Nothing Special   »   [go: up one dir, main page]

Typ. SLD With String Inverter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

PROJECT SUMMARY

PLANT CAPACITY 100 MWp


Modules per string - 30 Modules per string - 30 Modules per string - 30 Modules per string - 30 Modules per string - 30 Modules per string - 30 Modules per string - 30 Modules per string - 30 Modules per string - 30 Modules per string - 30 Modules per string - 30 Modules per string - 30 Modules per string - 30
PV MODULE CAPACITY 340 Wp
No. of strings- 27 No. of strings- 27 No. of strings- 27 No. of strings- 27 No. of strings- 27 No. of strings- 27 No. of strings- 27 No. of strings- 27 No. of strings- 27 No. of strings- 27 No. of strings- 27 No. of strings- 27 No. of strings- 27 NO. OF PV MODULES 294120
No. of modules - 810 No. of modules - 810 No. of modules - 810 No. of modules - 810 No. of modules - 810 No. of modules - 810 No. of modules - 810 No. of modules - 810 No. of modules - 810 No. of modules - 810 No. of modules - 810 No. of modules - 810 No. of modules - 810 PITCH 6.5 Mtr
TILT 18°
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 NO. OF PV MODULE/TABLE 30 NOS.
INVERTER CAPACITY 200kVA
1 TO 27 1 TO 27 1 TO 27 1 TO 27 1 TO 27 1 TO 27 1 TO 27 1 TO 27 1 TO 27 1 TO 27 1 TO 27 1 TO 27 1 TO 27 NO. OF INVERTERS 350 NOS.
METERING CLASS 0.2
FAULT LEVEL 50kA for 1 Sec on LV Side

30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30

NOTES:-

1Cx06 Sq.mm Cu (1) CABLE SIZES INDICATED IN THIS ARE


DC Solar Cable
TENTATIVE.
(2) FINAL CT RATIO SHALL BE DECIDED AT
INV-01 INV-02 INV-03 INV-04 INV-05 INV-06 INV-07 INV-08 INV-09 INV-10 INV-11 INV-12 INV-13
Pmax =200kVA

Imax =180.5A
Pmax =200kVA

Imax =180.5A
Pmax =200kVA

Imax =180.5A
Pmax =200kVA

Imax =180.5A
Pmax =200kVA

Imax =180.5A
Pmax =200kVA

Imax =180.5A
Pmax =200kVA

Imax =180.5A
Pmax =200kVA

Imax =180.5A
Pmax =200kVA

Imax =180.5A
Pmax =200kVA
Imax =180.5A
Pmax =200kVA
Imax =180.5A
Pmax =200kVA
Imax =180.5A
Pmax =200kVA
Imax =180.5A
DETAIL ENGINEERING.
Vmax =800V Vmax =800V Vmax =800V Vmax =800V Vmax =800V Vmax =800V Vmax =800V Vmax =800V Vmax =800V Vmax =800V Vmax =800V Vmax =800V Vmax =800V (3) CONTROL SUPPLY VOLTAGE SHALL BE
800/110VAC.

3Cx300 Sq.mm XLPE Ar. Al AC Cable

6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB 6A SP MCB

ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF

3P, 250A,800V
TP,TMA TYPE MCCB
50kA WITH OL &
SC PROTECTION

800V, 3P, 50Hz 50KA for 1 Sec. 2500A AL Bus Bar


6A SP MCB
SPD TYPE-2

ON OFF TRIP
6A SP MCB

R Y B
CT 2500/1A
MFM
0.2 CLASS

2500 A EDO TYPE ACB 50 kA With Adj.


00 03.01.2020 FOR APPROVAL
OL, SC & EF PROTECTION, LSIG
ACDB REV. DATE REVISION HISTORY
9R, 3Cx400 Sq.mm XLPE PROJECT TITLE :
Ar. Al. AC Cable
70 MW SOLAR PLANT IN UTTAR PRADESH
TRANSFORMER

CLIENT :
LALGANJ POWER PVT. LTD.
C/O FOURTH PARTNER ENERGY PVT. LTD.

EPC CONTRACTOR:
RAYS POWER INFRA PVT. LTD., 3RD FLOOR,
LANDMARK HOUSE, PLOT – 65, SECTOR – 44,
GURUGRAM - 122003
DRAWING TITLE :
DC SLD

DRAWING NO. : RPIPL-UP-FP-EE-DWG-DCSLD-001

SITE CO-ORDINATE. :

SHEET NO. 1 OF 1 SCALE NTS


DRAWN RK PAPER SIZE A0
CHECKED AG REV NO. R0
APPROVED NSG DATE 03.01.2020