Earthing Grid Calculations For Khondbond R3 For Approval
Earthing Grid Calculations For Khondbond R3 For Approval
Earthing Grid Calculations For Khondbond R3 For Approval
SHEET 3 OF 25
TPL-039-EDC-8001 EARTHING CALCULATION
Reference standard : IS 3043
1. CONDUCTOR SIZING
Input data :-
Conductor Size :-
As per IS,
(B+20) θf - θ i
A= If. t K = QC log e 1 +
K δ 20 B+θi
K = 80.69
A 619.68 sq.mm
= 29.60 mm
to standard size
As per calculation 32mm Dia rod is sufficient, however as per MOM 29-11-2012 Note number 25 page 20 of 22
Reference documents :
a) IS 3043
b) Soil Resistivity Report :Attached
90 Refer Group-4
4 Group-4 (R4) 3.77 15 Calculation Sheet 562.43
1 60 Refer Group-6
6 Group-6 (R6) 10.48 25 Calculation Sheet 113
75 Refer Group-7
7 Group-7 (R7) 3.79 15 Calculation Sheet 600.1
1/Rz=1/R1+1/R2+1/R3+1/R4+1/R5+1/R6+1/R7+1/R8+
1/R9+1/R10+1/R11
Paralleling of all the Zones
1/RZ 10.46
Value of RZ 0.096
Conclusion
The Earth resistance of whole plant area is 0.096(Ω) which satisfies the requirement of Earth resistance of
overall to be lower than 1(Ω).
No of driven rods apart from node rods will be placed along the building periphery and at free space
NOTE: 1
which will be connected to main grid.
3 Neutral earth pits are not considered for the above sizing calculation.
4 All Building Dimensions are approximate however their can be variation at a later date.
5 Dedicated Electronic Earth pit will be considered separately for electronic equipments.
6 Earthing conductor along the pipe rack structure to the slime dam area is not considered
in the above calculations. How ever by considering the same the Resistance value further come down.
7 Any other area which is not considered in the above calculation will be shown in Composite
Earthing Layout
8 Earth conductor and Inter connection rods buried 600mm from Finished Ground level
9 Zones are marked in enclosed Annexure-1 for Reference.
For Weigh Bridge area which is isolated from main grid for present operation , for this area good soil to be used for
10 achieving required Grid resistance.
CALCULATION NO TATA PROJECTS LIMITED
SHEET 5 OF 25
TPL-039-EDC-8001 EARTHING CALCULATION
LCSS-1
1 Input Data :
1 System Voltage, Vs = 6.6 kV
Where,
Ig = grid current = I f x Sf
Ig = 11 KA at Sf = 0.5
Substituting the values,
As GPR is < 10kV,in this case no need to calculate Attainable touch and Step Potential.
CALCULATION NO TATA PROJECTS LIMITED
SHEET 6 OF 25
TPL-039-EDC-8001 EARTHING CALCULATION
2 Calculation for Resistance of one pipe electrode for deep bore (Re):
a) Resistance of one pipe electrode (Re) = 100ρ 4l
2pi l d
---------- In -----
2pi l d
2pi l d
---------- In -------
2pi l wt
LCSS-2
1 Input Data :
Where,
Ig = grid current = If x S f
Ig = 11 KA at Sf = 0.5
As GPR is < 10kV,in this case no need to calculate Attainable touch and Step Potential.
CALCULATION NO TATA PROJECTS LIMITED
SHEET 9 OF 25
TPL-039-EDC-8001 EARTHING CALCULATION
2 Calculation for Resistance of one pipe electrode for deep bore (Re):
= 0.90 ohm
Total Resistance
CALCULATION NO TATA PROJECTS LIMITED
SHEET 11 OF 25
TPL-039-EDC-8001 EARTHING CALCULATION
MPDS
1 Input Data :
Where,
Ig = grid current = If x Sf
Ig = 11 KA at Sf = 0.5
As GPR is < 10kV,in this case no need to calculate Attainable touch and Step Potential.
CALCULATION NO TATA PROJECTS LIMITED
SHEET 12 OF 25
TPL-039-EDC-8001 EARTHING CALCULATION
2 Calculation for Resistance of one pipe electrode for deep bore (Re):
= 2.40 ohm
For MPDS Earthing Resistance(RG2)
Effective Resistence 1.10
(1/RG1+1/Rp1+1/Rp2+1/Re)
0.91 Ohm
Total Resistance
CALCULATION NO TATA PROJECTS LIMITED
SHEET 14 OF 25
TPL-039-EDC-8001 EARTHING CALCULATION
LCSS-3
1 Input Data :
Where,
Ig = grid current = I f x Sf
Ig = 11 KA at Sf = 0.5
As GPR is < 10kV,in this case no need to calculate Attainable touch and Step Potential.
