOS Hellas A.E.B.E. GRUNDFOS Netherlands Tel.: +41-1-806 8111
220123, Минск, 20th km. Athinon-Markopoulou Av. Veluwezoom 35 Telefax: +41-1-806 8115
ул. В. Хоружей, 22, оф. 1105 P.O. Box 71 1326 AE Almere
Тел.: +(37517) 233 97 65, GR-19002 Peania Postbus 22015 Taiwan
Факс: +(37517) 233 97 69 Phone: +0030-210-66 83 400 1302 CA ALMERE GRUNDFOS Pumps (Taiwan) Ltd.
E-mail: grundfos_minsk@mail.ru Telefax: +0030-210-66 46 273 Tel.: +31-88-478 6336 7 Floor, 219 Min-Chuan Road
Telefax: +31-88-478 6332 Taichung, Taiwan, R.O.C.
Bosnia/Herzegovina Hong Kong E-mail: info_gnl@grundfos.com Phone: +886-4-2305 0868
GRUNDFOS Sarajevo GRUNDFOS Pumps (Hong Kong) Ltd. Telefax: +886-4-2305 0878
Trg Heroja 16, Unit 1, Ground floor New Zealand
BiH-71000 Sarajevo Siu Wai Industrial Centre GRUNDFOS Pumps NZ Ltd. Thailand
Phone: +387 33 713 290 29-33 Wing Hong Street & 17 Beatrice Tinsley Crescent GRUNDFOS (Thailand) Ltd.
Telefax: +387 33 659 079 68 King Lam Street, Cheung Sha Wan North Harbour Industrial Estate 92 Chaloem Phrakiat Rama 9 Road,
e-mail: grundfos@bih.net.ba Kowloon Albany, Auckland Dokmai, Pravej, Bangkok 10250
Phone: +852-27861706 / 27861741 Phone: +64-9-415 3240 Phone: +66-2-725 8999
Brazil Telefax: +852-27858664 Telefax: +64-9-415 3250 Telefax: +66-2-725 8998
BOMBAS GRUNDFOS DO BRASIL
Av. Humberto de Alencar Castelo Branco, Hungary Norway Turkey
630 GRUNDFOS Hungária Kft. GRUNDFOS Pumper A/S GRUNDFOS POMPA San. ve Tic. Ltd. Sti.
CEP 09850 - 300 Park u. 8 Strømsveien 344 Gebze Organize Sanayi Bölgesi
São Bernardo do Campo - SP H-2045 Törökbálint, Postboks 235, Leirdal Ihsan dede Caddesi,
Phone: +55-11 4393 5533 Phone: +36-23 511 110 N-1011 Oslo 2. yol 200. Sokak No. 204
Telefax: +55-11 4343 5015 Telefax: +36-23 511 111 Tlf.: +47-22 90 47 00 41490 Gebze/ Kocaeli
Telefax: +47-22 32 21 50 Phone: +90 - 262-679 7979
Bulgaria India Telefax: +90 - 262-679 7905
Grundfos Bulgaria EOOD GRUNDFOS Pumps India Private Limited Poland E-mail: satis@grundfos.com
Slatina District 118 Old Mahabalipuram Road GRUNDFOS Pompy Sp. z o.o.
Iztochna Tangenta street no. 100 Thoraipakkam ul. Klonowa 23 Ukraine
BG - 1592 Sofia Chennai 600 096 Baranowo k. Poznania ТОВ ГРУНДФОС УКРАЇНА
Tel. +359 2 49 22 200 Phone: +91-44 2496 6800 PL-62-081 Przeźmierowo 01010 Київ, Вул. Московська 8б,
Fax. +359 2 49 22 201 Tel: (+48-61) 650 13 00 Тел.:(+38 044) 390 40 50
email: bulgaria@grundfos.bg Indonesia Fax: (+48-61) 650 13 50 Фах.: (+38 044) 390 40 59
PT GRUNDFOS Pompa E-mail: ukraine@grundfos.com
Canada Jl. Rawa Sumur III, Blok III / CC-1 Portugal
GRUNDFOS Canada Inc. Kawasan Industri, Pulogadung Bombas GRUNDFOS Portugal, S.A. United Arab Emirates
2941 Brighton Road Jakarta 13930 Rua Calvet de Magalhães, 241 GRUNDFOS Gulf Distribution
Oakville, Ontario Phone: +62-21-460 6909 Apartado 1079 P.O. Box 16768
