Nothing Special   »   [go: up one dir, main page]

BOQ of Fire Alarm, PA 05-08-14

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 5

Proposed Commercial Complex

at Sector-14, Bahadurgarh.

SUMMARY SHEET (Commercial Block)

SUB
DESCRIPTION Amount (in Rs.)
HEAD
Ph-I Ph-II

Intelligent Analogue Addressable Fire Detection & Alarm


I
System

II Public Address System

III CCTV Surveillance System

TOTAL (in Rs.) - -

SPC Engineers Pvt. Ltd. SQ-5


Proposed Commercial Complex
at Sector-14, Bahadurgarh.

1. Intelligent Analogue Addressable Fire Detection & Alarm System Proposed Commercial Complex at Bahadurgarh.

S.N. Description Unit Rate (Rs.) Qty Amount (Rs.)

Supply, installation testing and commissioning of the following as per


Ph-I PH-II Ph-I PH-II
specification
(for C.C.) (during Fitout)
1 Analogue addressable Acclimate Photo-thermal (Multisensor-combined
photoelectric & thermal sensing in single device) having floating sensitivity,
complete with mounting base & LED, as required. Each 335 110

2 Analogue addressable Acclimate Photo-thermal (Multisensor-combined


photoelectric & thermal sensing in single device) having floating sensitivity,
complete with inbuilt Fault Isolator, mounting base & LED, as required.
Each 15 0

3 Analogue addressable & Multi-cooperative sensing Photoelectric detector,


complete with mounting base & LED, as required. Each 173 0

4 Analogue addressable & Multi-cooperative sensing Photoelectric detector,


complete with inbuilt Fault Isolator, mounting base & LED, as required.
Each 7 2

5 Analogue addressable fixed rate of rise temperature (thermistor) type Heat


detector complete with mounting base & LED, as required. Each 0 5

6 Analogue Addressable Beam detector with Manual as well as Acclimate


variable Sensitivity setting complete with mounting base & LED, as required.
Each 0 6

7 Fault isolator module for isolating shorted, dewired and loose circuits
between two successive fault with automatic resetting arrangement. Each 10 0

8 Analogue Addressable Manual Call point as per specification Each 20 0

9 Addressable Control Modules/ Relay Output module for controlling


Hooters, AHU's, Smoke and Pressurization fans, Fire pumps etc. Each 12 12

10 Addressable Monitor Module with potential free NO & NC contacts


complete with Water flow/Damper control supervisory (for FHC & Damper of
AHU) Each 24 0

11 Analogue Addressable Piezo electronic Hooters/ Sounders of 90 dBA


sound level minimum 10 feet away from the device, including ceiling/ wall
mounting arrangements . Set 20 0

12 Analogue Addressable Piezo electronic Hooters/ Sounders of 90 dBA


sound level minimum 10 feet away from the device with Strobe light (100
cd) including ceiling/ wall mounting arrangements . Set 20 0

13 Response Indicator as per specification Each 80 105

14 Analogue Addressable Two Way communication fire fighters Telephone


Jack with Control module complete as reqd. Set 18 0

15 Supply of Fire fighters Handset Each 2 2

16 Supply, Installation, Testing & commissioning of Audio Coupling Transformer


to integrate DVC with analog amplifiers of PA System along with all
accessories, hardwares as required. Set 1 1

17 Supply, Installation, Testing & commissioning of integrated 8 channel Digital


Voice Command (DVC) for contolling Two Way Communication Fire Fighter
system capable to supervision of all circuits including 8 channel Integerator
Module (DVC-AO) for interfacing Analogue PA system, complete with
accessories etc. as required for complete system. The equipment shall be of
same make as Panel for Fire Alarm System. (Note; the system shall be of
same make as FACP)
Set 1 0

SPC Engineers Pvt. Ltd. SQ-6


Proposed Commercial Complex
at Sector-14, Bahadurgarh.

S.N. Description Unit Rate (Rs.) Qty Amount (Rs.)