CALCULATION NO TATA PROJECTS LIMITED
SHEET 15 OF 25
TPL-039-EDC-8001 EARTHING CALCULATION
2 Calculation for Resistance of one pipe electrode for deep bore (Re):
---------- In -----
2pi l d
(i) Length of pipe, L = 2000 cm
---------- In -----
2pi l d
---------- In -----
2pi l d
---------- In -------
2pi l wt
1/RG1= 1/R1+1/R4+1/R5
Paralleing of all the areas Value of
1/RG1 0.46
---------- In -----
2pi l d
---------- In -----
2pi l d
SECONDARY CRUSHER
2 17 15 2510.33 0.6 12800 41.95 0.20 20.00 100.00 4.92
HOUSE (DOUBLE GRID)(R2)
1/RG1=1/R1+1/R2+1/R3+1/R4
Paralleing of all the areas
Value of 1/RG1 0.64
---------- In -----
2pi l d
---------- In -----
2pi l d
1/RG1=1/R1+1/R2+1/R3+1/R4+1/R5+1/R6
+1/R7
Paralleing of all the areas
Value of 1/RG1 0.30
Effective value
of RG
4.76
CALCULATION NO TATA PROJECTS LIMITED SHEET 20 OF 25
---------- In -----
2pi l d
---------- In -----
2pi l d
1/RG1=1/R1+1/R2+1/R3+1/R4+1/R5+1/R6+1/
R7
Paralleing of all the areas
Value of 1/RG1 0.27
---------- In -----
2pi l d
---------- In -----
2pi l d
0.6 85.13
2 TH8(SINGLE GRID)(R2) 14.1 11 2321.30 5020
0.6 65.34
3 TH9(SINGLE GRID)(R3) 19.5 15 2321.30 6900
0.6 98.61
4 TH10(SINGLE GRID)(R4) 12 9 2321.30 4200
DH1 AND DH2 (SINGLE GRID) 0.6 24.98 0.19 15.00 80.00 5.17
5 (R5) 100 7 2321.30 21400
TH11(SINGLE GRID)(R6)
6 12 9 4225.34 0.6 4200 179.50 5.02
MUTUAL WITH R5
1/RG1=1/R1+1/R2+1/R3+1/R4+1/R6
Paralleing of all the areas
Value of 1/RG1 0.50
---------- In -----
2pi l d
---------- In -----
2pi l d
1/RG1=1/R1+1/R2+1/Rp1+1/Rp2
Paralleing of all the areas Value of
1/RG1 0.10
---------- In -----
2pi l d
---------- In -----
2pi l d
EMERGENCY DG (SINGLE
GRID AND IT MAY BE 0.6 88.34
CLBBED WITH MPDS GRID)
1 (R1) 13 11 2321.30 4800
0.6 74.46
4 TH7(SINGLE GRID)(R4) 17.5 12 2321.30 5900
0.6 81.39
5 TH6(SINGLE GRID)(R5) 19 7.5 2321.30 5300
1/RG1=1/R1+1/R2+1/R3+1/R4+1/R5
Paralleing of all the areas
Value of 1/RG1 0.26
Thickness
(in sqmm)
S.No Equipment Remarks
(in mm)
(in mm)
Width
Area
Neutral Earthing
LV Neutral of Power Through 1Cx630sqmm cable
1 Transformer through
NGR
LV Neutral of service Through 1Cx630sqmm cable
2 Transformer
(1000kVA & above)
LV Neutral of service Through 1Cx630sqmm cable
3 Transformer (630kVA
& below)
LV Neutral of Lighting
4 25 4 100
Transformer
Enclosure Earthing
33/6.9 Power
5 75 10 750
Transformer
6 6.6 kV SPB Busduct 75 10 750
7 6.6 kV Swgr 75 10 750
8 6.6 kV Motors 50 6 300
2000kVA LT
9 75 10 750
Transformers
1600kVA and
10 65 8 520
1000kVA Transformer
11 LT Busducts 65 8 520
12 LT PCC 65 8 520
13 LT MCC 65 6 390
14 DB 50 6 300
15 DG Set 50 6 300
Battery Charger
16 50 6 300
/DCDB
17 Cable Trays 25 6 150
Structural Steel
18 25 6 150
Columns
19 Steel pipe rack 25 6 150
20 Control Panel 25 6 150
21 3 Phase Receptacles 25 6 150
22 Fence/Gate 25 6 150
23 Lighting Mast/Pole 25 4 100
24 Local Starters 8 SWG
25 Junction Boxes 8 SWG
26 Local control stations 8 SWG
Thickness
(in sqmm)
S.No Equipment Remarks
(in mm)
(in mm)
Width
Area
LT Motors (Rating in kW)
LT AC motors from
27 150 KW up to 200 50 6
KW
LT AC motors from
28 110 KW up to 132 40 6
KW
LT AC motors from 55
29 25 6
KW up to 90 KW
LT AC motors from 15
30 25 6
KW up to 45 KW
LT AC motors from
31 16.0 Stranded
3.75 KW up to 11 KW
LT AC motors from
32 6 Stranded
0.75 KW up to 11 KW
Main lighting
33 50 6
distribution board
MCB DB/sub-lighting
boards, lighting
transformer,
34 25 4
continuous earth bus
for highbay lighting
system
Push-button station,
limit switches, switch
36 boxes, isolator and 6 Stranded
socket outlet up to
16A
Highbay lighting
37 fittings, control gear 12 SWG
and junction boxes
38 Lighting wiring system 14 SWG