L6H 6C9 Telefax: +62-21-460 6910 / 460 6901 P-2770-153 Paço de Arcos Jebel Ali Free Zone
Phone: +1-905 829 9533 Tel.: +351-21-440 76 00 Dubai
Telefax: +1-905 829 9512 Ireland Telefax: +351-21-440 76 90 Phone: +971-4- 8815 166
GRUNDFOS (Ireland) Ltd. Telefax: +971-4-8815 136
China Unit A, Merrywell Business Park România
GRUNDFOS Pumps (Shanghai) Co. Ltd. Ballymount Road Lower GRUNDFOS Pompe România SRL United Kingdom
50/F Maxdo Center No. 8 XingYi Rd. Dublin 12 Bd. Biruintei, nr 103 GRUNDFOS Pumps Ltd.
Hongqiao development Zone Phone: +353-1-4089 800 Pantelimon county Ilfov Grovebury Road
Shanghai 200336 Telefax: +353-1-4089 830 Phone: +40 21 200 4100 Leighton Buzzard/Beds. LU7 8TL
PRC Telefax: +40 21 200 4101 Phone: +44-1525-850000
Phone: +86-021-612 252 22 Italy E-mail: romania@grundfos.ro Telefax: +44-1525-850011
Telefax: +86-021-612 253 33 GRUNDFOS Pompe Italia S.r.l.
Via Gran Sasso 4 Russia U.S.A.
Croatia I-20060 Truccazzano (Milano) ООО Грундфос GRUNDFOS Pumps Corporation
GRUNDFOS CROATIA d.o.o. Tel.: +39-02-95838112 Россия, 109544 Москва, ул. Школьная 17100 West 118th Terrace
Cebini 37, Buzin Telefax: +39-02-95309290 / 95838461 39 Olathe, Kansas 66061
HR-10010 Zagreb Тел. (+7) 495 737 30 00, 564 88 00 Phone: +1-913-227-3400
Phone: +385 1 6595 400 Japan Факс (+7) 495 737 75 36, 564 88 11 Telefax: +1-913-227-3500
Telefax: +385 1 6595 499 GRUNDFOS Pumps K.K. E-mail grundfos.moscow@grundfos.com
Gotanda Metalion Bldg., 5F, Usbekistan
www.grundfos.hr Представительство ГРУНДФОС в
5-21-15, Higashi-gotanda Serbia
Czech Republic Shiagawa-ku, Tokyo GRUNDFOS Predstavništvo Beograd Ташкенте
GRUNDFOS s.r.o. 141-0022 Japan Dr. Milutina Ivkovića 2a/29 700000 Ташкент ул.Усмана Носира 1-й
Čajkovského 21 Phone: +81 35 448 1391 YU-11000 Beograd тупик 5
779 00 Olomouc Telefax: +81 35 448 9619 Phone: +381 11 26 47 877 / 11 26 47 496 Телефон: (3712) 55-68-15
Phone: +420-585-716 111 Telefax: +381 11 26 48 340 Факс: (3712) 53-36-35
Telefax: +420-585-716 299 Korea
GRUNDFOS Pumps Korea Ltd. Singapore
Denmark 6th Floor, Aju Building 679-5 GRUNDFOS (Singapore) Pte. Ltd.
GRUNDFOS DK A/S Yeoksam-dong, Kangnam-ku, 135-916 24 Tuas West Road
Martin Bachs Vej 3 Seoul, Korea Jurong Town
DK-8850 Bjerringbro Phone: +82-2-5317 600 Singapore 638381
Tlf.: +45-87 50 50 50 Telefax: +82-2-5633 725 Phone: +65-6865 1222
Telefax: +45-87 50 51 51 Telefax: +65-6861 8402
E-mail: info_GDK@grundfos.com
www.grundfos.com/DK

Addresses revised 29.09.2010


Being responsible is our foundation
Thinking ahead makes it possible
Innovation is the essence

96891528 0211
Repl. 96891528 1110
GB
The name Grundfos, the Grundfos logo, and the payoff Be–Think–Innovate are registrated trademarks
ECM: 1071415 owned by Grundfos Management A/S or Grundfos A/S, Denmark. All rights reserved worldwide.

www.grundfos.com

You might also like