18 Providing, installing, connecting, testing and commissioning of micro


processor based Logic driven Peer to Peer Networked (with Network card
as reqd.) Analogue Addessable Fire Alarm Control Panel of following no. of
Loop having not less than 124 addressable detectors per Loop, 640
character LCD display, four access levels. 4000 event historical logging, The
Panel shall be able to give pin point location of all Fire/ Fault conditions of
addressable units via the address codes for each unit. The Panel shall also
be able to automatically switch off all Control Switches when ever any Alarm
is triggered. The Panel shall be coupled to the PA System and have sealed
maintenance free batteries of required capacity of 24 volts capable of
running for a minimum of 24 hours with battery charger, rectifier, Loop cards,
Keypad operation, LCD unit to indicate Fire /Fault Signal of individual unit, in
built / external printer to log all incoming data etc. complete in all respects.
The Panel shall also have Logic hardware and software built into it for
initiating specific AHU tripping, starting of Ventilation Fan & Pumps, time
delay operation of hooter, subsequent operation of analogue speakers, and
shall monitor the Fire Sprinkler & hydrant system. Panel shall also have
inbuilt Auto-dialler with minimum six line output. Panel shall have provide
data output on Modbus for Building management System Platform. One
shall be able to read any Fire / Fault message from any Panel and any panel
shall be able to read the data of any networked panel. However,
configuring /programming shall be from the panel itself.

### 8 Loop Panel Each 1 0

19 Network Repeater Panel with 640 character back lit LCD display with
complete system function keys for programing and control like system reset,
alarm acknowledge, alarm silence, trouble acknowledge etc. and LED
indicated Mimic diagram complete as required. Each 1 1

20 Fire Alarm PC Station consisting of Pentium core i3 processor, 21" colour


LCD TFT monitor, 1024 MB RAM, 120 GB Hard Disk, DVD Drive, USB Port,
Ethernet port, mouse, Windows XP/7 based Software, Graphic (GUI)
software including copy in CD ROM complete as required. PC Work Station
shall include complete Fire Alarm Graphics Software including floor plans
with location of detectors and other devices. All Floors shall be available as
drawing files with location of detectors and devices complete with Loop
number and other details as available on the Software. The Software shall
be customised to the Building and Fire Alarm layout of the building with
location of detectors marked on floor drawings complete with detector
address, detector condition etc. The PC and software shall allow for
programming/ re programming of detector addresses, addition or deletion of
detectors with address change, condition of detectors, event logs for 1000
events complete. The Softwares shall be supllied complete with registered
CD unit complete and site training. The software shall be capable of
monitoring 100 Nodes with 12 MB bud Transmission on cable or more. The
software shall provide the facility to Monitor, control all the Digital PAVA as
well as 2 way communication from main control room using voice signals
over Fire Network as well as over Analogue Public Address system along
with the Fire detection signal.

Set 0 1

21 Supply & fixing of 300/ 500 Volt grade 2C x 1.5sq.mm.Cu.Unarmoured Fire


Survival cables of having cross linked Silicon Rubber insulation with ATC
drain wire and laminated Al. tape screening, LSZH LTS 3 thermoplastic
overall sheathed conforming to BS 7629-1:2008 and conforming to CWZ fire
survival test as per BS 6387:1994 & BS EN 50200:2006 Annex-E.

RM 8500 1500

22 Supply and fixing of 2x1.5sq.mm. FRLS PVC insulated stranded copper


conductor wire in suitable size of 20 mm dia.G.I. Flexible conduit complete
with all accessories as required for wiring of Response Indicator.
RM 300 400

TOTAL
- -

Grand Total -

SPC Engineers Pvt. Ltd. SQ-7


Proposed Commercial Complex
at Sector-14, Bahadurgarh.

2. Public Address System


Amount
S.No. Description Unit Qty Rate (Rs.)
(Rs.)
1 Recess mounted Speakers equivalent to Philips cat No.LBD8353 (6 Watts
Read Power) including line-matching transformer, complete with clamp for
recessed mounting of speaker in false ceiling, as required. Nos 30

2 Wall Mounted Speakers equivalent to Philips cat No.LBC3410 (15 Watts


Read Power) including line matching transformer,complete with wall
mounting bracket and hardwares as required. Nos 30

4.1. 1x 240W PA Amplifier with 4 channel mixer, 5-band Grafic equalizer,


complete with Modular Moulded Plastic eqpt. Rack with glass door of
suitable size to accomondate the amplifers, CD Player & other related
eqpt., including prewired internal wiring, multiple extention 6A socket outlet,
suitable nos. of exhaust fans complete, as required.
Set 1

4.2. 1x 480W PA Amplifier with 4 channel mixer, 5-band Grafic equalizer,


complete with Modular Moulded Plastic eqpt. Rack with glass door of
suitable size to accomondate the amplifers, CD Player & other related
eqpt., including prewired internal wiring, multiple extention 6A socket outlet,
suitable nos. of exhaust fans complete, as required.
Set 1

