TECHNICAL MANUAL

KNX SERIES

vitrum.com
INDEX FOR SECTION

VITRUM INTERFACES POWER SUPPLY


PAG. 1
PAG. 5

OUTPUTS INPUTS/OUTPUTS
PAG. 11 PAG. 18

FANCOIL UNIT ENERGY METER


PAG. 28 PAG. 30

DIMMER INTERFACES & PROBE


PAG. 37 PAG. 44

INTERFACES & GATEWAY TOUCH PANEL


PAG. 52 PAG. 62

KNX SERIES
Vitrum Interfaces EU KNX Series
Datasheet

Aesthetic component Electronic module

cod. 11E01000.90001.00 cod. 0KE010020

cod. 11E02000.90001.00 cod. 0KE020020

cod. 11E03000.90001.00 cod. 0KE030020

cod. 11E04000.90001.00 cod. 0KE040020

cod. 11E06000.90001.00 cod. 0KE060020

Main features Mechanical and aesthetics specifications


• 1, 2, 3, 4, 6 buttons command device - KNX programmable Aesthetic component - GLASS COLLECTION
• Touch control based on capacitive technology - KNX programmable • Dimensions: 126x95 mm
• Hand proximity detection - KNX programmable • Thickness (visible outside wall): 8mm
• Acoustic feedback signal when button touched - KNX programmable • Button diameter: - 38 mm (1 button)
• RGB back light on button - KNX programmable (colour and intensity) - 16 mm (2,3,4,6 buttons)
• Access to local semplified setup menù: program button on the back or • Weight: 130 g.
combination of key sequence on face plate • Back light diameter: 42 mm (1 button)
• KNX switch functions: on-off, dimmer (quick and slow ramp), shutters
18 mm (2, 3, 4, 6 buttons)
Electronic module
• Fitting wall or plasterboard 3 modules Box (EU 503)
• Dimensions: 115x84 mm
• Weight: 98 g.

Electrical scheme Technical specifications

General info
• Power feed: Bus KNX 29 Vdc
• Energy consumption: <1,5watt
• IP Class: IP 20
• Storage temperature: -40°/+55C°
• Storage humidity: 10% - 93%
• Operating temperature: -10C°/+45°C
• Operating humidity 20% - 90%
Bus + suppl KNX 29 Vdc • Raccomanded cable for wiring:
- belden YE00820
- belden YE00906

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 1


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Vitrum Interfaces BS KNX Series
Datasheet

Aesthetic component Electronic module

cod. 11B01000.90001.00 cod. 0KB010020

cod. 11B02000.90001.00 cod. 0KB020020

cod. 11B04000.90001.00 cod. 0KB040020

Main features Mechanical and aesthetics specifications


• 1, 2, 4 buttons command device - KNX programmable Aesthetic component - GLASS COLLECTION
• Touch control based on capacitive technology - KNX programmable • Dimensions: 95x95 mm
• Hand proximity detection - KNX programmable • Thickness (visible outside wall): 8mm
• Acoustic feedback signal when button touched - KNX programmable • Button diameter: - 38 mm (1 button)
• RGB back light on button - KNX programmable (colour and intensity) - 16 mm (2, 4 buttons)
• Access to local semplified setup menù: program button on the back or • Weight: 95 g.
combination of key sequence on face plate • Back light diameter: 42 mm (1 button)
• KNX switch functions: on-off, dimmer (quick and slow ramp), shutters
18 mm (2, 4 buttons)
Electronic module
• Fitting wall or plasterboard two modules british Box
• Dimensions: 86x86 mm
• Weight: 90 g.

Electrical scheme Technical specifications

General info
• Power feed: Bus KNX 29 Vdc
• Energy consumption: <1,5watt
• IP Class: IP 20
• Storage temperature: -40°/+55C°
• Storage humidity: 10% - 93%
• Operating temperature: -10C°/+45°C
• Operating humidity 20% - 90%
Bus + suppl KNX 29 Vdc
• Raccomanded cable for wiring:
- belden YE00820
- belden YE00906

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 2


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Vitrum Interfaces EU Clima Control KNX Series
Datasheet

Aesthetic component Electronic module

Main features Mechanical and aesthetics specifications


• Electronic thermostat with a large easy display to read current room Aesthetic component - GLASS COLLECTION
temperature and the set-point • Dimensions: 126x95 mm
• The front wheel selector offer a user friendly interface to change the • Thickness (visible outside wall): 8mm
temperature set-point • Button diameter: 42 mm
• Two additional buttons for toggling the “eco mode” and one used for • Weight: 130 g.
cycling through different choice of fan speed • Back light diameter: 44 mm
• Touch control based on high sensitive capacitive technology
• Display for displaying the temperature Electronic module
• Hand proximity detection - KNX prog rammable • Fitting wall or plasterboard 3 modules Box (EU 503)
• Acoustic feedback signal when button touched - KNX programmable • Dimensions: 115x84 mm
• RGB back light on button - KNX programmable (colour and intensity) • Weight: 98 g.
• Access to local semplified setup menù: program button on the back or
combination of key sequence on face plate

Electrical scheme Technical specifications

General info
• Power feed: Bus KNX 29 Vdc
• Energy consumption: <1,5watt
• IP Class: IP 20
• Storage temperature: -40°/+55C°
• Storage humidity: 10% - 93%
• Operating temperature: -10C°/+45°C
• Operating humidity 20% - 90%
Bus + suppl KNX 29 Vdc • Raccomanded cable for wiring:
- belden YE00820
- belden YE00906

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 3


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Vitrum Interfaces BS Clima Control KNX Series
Datasheet

Aesthetic component Electronic module

Main features Mechanical and aesthetics specifications


• Electronic thermostat with a large easy display to read current room Aesthetic component - GLASS COLLECTION
temperature and the set-point • Dimensions: 95x95 mm
• The front wheel selector offer a user friendly interface to change the • Thickness (visible outside wall): 8mm
temperature set-point • Button diameter: 38 mm
• Two additional buttons for toggling the “eco mode” and one used for • Weight: 95 g.
cycling through different choice of fan speed • Back light diameter: 42 mm
• Touch control based on high sensitive capacitive technology
• Display for displaying the temperature Electronic module
• Hand proximity detection - KNX prog rammable • Fitting wall or plasterboard one gang british embedding box
• Acoustic feedback signal when button touched - KNX programmable • Dimensions: 86x86 mm
• RGB back light on button - KNX programmable (colour and intensity) • Weight: 90 g.
• Access to local semplified setup menù: program button on the back or
combination of key sequence on face plate

Electrical scheme Technical specifications


General info
• Power feed: Bus KNX 29 Vdc
• Energy consumption: <1,5watt
• IP Class: IP 20
• Storage temperature: -40°/+55C°
• Storage humidity: 10% - 93%
• Operating temperature: -10C°/+45°C
• Operating humidity 20% - 90%
Bus + suppl KNX 29 Vdc
• Raccomanded cable for wiring:
- belden YE00820
- belden YE00906

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 4


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Alimentatore 160 mA
cod. 0KD010020

