Electrical BOQ
Electrical BOQ
Electrical BOQ
INCOMING
a) 63 Amp TPN MCB - 1 No
b) 63 Amp DP RCBO (30mA) - 3 Nos
BUSBARS
a) 100 Amp TPN copper Busbars - 1 Set
OUTGOING
a) 6/16/20 Amp SP MCB - 36 Nos
(Twelve per phase)
b) Neutral links - 3 Nos
(Separate for each phase)
INCOMING
32 Amp DP RCBO (100mA) - 1 No
BUSBARS
100 ADP copper Busbars - 1 Set
OUTGOING
6/16A SP MCB - 8 Nos
2.0 WIRING
2.1 Wiring for switch controlled Primary Light Point, Fan point / Exhaust fan point
with 2X2.5+1X1.5 Sq. mm PVC insulated HF-FRLS/multistrand copper
conductor 1100 Volt grade wires in PVC surface/concealed conduit with
accessories including cost of providing saddles etc for surface conduiting and/or
cost of cutting & filling chases for consiled wiring complete as required. There are Points 10
two cluse for Primary Point:
i) Circuit to First Point (via S/B or direct from DB).
ii)S/B to S/B loop and First Point (Only One Point).
2.2 Wiring for Secondry Light points with 3x1.5sq. mm PVC insulated FRLS
multistrand copper conductor 1100 Volt grade wire in PVC surface/concealed
conduit with accessories including cost of providing saddles etc for surface
conduiting and/or cost of cutting & filling chases for consiled wiring complete as Points 30
required. Secondary point is from Primary to next all point(s) even from S/B
(except one Point).
2.3 Wiring for following 1No. 6/16 A Power plug point controlled by 1No 16A switch
with 3X2.5 Sq.mm PVC insulated FRLS multistrand copper conductor 1100 Volt
grade wires in recessed/surface PVC conduit including cost of providing saddles
Points 26
etc for surface conduiting and/or cost of cutting & filling chases for consiled wiring
complete as required.(From DB to Point)
2.4 Wiring for following 2 Nos. 6 pin 6/16 A Power plug point controlled by 2 No.
16A switch with 3 X 2.5 Sq. mm. PVC insulated HF-FRLS multi strand copper
conductor 1100 Volt grade wires in recessed/surface PVC conduit including cost
of providing saddles etc for surface conduiting and/or cost of cutting & filling
chases for consiled wiring complete as required.(From DB to Point)
2.5 Wiring for 3nos. 6 pin 6/16 A Power plug point controlled by 2nos 16A switch
with 3X 2.5 Sq.mm PVC insulated HF-FRLS multistrand copper conductor 1100
Volt grade wires in recessed/surface PVC conduit including cost of providing
saddles etc for surface conduiting and/or cost of cutting & filling chases for
consiled wiring complete as required. (From DB to Point)
2.6 Wiring for 32A MCCB Breaker with 4sqmm 4Core Copper Cable mounted on
Metal Box with proper Earthing (from DB to AHU) Sets 2
4.2 Fabrication supply and fixing of angle / channel iron brackets / supports of
adequate size to support the cables and panels in existing cable trenches including
fixing clamps and hard ware metering good the damage etc. as required .( Cable
trenches shall be in the scope of building contractor). Contractor should supply the KG 200
Shop Drawings of Hanging arrangement of Cable Tray.
5.0 MV CABLES
5.1 Supplying, Laying, testing & commissioning of the following sizes of XLPE
insulated, multistand Al. & Cu. Conductor armoured cables of 1.1KV grade on the
surface of wall or on existing cable trays or existing Under Ground cable trench
complete with fixing hardware etc. as required.
5.2 Suppling, making, testing & commissioning of end terminations with brass mettalic
double compression glands suitable for the following sizes of XLPE Al. & Cu.
conductor arnoured cables including proper sizes of copper thimbles etc. as
required.