Assignment 6 Solar ERGY 420
Assignment 6 Solar ERGY 420
Assignment 6 Solar ERGY 420
Calculate the overall loss coefficient for a flat plate collector with two glass covers with the
following data:
Wind speed
Solution:
𝑇𝐶
𝑇𝐶1
𝑇𝑃𝑀
[( ) ]
( )
[ ]
( ) [ ]
[ ]
( )
[ ]
( ) [ ]
( ) ( )( )( )
[ ] [
1 1
At this
[ ]
( )
( )
( )
⁄ ( )
( )( )
([ ] )
( )
( )
#1 #2 #3
326.4
307.4 162 161.1 158.4
, ( )
( )
( ) ( )( )
( )( )
350.8236
Problem (2)
Use the top loss empirical equation to calculate the top loss coefficient for the data of
previous problem.
Take
Compare the answer with the value obtained by the exact procedure adopted in problem
(1).
Solution:
[ ]
( )( )
[ ]
( )( )
( )( ) ( )
[ ] [ ]
In Problem 1 we calculated
Conclusion : adding a second glass cover saves more heat energy to the collector
Problem (3)
Determine the collector top loss coefficient for a single glass cover ( M=1 ) with the following
specifications:
Plate emittence,
Solution:
[ ]
( )( )
1
( )( )
[ ]
( )( )
[ ( ) ]
Problem (4)
For the collector of Problem (3) with a top loss coefficient of 6.6 .
Calculate the overall loss coefficient with the following additional specifications:
Collector bank length = 10m , Collector bank width = 3m , Collector thickness =75 mm
Solution:
, 1 , , ,
( 1 )
1
Solar Collector Efficiency
Note that Aperture, Absorber and Gross measurements may differ between test labs and
countries based on their definitions. Eg. Solarkeymark and SRCC are different.
Efficiency Comparisons
As stated above, Aperture is the most widely accepted surface area to use when looking at
performance variables. This is very important, as using the wrong type of surface area greatly
effects the values.
Example:
The "peak efficiency" value for an AP solar collector is 68.7% based on Aperture area of
2.83m2. If based on gross area of 4.4m2, this value is only 43.7%.
A flat plate collector may have a performance value of 75% based on aperture area, but because
the gross area is almost the same as aperture, the gross value will only be slightly lower. So
comparing a flat plate collector's gross area to the gross area of an evacuated tube collector
provides very misleading results.
Sun Angle (IAM)
Depending on the design of the collector, the output may change as the angle between the
collector and the sun changes. This is referred to as Incidence Angle Modifier (IAM). A more
layman friendly term to use is the Sun Angle Factor. Flat plate collectors generally all have the
same curves, but evacuated tube collectors and those with reflectors can have very different
curves throughout the day. For this reason it is important to understand and consider the Sun
Angle Factor for collectors when doing a comparison.
The two types of IAMs are as follows:
Transversal IAM measures the change in performance as the angle of the sun in relation
to the collector changes through the DAY.
Longitudinal IAM measures the change in performance as the angle of the sun in relation
to the collector changes through the YEAR.
Below are examples of IAM curves for the average flat plate collector, and then the Apricus AP
evacuated tube collector.
For flat plate collectors, both the longitudinal and transversal curves follow the same path, which
is close to a cosine curve. As the angle of the sun passes the 45o point the amount of light the
collector receives rapidly drop, reaching zero at 90o.
The graph shown above is for the Apricus AP evacuated tube solar collector
(Link for More info & Reference : http://www.apricus.com/html/solar_collector.htm#.VmTwRlQdAjU )
. For such evacuated tubes collectors that have the tubes installed in the vertical orientation (up-
down, not left-right) the longitudinal curve is virtually the same as a flat plate. The transversal
curve, however, differs greatly, with the actual shape of the curve depending greatly on the
spacing of the evacuated tubes and if a reflective panel is present or not. The IAM angle factors
can be multiplied by an energy output calculation (outlined earlier) to obtain the actual output from
the collector at a certain time of the day. Below are the raw values for each angle which are
required if doing solar collector output calculations.
Longitudinal 1.00 1.00 1.00 0.99 0.97 0.92 0.84 0.70 0.45 0.00
Transversal 1.00 1.02 1.08 1.18 1.35 1.47 1.39 1.57 0.95 1.00
The shape of the transversal IAM curve is linked to the round shape of the evacuated tubes and
the space between the tubes that allow light through at midday.
Due to the 360o absorber surface, Apricus evacuated tubes Passively Track the sun throughout
the day, as the round absorber is facing the sun from 7am to 5pm. This is a key advantage over
flat plate collectors than only have maximum sun exposure (angle factor = 1) at midday.
Passive tracking of Apricus AP evacuated tube solar collectors and the resultant Sun Angle
Factor adjustment is required to get true output values. Ignoring this and just comparing to
another collector based on the performance variables would not provide accurate real life output
values. Modeling software packages such as Polysun (used by Apricus) take into full
consideration both the longitudinal and transversal IAM factors to provide a very accurate output
model for a system over a typical full year of operation.