Product and Applications Description

The power supply unit 0KD010020 provides the system power necessary for Input voltage
the instabus EIB. The connection to the bus line is established by clicking • rated voltage: AC 100.240 V, 50...60Hz Rated power intake
the device onto the DIN-rail (with a data rail installed) and/or via the bus approx. 24 VA
connection block located on the front side.
The integrated choke prevents the data telegrams from shortcircuiting on Output voltage
the bus line. When the built-in reset switch is operated (operation > 20s), the • rated voltage: DC 30 V
bus devices are returned to their initial state. • safety extra low voltage (SELV)
For each bus line, at least one power supply unit 0KD010020 is needed. Up • permissible range: DC 28 ... 31 V
to two power supply units may be attached to a single bus line.
A second unit is not required unless the supply voltage at a bus device is Output current
less than 21 V. The cable length between the two power supply units must • rated current : 160 mA
be at least 200 m. Backup interval
When more than 30 bus devices are installed in short bus cable distance (e.g. 160 mA 0KD010020
10 m), e.g. in distribution boards, the power supply unit 0KD010020 should on input voltage failure: approx. 200 ms at rated current
be arranged near these bus devices. The distance between power supply
unit 0KD010020 and any of its bus devices must not exceed 350 m. Connections
The power supply unit 0KD010020 has a voltage and current regulation and • mains connection: max 2,5 mm2 cross sections
is therefore short-circuit proof. Short power failures can be bridged with a • bus line: pressure contacts on data rail, screwless extra low voltage terminal
backup interval of approximately 200 ms. (red.black) 0 0,6 ... 0,8 mm
To ensure an uninterrupted power supply a separate circuit with safety • output voltage (no choke): screwless extra low voltage terminal (yellow-
separation should be used for the power supply unit 0KD010020’s power white) 0 0,6 ... 0,8 mm
supply line.
The power supply unit 0KD010020 can supply DC 30 V power from an Physical specifications
additional pair of terminals (yellow-white). • dimensions: DIN-rail mounted device, width: 4 SU (1 SU = 18 mm)
• weight: approx. 240 g
The OKD010020 does not require any application programs
Electrical safety
• protection (according to EN 60529): IP 20 Environmental specifications
• ambient temperature operating: - 5 ... + 45 °C
• storage temperature: - 25 ... + 70 °C
• relative humidity (non-condensing): 5 % to 93 %

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 5


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Power Supply Unit 320 mA
cod. 0KD010024

Product and Applications Description

The power supply unit 0KD010024 provides the system power necessary for Input voltage
the instabus EIB. The connection to the bus line is established by clicking • rated voltage: AC 100.240 V, 50...60Hz
the device onto the DIN-rail (with a data rail installed) and/or via the bus Rated power intake
connection block located on the front side. approx. 24 VA
The integrated choke prevents the data telegrams from shortcircuiting on
the bus line. When the built-in reset switch is operated (operation > 20s), the Output voltage
bus devices are returned to their initial state. • rated voltage: DC 29 V
For each bus line, at least one power supply unit 0KD010024 is needed. Up • safety extra low voltage (SELV)
to two power supply units may be attached to a single bus line. • permissible range: DC 28 ... 31 V
A second unit is not required unless the supply voltage at a bus device is
less than 21 V. The cable length between the two power supply units must Output current
be at least 200 m. • rated current : 320 mA 0KD010024
When more than 30 bus devices are installed in short bus cable distance (e.g. • short-circuit current: 0KD010024 limited to 1,0 A
10 m), e.g. in distribution boards, the power supply unit 0KD010024 should
be arranged near these bus devices. The distance between power supply Backup interval on input voltage failure: approx. 200 ms at rated current
unit 0KD010024 and any of its bus devices must not exceed 350 m.
The power supply unit 0KD010024 has a voltage and current regulation and Connections
is therefore short-circuit proof. Short power failures can be bridged with a • mains connection, screwless plug-in terminals: strip insulation for 9..10 mm
backup interval of approximately 200 ms. permissible conductor types/cross sections:
To ensure an uninterrupted power supply a separate circuit with safety • 0,5 ... 3,3 mm² ( AWG 12) single core
separation should be used for the power supply unit 0KD010024’s power • 0,5 ... 2,5 mm² plain flexible conductor
supply line. • 0,5 ... 3,3 mm² (AWG 12) stranded conductor
The power supply unit 0KD010024 can supply DC 30 V power from an • 0,5 ... 3,3 mm² (AWG 12) flexible conductor with terminal pin, crimped
additional pair of terminals (yellow-white). on gas tight
• bus line: pressure contacts on data rail, screwless extra low voltage terminal
(red.black)  0,6 ... 0,8 mm
The 0KD010024 does not require any application programs
• output voltage (no choke) : screwless extra low voltage terminal (yellow-
white)  0,6 ... 0,8 mm

Physical specifications
• dimensions: DIN-rail mounted device, width: 4 SU (1 SU = 18 mm)
• weight: approx. 240 g

Electrical safety
• protection (according to EN 60529): IP 20

Environmental specifications
• ambient temperature operating: - 5 ... + 45 °C
• storage temperature: - 25 ... + 70 ° C
• relative humidity (non-condensing): 5 % to 93 %

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 6


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Power Supply Unit 640 mA
cod. 0KD010021

Product and Applications Description

The power supply unit 0KD010021 provides the system power necessary for Input voltage
the instabus EIB. The connection to the bus line is established by clicking • rated voltage: AC 100.240 V, 50...60Hz Rated power intake
the device onto the DIN-rail (with a data rail installed) and/or via the bus approx. 24 VA
connection block located on the front side.
The integrated choke prevents the data telegrams from shortcircuiting on Output voltage
the bus line. When the built-in reset switch is operated (operation > 20s), the • rated voltage: DC 29 V
bus devices are returned to their initial state. • safety extra low voltage (SELV)
For each bus line, at least one power supply unit 0KD010021 is needed. Up • permissible range: DC 28 ... 31 V
to two power supply units may be attached to a single bus line.
A second unit is not required unless the supply voltage at a bus device is Output current
less than 21 V. The cable length between the two power supply units must • rated current : 640 mA
be at least 200 m. • short-circuit current: limited to 1,0 A
When more than 30 bus devices are installed in short bus cable distance (e.g.
10 m), e.g. in distribution boards, the power supply unit 0KD010021 should Backup interval
be arranged near these bus devices. The distance between power supply on input voltage failure: approx. 200 ms at rated current
unit 0KD010021 and any of its bus devices must not exceed 350 m.
The power supply unit 0KD010021 has a voltage and current regulation and Connections
is therefore short-circuit proof. Short power failures can be bridged with a • mains connection, screwless plug-in terminals: strip insulation for 9 ... 10
backup interval of approximately 200 ms. mm
To ensure an uninterrupted power supply a separate circuit with safety permissible conductor types/cross sections:
separation should be used for the power supply unit 0KD010021’s power - 0,5 ... 3,3 mm2 ( AWG 12) single core
supply line. - 0,5 ... 2,5 mm2 plain flexible conductor
The power supply unit 0KD010021 can supply DC 30 V power from an - 0,5 ... 3,3 mm2 (AWG 12) stranded conductor
additional pair of terminals (yellow-white). - 0,5 ... 3,3 mm2 (AWG 12) flexible conductor with terminal pin, crimped on
gas tight
• bus line: pressure contacts on data rail, screwless extra low voltage terminal
The OKD010021 does not require any application programs
(red.black) 0 0,6 ... 0,8 mm
• output voltage (no choke) : screwless extra low voltage terminal (yellow-
white) 0 0,6 ... 0,8 mm

Physical specifications
• dimensions: DIN-rail mounted device, width: 6 SU (1 SU = 18 mm)
• weight: approx. 240 g

Electrical safety
• protection (according to EN 60529): IP 20

Environmental specifications
• ambient temperature operating: - 5 ... + 45 °C
• storage temperature: - 25 ... + 70 °C
• relative humidity (non-condensing): 5 % to 93 %

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 7


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Line Coupler BUS line KNX
cod. 0KD010000

Product and Applications Description

This device is a product of the KNX/EIB instabus-KNX/ EIB system and


complies with KNX directives. Detailed technical knowledge obtained in
KNX/EIB training courses is a prerequisite to proper understanding. Terminals, connections and command/visualisation elements
0KD010000 can be used as a line coupler to connect a line to a main line or
as a backbone coupler to connect a main line to a backbone line.
0KD010000 supports long messages (up to 250 bytes) and provide a
configurable special function activating by a frontal button which is very
useful in commissioning / installing phase or during system tuning.
Planning, installation and commissioning of the unit is effected by means of
KNX-certified software.

Technical Specifications

The coupler connects two instabus KNX/EIB data lines and ensures the
electrical (galvanic) separation of these lines from one another.
The definite functions of the device are defined by addressing and
parameterization.