5 Supply installation testing and commissioning of Four channel Audio mixer


with Goose neck call station with 10 Zone paging microphone comprising
of a paging console with microphone and ON/OFF switches for Zone
Selection, ALL CALL, RESET & Pre-recorded Voice/alarm function,
complete with Distribution unit having a monitored output and 10 individual
zone outputs through 1/4" phone jacks. inside the Security room or in
control room complete as required.
Set 1

6 Supply installation testing and commissioning of Goose neck microphone


complete with all accessories as required (Optional). Nos 1

7 Supply & fixing of 300/ 500 Volt grade 2C x 1.5sq.mm.Cu.Unarmoured


Fire Survival cables of having cross linked Silicon Rubber insulation with
ATC drain wire and laminated Al. tape screening, LSZH LTS 3
thermoplastic overall sheathed conforming to BS 7629-1:2008 and
conforming to CWZ fire survival test as per BS 6387:1994 & BS EN
50200:2006 Annex-E.
RM 2400
Total -

SPC Engineers Pvt.Ltd. SQ-3


Proposed Commercial Complex
at Sector-14, Bahadurgarh.

3. CCTV Surveillance System


S.No. Description Unit Qty Rate (Rs.) Amount (Rs.)
1 1/4" CCD image sensor, high Speed PTZ Dome Camera having 470 TV
Lines resolution, 0.7 Lux, 18X optical and 12X digital Zoom with
continuous auto focus, back light compensation, auto iris control, 360
degree of endless rotation, high speed pan/tilt, including 230V AC / 12V
DC Adaptor (convertor) and plug top with shielded wires and Ceiling
mounting bracket for camera complete.
1.1. With Wall mounted indoor housing Nos 1
1.2. With Wall mounted outdoor housing with sunshield, heater and blower Nos 3

2 1/3" CCD image sensor, fixed Dome Colour Camera, 480 TV Lines, 1.0
Lux with Vari-focal Auto iris lens (4mm-9mm) including 230V AC / 12V DC
Adaptor (convertor) and plug top with shielded wires and Ceiling
mounting bracket for camera complete. Nos. 16

3.1. 16 Channel Real time Digital Video Recorder, 16 Loop-through Video


output respectively, TCP/IP Connectivity, supporting multiprotocols, Live
monitoring at 400FPS & Recording at 200 FPS, simultaneous Recording &
Play Back, built-in Motion based Auto recording in MPEG-4 or H-264
compression format, easy back up through USB port/device, One monitor
(BNC connector) and 1 VGA output complete, including HDD of suitable
GB capacity to back-up for 30 days, as required.
Nos. 1

3.2. 4 Channel Real time Digital Video Recorder, 4 Loop-through Video output
respectively, TCP/IP Connectivity, supporting multiprotocols, Live
monitoring at 400FPS & Recording at 200 FPS, simultaneous Recording &
Play Back, built-in Motion based Auto recording in MPEG-4 or H-264
compression format, easy back up through USB port/device, One monitor
(BNC connector) and 1 VGA output complete, including HDD of suitable
GB capacity to back-up for 30 days, as required.
Nos. 1

4 Supply installation testing and commissioning 24-INCH Color LCD CCTV


MONITOR for viewing complete as required. Nos. 2

5 Multifunction keyboard controller to control DVRs, Monitors and pan and


tilt movement of Speed-dome Cameras with variable speeds from
0.1deg./Sec. to 360deg/Sec. as well as its zoom, focus and iris as
required. Nos 1

6 Supply & laying of following Solid annealed bare electrolytic grade copper
conductor, co-axial cable with PE dielectric, poly-laminated aluminum tape
followed by copper braiding & overall PVC sheathed cable.

a) RG 11 coaxial cable Mtrs. 1700

7 Wiring for 250 volt 6 amps switch socket outlet with 1100 volts grade 1.5
sq.mm PVC insulated multi-stranded copper conductor wires in existing
conduit including providing & fixing of 6 amps 5 pin modular switched
socket with grid & cover plate in GI box and earthing of third pin of socket
with 1.5 sq.mm PVC insulated copper conductor earth wire complete.

a) 6A Switched Socket Nos. 20


b) 2x1.5sq.mm.+1.5sq.mm.(E) Cu.Wire (3Cx 1.5sq.mm.) Mtrs. 800
c) CAT- 5 wire for Speed Dome Camera Mtrs 350

Total -

SPC Engineers Pvt. Ltd. SQ- 4

You might also like