Line coupler LK: Physical address X.0.0


Connection of a main line (HL) with an area line (BL). Alternatively with or
without filter function. The coupler belongs logically to the subordinate line.

Area coupler BK: Physical address X.0.0


Connection of a main line with an area line. Alternatively with or without
filter function. The coupler belongs logically to the subordinate line.

Amplifier V: Physical address X.Y.Z


Handling and repetition of telegrams on a line, no filter function. Division
of a line into max. 4 independent line segments => max. 3 line amplifiers
connected in parallel per line (FIG. C). Each line segment requires a separate
power supply (SV) including a choke (DR)

Supply from bus KNX/EIB: 21 - 30 V DC


approx 30 mA from primary line approx 5 mA from secondary line.

Connection:
KNX/EIB instabus terminal for superordinate and subordinate line.

Fitting: Snap-fastening on DIN rail

Ambient temperature: -5 °C ... +45 °C


Storage temperature.: -20 °C ... + 60 °C
Relative Humidity: max 93% not condensing

Electrical Safety:
Type of protection: IP 20 in acc. with EN 60529
Safety class: III in acc. With EN 61140

Device complies with EN 50090-2-2 and IEC 60664-1

Installation width: 36 mm (2 modules)

Weight: Approx. 66 g

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 8


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Line Coupler BUS line KNX
cod. 0KD010000

LED DESCRIPTION

LED Bus Stat Main green


Off: main line error Location/Function of the Display and Operating elements
On: main line ok
1. LED Bus Stat Main
LED Bus Stat Main red 2. LED Bus Stat Sub
On: manual overwrite active
3. LED Traffic Main
LED Bus Stat Sub green 4. LED Traffic Sub
Off: sub line error or not connected 5. LED GA (Group Address)
On: sub line ok 6. LED PA (Physical Address)
7. Function button
LED Traffic Main green 8. Programming LED
Blinking: bus traffic on main line 9. Programming button
Off: no traffic on main line
10. KNX-Bus connection:
LED Traffic Sub green Main line
Blinking: bus traffic on sub line 11. KNX-Bus connection:
Off: no traffic on sub line Sub line

LED Traffic Main red


Blinking: transmission error on main line

LED Traffic Sub red


Blinking: transmission error on
sub line

LED Group Address Mounting and Wiring hintselements


Routing of group telegrams
Off: main and sub different 1 The device is snap-fastened on the DIN rail until the latch is heard to
Green: filter table active engage, with the connecting terminals pointing downwards.
Green and red: route all 2 The PRIMARY line is connected with the lefthand terminal This terminal
Red: block supplies power to the device electronics so that it is possible to report a bus
voltage failure of the subordinate via the PRIMARY line.
LED Physical Address 3 The secondary line is connected to the right-hand terminal
Routing of physical addressed telegrams 4 Load the physical address into the push-button from the ETS via the KNX
Off: main and sub different bus.
Green: filter table active 5 Complete the required configuration settings in the ETS, and transfer the
Green and yellow: route all configuration via EIB into the coupler.
Yellow: block
IMPORTANT
• This device must be installed only by a qualified electrician.
FUNCTION BUTTON • Install in conformity to SELV installation rules.
•The applicable safety and accident prevention regulations must be
Long press (3 sec)
Switch to manual override. observed.
Default function is set with main line and (sub) line parameter. • The device must not be opened. Any faulty devices should be returned to
Manual override functionality is configured in “General parameters”. manufacturer.
• For planning and construction of electric installations, the relevant
LED Bus Stat Main red guidelines, regulations and standards of the respective country are to be
On: manual override active considered.
Off: default configuration active

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 9


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Transformer 230V-12/15 VAC (max. 6 devices)
Transformer 230V-12/24 VAC (max. 12 devices)
cod. 0KD010022 e 0KD010023

Product and Applications Description Terminals, connections and command/visualisation

The products 0KD010022 and 0KD010023 are range of transformer


modules for continuous use.
The entire series has double insulation between primary and secondary
circuit.

Technical Specifications

• Primary voltage: 230 Vac. ± 10%


• Frequency: 50/60 Hz
• Class of Operation: II
• Housing: Self-extinguishing Thermoplastic Material
• Operating Temperature Continuous: +115 ° C (according to IEC216)
Section-Max Cables: 4mm ²
• Inspection and testing of Dielectric strength: 3.75 KV
0KD010022
• Compliance Standards: 73/23 / EEC mod.da 93/68 / EEC (low
voltage)89/336 / EEC mod.da 92/31 / EEC and 93/68/EEC(EMC) is declared
in 0KD010023
reference to the following Standards: CEI EN 60742 Safety (95)

0KD010022
0KD010023

Mounting and Wiring hints

Device is intended to be used indoor in dry places.

IMPORTANT
• This device must be installed only by a qualified electrician.
• Install in conformity to SELV installation rules.
• The applicable safety and accident prevention regulations must be
observed.
• The device must not be opened. Any faulty devices should be returned
to manufacturer.
• For planning and construction of electric installations, the relevant
guidelines, regulations and standards of the respective country are to be
considered.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 10


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Module 4 Output with Manual Control
cod. 0KD040020

Product and Applications description


0KD040020 is a Din Rail 4 output 16A - 230V AC actuator and
can be used to:
• Control up to 4 independent loads / lights
• Control up to 2 independent blind / roller shutters with mechanical end
position

Device is intended to be installed on DIN rail.

ETS Application Program


Maximum number of group addresses: 53
This is the maximum number of different group addresses the device
is able to memorize.
Maximum number of associations: 60 Terminal and connections
This is the maximum number of associations between communication SCREW TERMINALS:
objects and group addresses the device is able to store. 1. COM OUT 1
Caution: there is a limit to the number of associations that can be 2. OUT 1 contact relay 1
created, on the same device, between transmission communications 3. COM OUT 2
4. OUT2 contact relay 2
objects (i.e. output feedback) and receiving communication
5. COM OUT 3
objects (i.e. outputs). 6. OUT3 contact relay 3
If you want, on the same device, add a group address linked to 7. COM OUT 4
a transmission communication object (feedback) to a receiving 8. OUT4 contact relay 4
communication object (output) which already has a different group
PROGRAMMING:
address associated, please note that you can add a maximum of 7
30. ETS programming led
group addresses of this kind for the whole device. 31. ETS programming switch

Technical Specifications
Output Configuration for Shutter
Power Supply
• Via bus EIB/KNX cable 21..32V DC
• Current consumption ≤ 10 mA
• Max Current consumption during switching (30 ms): 14mA
Outputs
• 16 A cos φ 1 - 230 V AC
• 8 A cos φ 0.6 - 230 V AC
• Minimum switching current: 10mA
Pure resistive loads: max 16 A Installation Instructions
Incandescent lamps: max 10 A WARNING: Device must be installed keeping a minimum distance of 4mm
Motors e motor reduction: max 10 A between electrical power line (mains - 230V) and red / black bus connector or bus
Fluorescent lamps with electronic transformer: max 4 A cable.
Fluorescent lamps: (max 140 μF) max 3A (700W) • Device may be used for indoor installations in dry locations.
Physical specifications and Dimensions • Device must be mounted by an authorised installer.
• Plastic enclosure: PA6 • Device must be installed in a location that is accessibleonly to qualified
• Dimensions: (alt. x larg. x prof.): 90 x 71 x 58 mm installers
• Weight (approx): 200 g • The applicable safety and accident prevention regulationsmust be
• Installation: Din Rail observed.
• Din rail width: 4 modules • Device must not be opened. Any faulty device should bereturned to
Electrical Safety manufacturer.
• Degree of pollution (IEC 60664-1): 2 • For planning and construction of electric installations, therelevant
• Degree of protection (EN 60529): IP 20 guidelines, regulations and standards of the respectivecountry are to be
• Protection class (according to IEC 1140): III considered.
• Overvoltage class (according to IEC 664-1): III • KNX bus allows you to remotely send commands to thesystem actuators.
• Bus: safety voltage SELV Always make sure that the execution ofremote commands do not lead to
• Meets EN 50491-3 hazardous situations,and that the user always has a warning about which
Electromagnetic compatibility commandscan be activated remotely.
Compliant with EN 50491-5-1 and EN 50491-5-2 • Relays are always switched opened before deliveringbut , it is possible
Environmental specifications during transportation, they get closed.It is recommended, when device is
• According to EN 50491-2 installed, to connect and supply the bus before the load voltage to
• Ambient temperature during operation: 0°C + 45°C ensure the opening of the contacts
• Storage temperature: - 20 °C + 55 °C • Before configuring the device using ETS, the output channels are
• Relative humidity: max 90 % configured for shutter management in order to avoid improper control of
this type of load. Frontal button are configured to switch the relay with
logical interlock.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 11


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Module 4 Output
cod. 0KD040021

Product and Applications description Wiring Diagram


The DIN RAIL 4 Output Module 0KD040021 is an EIB/KNX DIN rail mounting
device useful to interface loads (e.g. lamps) for any kind of applications.
Device 4 outputs on board can be configured:
• Each output can be configured independently for load control (R1 to R4)
• Each output can be configured independently for ON / OFF or continuous
switching (PWM) for Electric valves (solenoid actuators) (EV1 to EV4)
• Outputs can be configured in pairs for the management of roller shutters
and blinds; up to 2 channels (Channels A to B)
• Outputs can be configured in pairs for management of Motor Reductor
or for solenoid valves with 3-point control or for ventilating grille; up to 2
channels (Channels A to B)
Device is intended to be installed on DIN rail.

Application Program
Maximum number of group addresses: 50
This is the maximum number of different group addresses the device is able
to memorize.

Maximum number of associations: 63 Physical specifications and Dimensions


This is the maximum number of associations between communication • Housing: plastic
objects and group addresses the device is able to memorize. • Dimensions: (W x H x D):: 70 x 90 x 58 mm
• Mounting width: 4 (1 SU=17,5mm)
Caution: there is a limit to the number of associations that can be created, on • Weight: ca. 200 g.
the same device, between transmission communications objects (i.e. inputs) • Installation: On 35mm mounting DIN rail (EN 60715)
and receiving communication objects (i.e. outputs)
If you want, on the same device, add a group address linked to a transmission Electrical Safety
communication object (input) to a receiving communication object (output) • Pollution degree: 2 (according to IEC 60664-1)
which already has a different group address associated, please note that you • Protection class IP 20 (according to EN 60529):
can add a maximum of 13 group addresses of this kind for the whole device. • Safety Class III (according to IEC 61140)
• Over voltage category III (according to IEC 664-1)
• Bus: Safety extra low voltage - SELV
• Compliant to EN50491-3
Technical Specifications Electromagnetic compatibility
Power Supply Compliant to: EN50491-5-1, EN50491-5-2
• Via Bus EIB/KNX 21..32V DC CE Mark
• Current consumption ≤ 10 mA In accordance with the EMC and low voltage guidelines

Outputs
• 16 A cos φ 1 - 230 Vac
• 8 A cos φ 0.6 - 230 Vac
• Minimum switching current: 10mA

Resistive loads: max 16 A Mmmm


Incandescent lamps: max 10 A
Motors e motor reduction units: max 10 A
Fluorescent lamps with electronic transformer: max 4A
Fluorescent lamps (max 140 μF) max 3A (700W)

Environmental specifications
• According to EN 50090-2.2
• Operative temperature: 0°C + 45°C
• Storage temperature: -20 + 55°C
• Relative Humidity (not condensing): max 90 %

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 12


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Module 4 Output
cod. 0KD040021

SCREW TERMINALS: Disposal


1 COM OUT 1
2 OUT 1 NO contact relay 1
3 COM OUT 2
4 OUT2 NO contact relay 2
5 COM OUT 3 The crossed-out bin symbol on the equipment or packaging means the
6 OUT3 NO contact relay 3 product must not be included with other general waste at the end of its
7 COM OUT 4 working life.
8 OUT4 NO contact relay 4 The user must take the warn product to a sorted waste center, or return
it to the retailer when purchasing a new one. An efficient sorted waste
PROGRAMMING: collection for the environmentally friendly disposal of the used device,
23 ETS programming led or its subsequent recycling, helps avoid the potential negative effects on
24 ETS programming switch the environment and people’s health, and encourages the re-use and/or
recycling of the construction materials.

Output Configuration for Shutter

Output Configuration for Motor Reduction Driver

Installation Instructions
Device must be used for permanent indoor installations in dry locations
within distribution boards or wall boxes.
• The prevailing safety rules must be heeded.
• Device must be mounted and commissioned by an authorised installer.
• The applicable safety and accident prevention regulations must be
observed.
• The device must not be opened. Any faulty devices should be returned to
manufacturer.
• For planning and construction of electric installations, relevant guidelines
and regulations of the respective country are to be considered.
• Relays are always switched opened before delivering but , it is
possible during transportation, they get closed. It is recommended,
when device is installed, to connect and supply the bus before the load
voltage to ensure the opening of the contacts
• Before configuring the device using ETS, the output channels are
configured for shutter management in order to avoid improper control
of this type of load. Frontal button are configured to switch the relay
with logical interlock.

Mounting and Wiring hints


General Description
The device configuration (KNX physical address assignment) is done
by pressing the programming push button located on the front of the
housing.

Connecting bus cables


Connect each single KNX/EIB bus core inside the terminal block observing
bus polarity; slip the bus connection into the guide slot placed on the front
side of this device and press the block down to the stop.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 13


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Module 8 Output with Manual Control
cod. 0KD080020

Descrizione del prodotto e del suo funzionamento


0KD080020 is a Din Rail 8 output 16 A - 230 V AC actuator and can be used
to:
• Control up to 8 independent loads / lights
• Control up to 4 independent blind / roller shutters withmechanical end
position

Device is intended to be installed on DIN rail.

Application Program ETS


Maximum number of group addresses: 53
This is the maximum number of different group addresses the device Terminal and connections
is able to store.
Maximum number of associations: 60 SCREW TERMINALS:
1. COM OUT 1
This is the maximum number of associations between communication
2. OUT 1 contact relay 1
objects and group addresses the device is able to store. 3. COM OUT 2
Caution: there is a limit to the number of associations that can be 4. OUT2 contact relay 2
created, on the same device, between transmission communications 5. COM OUT 3
objects (i.e. output feedback) and receiving communication 6. OUT3 contact relay 3
objects (i.e. outputs). 7. COM OUT 4
If you want, on the same device, add a group address linked to 8. OUT4 contact relay 4
9. COM OUT 5
a transmission communication object (feedback) to a receiving
10. OUT3 contact relay 5
communication object (output) which already has a different group 11. COM OUT 6
address associated, please note that you can add a maximum of 7 12. OUT3 contact relay 6
group addresses of this kind for the whole device. 13. COM OUT 7
14. OUT3 contact relay 7
15. COM OUT 8
16. OUT3 contact relay 8
Technical Specifications PROGRAMMING:
30. ETS programming led
Power Supply 31. ETS programming switch
• Via bus EIB/KNX cable 21..32V DC
• Current consumption ≤ 10 mA
• Max Current consumption during switching (30 ms): 14mA Output Configuration for Shutter
Outputs
• 16 A cos φ 1 - 230 V AC
• 8 A cos φ 0.6 - 230 V AC
• Minimum switching current: 10mA
Pure resistive loads: max 16 A
Incandescent lamps: max 10 A
Motors e motor reduction: max 10 A
Fluorescent lamps with electronic transformer: max 4 A
Fluorescent lamps: (max 140 μF) max 3A (700W)
Physical specifications and Dimensions
Installation Instructions
• Plastic enclosure: PA6
• Dimensions: (W xH x D): 90 x 71 x 58 mm WARNING: Device must be installed keeping a minimum distance of 4mm
• Weight: ca: 200 g between electrical power line (mains - 230V) and red / black bus connector or bus
• Installation: Din Rail cable.
• Din rail width: 4 modules • Device may be used for indoor installations in dry locations.
• Device must be mounted by an authorised installer.
Electrical Safety
• Device must be installed in a location that is accessible only to qualified
• Degree of pollution (IEC 60664-1): 2
installers.
• Degree of protection (EN 60529): IP 20 • The applicable safety and accident prevention regulations must be observed.
• Protection class (according to IEC 1140): III • Device must not be opened. Any faulty device should be returned to
• Overvoltage class (according to IEC 664-1): III manufacturer.
• Bus: safety voltage SELV • For planning and construction of electric installations, the relevant guidelines,
• Meets EN 50491-3 regulations and standards of the respective country are to be considered.
Electromagnetic compatibility • KNX bus allows you to remotely send commands to the system actuators.
Compliant with EN 50491-5-1 and EN 50491-5-2 Always make sure that the execution of remote commands do not lead to
Environmental specifications hazardous situations, and that the user always has a warning about which
• According to EN 50491-2 commands can be activated remotely.
• Ambient temperature during operation: 0°C + 45°C • Relays are always switched opened before delivering but , it is possible
• Storage temperature: - 20 °C + 55 °C during transportation, they get closed. It is recommended, when device is
• Relative humidity: max 90 % installed, to connect and supply the bus before the load voltage to ensure the
opening of the contacts
• Before configuring the device using ETS, the output channels are configured
CE Mark
for shutter management in order to avoid improper control of this type of
In accordance with the EMC and low voltage guidelines
load. Frontal button are configured to switch the relay with logical interlock.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 14


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Module 8 Output
cod. 0KD080021

Product and Applications description Wiring Diagram

The DIN RAIL 8 Output Module 0KD080021 is an EIB/KNX DIN rail mounting
device useful to interface commands (e.g. push buttons) or loads (e.g.
lamps) for any kind of applications.
Device 8 outputs on board can be configured:
• Each output can be configured independently for load control (R1 to R8)
• Each output can be configured independently for ON / OFF or continuous
switching (PWM) for Electric valves (solenoid actuators) (EV1 to EV8)
• Outputs can be configured in pairs for the management of roller shutters
and blinds; up to 4 channels (Channels A to D)
• Outputs can be configured in pairs for management of Motor Reductor
or for solenoid valves with 3-point control or for ventilating grille; up to 4
channels (Channels A to D)
• Fan Coil Actuator for 2/4 pipes systems for Heating / Cooling with 3 speed
motors) (uses relay from 1 to 5)
Device is intended to be installed on DIN rail.

Application Program
Physical specifications and Dimensions
Maximum number of group addresses: 50
• Housing: plastic
This is the maximum number of different group addresses the device is
• Dimensions: (W x H x D):: 70 x 90 x 58 mm
able to memorize.
• Mounting width: 4 (1 SU=17,5mm)
• Weight: ca. 200 g.
Maximum number of associations: 63
• Installation: On 35mm mounting DIN rail (EN 60715)
This is the maximum number of associations between communication
objects and group addresses the device is able to memorize.
Electrical Safety
• Pollution degree: 2 (according to IEC 60664-1)
Caution: there is a limit to the number of associations that can be created,
• Protection class IP 20 (according to EN 60529):
on the same device, between transmission communications objects (i.e.
• Safety Class III (according to IEC 61140)
inputs) and receiving communication objects (i.e. outputs)
• Over voltage category III (according to IEC 664-1)
If you want, on the same device, add a group address linked to a
• Bus: Safety extra low voltage - SELV
transmission communication object (input) to a receiving communication
• Compliant to EN50491-3
object (output) which already has a different group address associated,
please note that you can add a maximum of 13 group addresses of this
Electromagnetic compatibility
kind for the whole device.
Compliant to: EN50491-5-1, EN50491-5-2
CE Mark
In accordance with the EMC and low voltage guidelines
Technical Specifications
Terminals and connections
Power Supply
• Via Bus EIB/KNX 21.32V DC
• Current consumption ≤ 10 mA

Outputs
• 16 A cos φ 1 - 230 Vac
• 8 A cos φ 0.6 - 230 Vac
• Minimum switching current: 10mA

Resistive loads: max 16 A Mmmm


Incandescent lamps: max 10 A
Motors e motor reduction units: max 10 A
Fluorescent lamps with electronic transformer: max 4A
Fluorescent lamps (max 140 μF) max 3A (700W)

Environmental specifications
• According to EN 50090-2.2
• Operative temperature: 0°C + 45°C
• Storage temperature: -20 + 55°C
• Relative Humidity (not condensing): max 90 %

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 15


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Module 8 Output
cod. 0KD080021

SCREW TERMINALS: Installation Instructions


1 COM OUT 1
2 OUT 1 NO contact relay 1 Device must be used for permanent indoor installations in dry locations
3 COM OUT 2 within distribution boards or wall boxes.
4 OUT2 NO contact relay 2 • The prevailing safety rules must be heeded.
5 COM OUT 3 • Device must be mounted and commissioned by an authorised installer.
6 OUT3 NO contact relay 3 • The applicable safety and accident prevention regulations must be
7 COM OUT 4 observed.
8 OUT4 NO contact relay 4 • The device must not be opened. Any faulty devices should be returned to
9 COM OUT 5 manufacturer.
10 OUT 5 NO contact relay 5 • For planning and construction of electric installations, relevant guidelines
11 COM OUT 6 and regulations of the respective country are to be considered.
12 OUT 6 NO contact relay 6 • Relays are always switched opened before delivering but , it is
13 COM OUT 7 possible during transportation, they get closed. It is recommended,
14 OUT 7 NO contact relay 7 when device is installed, to connect and supply the bus before the load
15 COM OUT 8 voltage to ensure the opening of the contacts
16 OUT 8 NO contact relay 8 • Before configuring the device using ETS, the output channels are
configured for shutter management in order to avoid improper control
PROGRAMMING: of this type of load. Frontal button are configured to switch the relay
30 ETS programming led with logical interlock.
31 ETS programming switch

Output Configuration for Shutter Mounting and Wiring hints


General Description
The device configuration (KNX physical address assignment) is done
by pressing the programming push button located on the front of the
housing.

Connecting bus cables


Connect each single KNX/EIB bus core inside the terminal block observing
bus polarity; slip the bus connection into the guide slot placed on the front
Output Configuration for Motor Reduction Driver side of this device and press the block down to the stop.

Disposal

The crossed-out bin symbol on the equipment or packaging means the


product must not be included with other general waste at the end of its
Output Configuration for Fan Coil Actuator working life.
The user must take the warn product to a sorted waste center, or return
it to the retailer when purchasing a new one. An efficient sorted waste
collection for the environmentally friendly disposal of the used device,
or its subsequent recycling, helps avoid the potential negative effects on
the environment and people’s health, and encourages the re-use and/or
recycling of the construction materials.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 16


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Module 12 Output with Manual Control
cod. 0KD120020

Product and Applications description • Minimum switching current: 10mA


Pure resistive loads: max 16 A
0KD120020 is a Din Rail 12 output 16 A - 230 V AC actuator and can be used Incandescent lamps: max 10 A
to: Motors e motor reduction: max 10 A
• Control up to 12 independent loads / lights Fluorescent lamps with electronic transformer: max 4 A
• Control up to 6 independent blind / roller shutters with Fluorescent lamps: (max 140 μF) max 3A (700W)
mechanical end position Physical specifications and Dimensions
• Plastic enclosure: PPO
Device is intended to be installed on DIN rail. • Dimensions: (W xH x D): 90 x 159 x 58 mm
• Weight: ca: 350 g
ETS Application Program • Installation: Din Rail
• Din rail width: 9 modules
Maximum number of group addresses: 53 Electrical Safety
This is the maximum number of different group addresses the device • Degree of pollution (IEC 60664-1): 2
is able to store. • Degree of protection (EN 60529): IP 20
Maximum number of associations: 60 • Protection class (according to IEC 1140): III
This is the maximum number of associations between communication • Overvoltage class (according to IEC 664-1): III
objects and group addresses the device is able to memorize. • Bus: safety voltage SELV
Caution: there is a limit to the number of associations that can be • Meets EN 50491-3
created, on the same device, between transmission communications Electromagnetic compatibility
objects (i.e. output feedback) and receiving communication Compliant with EN 50491-5-1 and EN 50491-5-2
objects (i.e. outputs). Environmental specifications
If you want, on the same device, add a group address linked to • According to EN 50491-2
a transmission communication object (feedback) to a receiving • Ambient temperature during operation: 0°C + 45°C
communication object (output) which already has a different group • Storage temperature: - 20 °C + 55 °C
address associated, please note that you can add a maximum of 7 • Relative humidity: max 90 %
group addresses of this kind for the whole device.
CE Mark
According to EMC guideline
and low voltage directive

Installation Instructions
WARNING: Device must be installed keeping a minimum distance of 4mm
between electrical power line (mains - 230V) and red / black bus connector or bus
cable.
• Device may be used for indoor installations in dry locations.
• Device must be mounted by an authorised installer.
• Device must be installed in a location that is accessible only to qualified
installers.
• The applicable safety and accident prevention regulations must be observed.
• Device must not be opened. Any faulty device should be returned to
manufacturer.
• For planning and construction of electric installations, the relevant guidelines,
regulations and standards of the respective country are to be considered.
• KNX bus allows you to remotely send commands to the system actuators.
Always make sure that the execution of remote commands do not lead to
Technical Specifications hazardous situations, and that the user always has a warning about which
Power Supply commands can be activated remotely.
• Relays are always switched opened before delivering but , it is possible
• Via bus EIB/KNX cable 21..32V DC
during transportation, they get closed. It is recommended, when device is
• Current consumption ≤ 10 mA installed, to connect and supply the bus before the load voltage to ensure the
• Max Current consumption during switching (30 ms): 15mA opening of the contacts
Outputs • Before configuring the device using ETS, the output channels are configured
• 16 A cos φ 1 - 230 V AC for shutter management in order to avoid improper control of this type of
• 8 A cos φ 0.6 - 230 V A load. Frontal button are configured to switch the relay with logical interlock.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 17


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module 4 Input / 4 Output
cod. 0KD040030

Product and Applications description Wiring diagram

The DIN RAIL 4 Input / 4 Output Module 0KD040030 is an EIB/KNX DIN rail
mounting device useful to interface commands (e.g. push buttons) or loads
(e.g. lamps) for any kind of applications.
The device is equipped with 4 binary inputs (potential free) and 4 binary
relay outputs suitable for capacitive loads.
Inputs can be connected to conventional switching devices, e.g. push
buttons, switches, floating contacts, for switching functions with pulse
edge evaluation (e.g. rising or falling edge, toggle, etc...). Inputs can be
configured with ETS SW, as output channels to drive LED in synoptic
monitoring panels.
Inputs can be used to for on/off commands, dimming, shutter control,
scene recall and control; outputs include switching function, scene recall
and control logic function.
Outputs can act as interlocked channels; this function can be
used to drive fan coils with 2-pipe / 3 speed or 4-pipe / 2 speed.
Device is intended to be installed on DIN rail.
The device configuration for commissioning in terms of physical address,
group addresses and parameters is done with ETS (Engineering Tool
Software) through a download of the Application Program.

Technical Specifications
Power Supply
• Via Bus EIB/KNX
Physical specifications and Dimensions
• Current consumption < 15 mA
• Housing: plastic
• Dimensions: (W x H x D):: 70 x 90 x 58 mm
Inputs
• Mounting width: 4 (1 SU=17,5mm)
• 4 potential free contacts (dry contacts only)
• Weight: ca. 180 g.
• Input signal current at close contact = 0,5mA per channel
Installation: On 35mm mounting DIN rail (EN 60715)
• Maximum cable leght: 30m

Channels used as input


• Signal voltage Vn - 12 V DC (internally generated)

Channels used as output (for LED output)


• Input signal current = 0,5mA per channel

Outputs
• Number: 4 relays
16 A cos φ 1 - 230 Vac
8 A cos φ 0.6 - 230 Vac

Resistive loads: max 16 A Mmmm Electrical Safety


Incandescent lamps: max 10 A • Pollution degree: 2 (according to IEC 60664-1)
Motors e motor reduction units: max 10 A • Protection class IP 20 (according to EN 60529):
Fluorescent lamps: max 2 A • Safety Class III (according to IEC 61140)
Fluorescent lamps electronic transf.: max 6 A • Over voltage category III (according to IEC 664-1)
Fluorescent lamps: (max 140 μF) max 3 A (700W) • Bus: Safety extra low voltage - SELV
• Compliant to EN 50090-2-2

Electromagnetic compatibility
Compliant to: EN 50081-1, EN 50082-2 e EN 50090-2.2

Environmental specifications
• According to EN 50090-2.2
• Operative temperature: 0°C + 45°C
• Storage temperature: - 20 + 55 °C
• Relative Humidity: max 90 % not condensing

CE Mark
In accordance with the EMC and low voltage guidelines

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 18


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module 4 Input / 4 Output
cod. 0KD040030

Terminals and connections Mounting and Wiring hints

General Description
The device configuration (KNX physical address assignment) is done by
pressing the programming push button (24) located on the front of the
housing.

Connecting bus cables


• Connect each single KNX/EIB bus core inside the terminal
block observing bus polarity.
• Slip the bus connection block into the guide slot placed on the front side
of this device and press the block down to the stop.

Mounting DIN-rail devices (see next figure)


• Slide the device (B1) onto the DIN-rail (B2) and swivel back the device until
the slide clicks into the rail firmly.

Dismounting DIN-rail devices (see next figure)


SCREW TERMINALS: • Press down the slide (C3) with a screw-driver, click it into place by a slight
1 COM OUT 1 pressure and swivel the device (C1) from the DIN-rail (C2).
2 OUT 1 NO contact relay 1
3 COM OUT 2
4 OUT2 NO contact relay 2
5 COM OUT 3
6 OUT3 NO contact relay 3
7 COM OUT 4
8 OUT4 NO contact relay 4

17. IN 1 free potential contact or output led 1


18. IN 2 free potential contact or output led 2
19. COM1/2 common for inputs or outputs 1 and 2
20. IN 3 free potential contact or output led 3
21. IN 4 free potential contact or output led 4
22. COM3/4 common for inputs or outputs 3 and 4

Bus terminal connector block :


- Negative - Black
+ Positive - Red

Programming:
23 ETS programming led
24 ETS programming switch

Installation Instructions
Device must be used for permanent indoor installations in
dry locations within distribution boards or wall boxes.

WARNING
• The prevailing safety rules must be heeded.
• Device must be mounted and commissioned by an authorised
installer.
• The applicable safety and accident prevention regulations must be
observed.
• The device must not be opened. Any faulty devices should be returned to
manufacturer.
• For planning and construction of electric installations, the relevant
guidelines, regulations and standards of the respective country are to be
considered.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 19


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal DIN rail Module 4 inputs / outputs
cod. 0KD040031

Resistive loads: max 16A


Product and Applications description
Incandescent lamps: max 10 A
The DIN RAIL 4 Input / 4 Output Module 0KDO40031 is an EIB/KNX DIN rail Motors e motor reduction units: max 10 A
mounting device useful to interface commands (e.g. push buttons) or loads Fluorescent lamps with electronic transformer: max 6 A
(e.g. lamps) for any kind of applications. Fluorescent lamps (max 140 μF) max 3A (700W)
The device is equipped with 4 binary inputs (potential free) and 8 binary
relay outputs 16A-230V AC. Inputs can be connected to conventional Output configuration for shutter
switching devices, e.g. push buttons, switches, floating contacts, for
switching functions with pulse edge evaluation (e.g. rising or falling edge,
toggle...). Inputs can be configured with ETS SW as output to drive Leds.
Inputs can be used for on/off commands, dimming, shutter control, scene
recall and control; outputs include switching function, scene recall and
control logic function.
Device 4 outputs on board can be configured:
• Each output can be configured independently for load control (OUT 1 ÷ 4)
• Each output can be configured independently for ON / OFF or continuous
switching (PWM) for Electric valves (solenoid actuators) (OUT 1 ÷ 4) Output configuration for Motor Reduction Driver
• Outputs can be configured in pairs for the management of roller shutters
and blinds; up to 2 channels (Channels A ÷ B)
• Outputs can be configured coupled for management of Motor Reductor
or for solenoid valves with 3 point control or for ventilating grille; up to 2
channels (Channels A ÷ B)

Device is intended to be installed on DIN rail in cabinet for low voltage


distribution.
Physical specifications and Dimensions
Application Program ETS • Plastic enclosure: PA6
• Dimensions: (W x H x D): 71 x 90 x 58 mm
Maximum number of group addresses: 50
• Weight: ca. 340 g
This is the maximum number of different group addresses the device is
• Installation: DIN rail / 4 Modules
able to store.
Maximum number of associations: 63
Electrical Safety
This is the maximum number of associations between communication
• Pollution degree: 2 (according to IEC 60664-1)
objects and group addresses the device is able to store.
• Protection class IP 20 (according to EN 60529):
• Safety Class III (according to IEC 61140)
Caution: there is a limit to the number of associations that can be created,
• Over voltage category III (according to IEC 664-1)
on the same device, between transmission communications objects (i.e.
• Bus: Safety extra low voltage SELV
inputs) and receiving communication objects (i.e. outputs).
• Compliant to EN50491-3
If you want, on the same device, add a group address linked to a
transmission communication object (input) to a receiving communication
Electromagnetic compatibility
object (output) which already has a different group address associated,
Compliant to: EN50491-5-1, EN50491-5-2
please note that you can add a maximum of 13 group addresses of this
kind for the whole device.
Environmental specifications
• According to EN 50090-2.2
Technical Specifications • Operative temperature: 0°C + 45°C
Power Supply • Storage temperature: - 20 °C + 55 °C
• Via bus EIB/KNX 21..32V DC • Relative Humidity (not condensing): max 90 %
• Current consumption ≤ 10 mA
CE Mark
Input In accordance with the EMC and low voltage guidelines
• Number: 4 potential free contacts or led output
• Maximum cable lenght: ≤ 20m

Channels used as input


• Reading voltage: 3,3 V DC

Channels used as output (for LED output)


• Max. current < 0,5mA per channel

Outputs
• 16 A cos φ 1 - 230 V AC
• 8 A cos φ 0.6 - 230 V AC
• Minimum switching current: 10mA

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 20


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal DIN rail Module 4 inputs / outputs
cod. 0KD040031

Terminals and connections


SCREW TERMINALS:
1. COM OUT 1
2. OUT 1 contact relay 1
3. COM OUT 2
4. OUT2 contact relay 2
5. COM OUT 3
6. OUT3 contact relay 3
7. COM OUT 4
8. OUT4 contact relay 4
17. IN 1 free potential contact or output led 1
18. IN 2 free potential contact or output led 2
19. COM1/2 common for inputs or outputs 1 / 2
20. IN 3 free potential contact or output led 3
21. IN 4 free potential contact or output led 4
22. COM3/4 common for inputs or outputs 3 / 4
29. Bus terminal connector block:
Negative = Black / Positive = Red

PROGRAMMING:
30. ETS programming led
(30) LED KNX 31. ETS programming button

Installation Instructions
Device must be installed keeping a minimum distance of 4 mm between
electrical power line (mains 230V) and red/black bus connector or bus
cable
• Device may be used for indoor installations in dry locations.
• Device must be mounted by an authorised installer.
• Device must be installed in a location that is accessible only to qualified
installers.
• The applicable safety and accident prevention regulations must be
observed.
• Device must not be opened. Any faulty device should be returned to
manufacturer.
• For planning and construction of electric installations, the relevant
guidelines, regulations and standards of the respective country are to be
considered.
• KNX bus allows you to remotely send commands to the system actuators.
Always make sure that the execution of remote commands do not lead to
hazardous situations, and that the user always has a warning about which
commands can be activated remotely.
• Relays are always switched opened before delivering but , it is possible
during transportation, they get closed. It is recommended, when device is
installed, to connect and supply the bus before the load voltage to
ensure the opening of the contacts.

Disposal

The crossed-out bin symbol on the equipment or packaging means the


product must not be included with other general waste at the end of its
working life.
The user must take the warn product to a sorted waste center, or return
it to the retailer when purchasing a new one. An efficient sorted waste
collection for the environmentally friendly disposal of the used device,
or its subsequent recycling, helps avoid the potential negative effects on
the environment and people’s health, and encourages the re-use and/or
recycling of the construction materials.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 21


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Din Module 8 Input / 8 Output Module with Manual Control
cod. 0KD080030

Product and Applications description Wiring diagram


The DIN RAIL 8 Input / 8 Output Module 0KD080030 is an EIB/KNX DIN rail
mounting device useful to interface commands (e.g. push buttons) or loads
(e.g. lamps) for any kind of applications.
The device is equipped with 8 binary inputs (potential free) and 8 binary
relay outputs.
Inputs can be connected to conventional switching devices, e.g. push
buttons, switches, floating contacts, for switching functions with pulse
edge evaluation (e.g. rising or falling edge, toggle, etc...). Inputs can be
configured with ETS SW, as output channels to drive LEDs in synoptic
monitoring panels.
Inputs can be used to for on/off commands, dimming, shutter control,
scene recall and control; outputs include switching function, scene recall
and control logic function. Relay from 5 to 8 are equipped with tab and can
be switched manually.
Device is intended to be installed on DIN rail.
The device configuration for commissioning in terms of physical
address, group addresses and parameters is done with ETS (Engineering
Tool Software) through a download of the Application Program.

Application Program
Maximum number of group addresses: 44
This is the maximum number of different group addresses the device is
able to memorize.
Maximum number of associations: 69 Physical specifications and Dimensions
This is the maximum number of associations between communication • Housing: plastic
objects and group addresses the device is able to memorize. • Dimensions: (W x H x D):: 70 x 90 x 58 mm
Caution: there is a limit to the number of associations that can be created, • Mounting width: 4 (1 SU=17,5mm)
on the same device, between transmission communications objects (i.e. • Weight: ca. 200 g.
inputs) and receiving communication objects (i.e. outputs) Installation: On 35mm mounting DIN rail (EN 60715)
If you want, on the same device, add a group address linked to a
transmission communication object (input) to a receiving communication
object (output) which already has a different group address associated,
please note that you can add a maximum of 20 group addresses of this
kind for the whole device.

Technical Specifications
Power Supply
• Via Bus EIB/KNX
• Current consumption < 15 mA

Inputs
• Number: 8 potential free contacts Electrical Safety
• Input signal current at close contact = 0,5mA per channel • Pollution degree: 2 (according to IEC 60664-1)
• Maximum cable leght: 30m • Protection class IP 20 (according to EN 60529):
• Safety Class III (according to IEC 61140)
Channels used as input • Over voltage category III (according to IEC 664-1)
• Signal voltage Vn - 12 V DC (internally generated) • Bus: Safety extra low voltage - SELV
• Compliant to EN 50090-2-2
Channels used as output (for LED output)
• Input signal current = 0,5mA per channel Electromagnetic compatibility
Compliant to: EN 50081-1, EN 50082-2 e EN 50090-2.2
Outputs
• Number: 8 relays Environmental specifications
16 A cos φ 1 - 230 Vac • According to EN 50090-2.2
8 A cos φ 0.6 - 230 Vac • Operative temperature: 0°C + 45°C
• Storage temperature: - 20 + 55 °C
Resistive loads: max 16 A Mmmm • Relative Humidity: max 90 % not condensing
Incandescent lamps: max 10 A
Motors e motor reduction units: max 10 A CE Mark
Fluorescent lamps electronic transf.: max 6 A In accordance with the EMC and low voltage guidelines
Fluorescent lamps: (max 140 μF) max 3 A (700W)

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 22


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Din Module 8 Input / 8 Output Module with Manual Control
cod. 0KD080030

Terminals and connections Installation Instructions


Device must be used for permanent indoor installations in
dry locations within distribution boards or wall boxes.

WARNING
• The prevailing safety rules must be heeded.
• Device must be mounted and commissioned by an authorised
installer.
• The applicable safety and accident prevention regulations must be
observed.
• The device must not be opened. Any faulty devices should be returned to
manufacturer.
• For planning and construction of electric installations, the relevant
guidelines, regulations and standards of the respective country are to be
considered.

Mounting and Wiring hints


General Description
The device configuration (KNX physical address assignment) is done by
pressing the programming push button (24) located on the front of the
housing.

Connecting bus cables


• Connect each single KNX/EIB bus core inside the terminal
block observing bus polarity.
• Slip the bus connection block into the guide slot placed on the front side
of this device and press the block down to the stop.
Screw Terminals:
1. COM OUT 1 Mounting DIN-rail devices (see next figure)
2. OUT 1 NA contact relay 1 • Slide the device (B1) onto the DIN-rail (B2) and swivel back the device until
3. COM OUT 2 the slide clicks into the rail firmly.
4. OUT2 NA contact relay 2
5. COM OUT 3 Dismounting DIN-rail devices (see next figure)
6. OUT3 NA contact relay 3 • Press down the slide (C3) with a screw-driver, click it into place by a slight
7. COM OUT 4 pressure and swivel the device (C1) from the DIN-rail (C2).
8. OUT4 NA contact relay 4
9. COM OUT 5
10. OUT 5 NA contact relay 5
11. COM OUT 6
12. OUT 6 NA contact relay 6
13. COM OUT 7
14. OUT 7 NA contact relay 7
15. COM OUT 8
16. OUT 8 NA contact relay 8
17. IN 1 free potential contact or output led 1
18. IN 2 free potential contact or output led 2
19. COM1/2 common for inputs or outputs 1 and 2
20. IN 3 free potential contact or output led 3
21. IN 4 free potential contact or output led 4
22. COM3/4 common for inputs or outputs 3 and 4
23. IN 5 free potential contact or output led 5
24. IN 6 free potential contact or output led 6
25. COM5/6 common for inputs or outputs 5 and 6
26. IN 7 free potential contact or output led 7
27. IN 8 free potential contact or output led 8
28. COM7/8 common for inputs or outputs 7 and 8
Bus terminal connector block :
- Negative - Black
+ Positive - Red
Programming:
30. ETS programming led
31. ETS programming switch

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 23


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal DIN Module 8 Input / 8 Output
cod. 0KD080031

Product and Applications description Wiring Diagram


The DIN RAIL 8 Input / 8 Output Module 0KD080031 is an EIB/KNX DIN
rail mounting device useful tointerface commands (e.g. push buttons) or
loads (e.g. lamps) for any kind of applications. The device is equipped with
8 binary inputs (potential free) and 8 binary relay outputs. Inputs can be
connected to conventional switching devices, e.g. push buttons, switches,
floating contacts, for switching functions with pulse edge evaluation (e.g.
rising or falling edge, toggle...). Inputs can be configured with ETS SW, as
output to drive Leds. Inputs can be used to for on/off commands, dimming,
shutter control, scene recall and control; outputs include switching
function, scene recall and control logic function.
Device 8 outputs on board can be configured:
• Each output can be configured independently for load control (R1 to R8)
• Each output can be configured independently for ON / OFF or continuous
switching (PWM) for Electric valves (solenoid actuators) (EV1 to EV8)
• Outputs can be configured in pairs for the management of roller shutters
and blinds; up to 4 channels (Channels A to D)
• Outputs can be configured in pairs for management of Motor Reductor
or for solenoid valves with 3-point control or for ventilating grille; up to 4
channels (Channels A to D)
• Fan Coil Actuator for 2/4 pipes systems for Heating / Cooling with 3 speed
motors) (uses relay from 1 to 5).
Device is intended to be installed on DIN rail.

Application Program Physical specifications and Dimensions


Maximum number of group addresses: 50 • Plastic enclosure: PA6
This is the maximum number of different group addresses the device is • Dimensions: (W x H x D): 71 x 90 x 58 mm
able to memorize. • Mounting width: 4 (1 SU=17,5mm)
Maximum number of associations: 63 • Weight: ca. 200 g
This is the maximum number of associations between • Installation: On 35mm mounting DIN rail (EN 60715)
communication objects and group addresses the device
is able to memorize. Electrical Safety
Caution: there is a limit to the number of associations that can be created, • Pollution degree: 2 (according to IEC 60664-1)
on the same device, between transmission communications objects (i.e. • Protection class IP 20 (according to EN 60529):
inputs) and receiving communication objects (i.e. outputs). • Safety Class III (according to IEC 61140)
If you want, on the same device, add a group address linked to a • Over voltage category III (according to IEC 664-1)
transmission communication object (input) to a receiving communication • Bus: Safety extra low voltage SELV
object (output) which already has a different group address associated, • Compliant to EN50491-3
please note that you can add a maximum of 13 group addresses of this
kind for the whole device. Electromagnetic compatibility
Compliant to: EN50491-5-1, EN50491-5-2
Technical Specifications
Environmental specifications
Power Supply • According to EN 50090-2.2
• Via Bus EIB/KNX • Operative temperature: 0°C + 45°C
• Current consumption ≤ 10 mA • Storage temperature: - 20 °C + 55 °C
• Relative Humidity (not condensing): max 90 %
Inputs
• Number: 8 potential free contacts CE Mark
• Input signal current at close contact = 0,5mA x ch. In accordance with the EMC and low voltage guidelines
• Maximum cable leght: ≤ 20m
Channels used as input
• Signal voltage Vn – 3,3 V DC
Channels used as output (for LED output)
• Input signal current < 0,5mA per channel

Outputs
• 16 A cos φ 1 - 230 Vac
• 8 A cos φ 0.6 - 230 Vac
• Minimum switching current: 10mA
Resistive loads: max 16 A Mmmm
Incandescent lamps: max 10 A
Motors e motor reduction units: max 10 A

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 24


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal DIN Module 8 Input / 8 Output
cod. 0KD080031

Terminals and connections Output Configuration for Shutter

Output Configuration for Motor Reduction Driver

Output Configuration for Fan Coil Actuator

Installation Instructions
Device must be installed keeping a minimum distance of 4 mm between
electrical power line (mains 230V) and red/black bus connector or bus
cable
• Device may be used for indoor installations in dry locations.
SCREW TERMINALS: • Device must be mounted by an authorised installer.
1. COM OUT 1 • Device must be installed in a location that is accessible only to qualified
2. OUT 1 contact relay 1 installers.
3. COM OUT 2 • The applicable safety and accident prevention regulations must be
4. OUT2 contact relay 2 observed.
5. COM OUT 3 • Device must not be opened. Any faulty device should be returned to
6. OUT3 contact relay 3 manufacturer.
7. COM OUT 4 • For planning and construction of electric installations, the relevant
8. OUT4 contact relay 4 guidelines, regulations and standards of the respective country are to be
9 COM OUT 5 considered.
10 OUT 5 NA contact relay 5 • KNX bus allows you to remotely send commands to the system actuators.
11 COM OUT 6 Always make sure that the execution of remote commands do not lead to
12 OUT 6 NA contact relay 6 hazardous situations, and that the user always has a warning about which
13 COM OUT 7 commands can be activated remotely.
14 OUT 7 NA contact relay 7 • Relays are always switched opened before delivering but , it is possible
15 COM OUT 8 during transportation, they get closed. It is recommended, when device is
16 OUT 8 NA contact relay 8 installed, to connect and supply the bus before the load voltage to
17. IN 1 free potential contact or output led 1 ensure the opening of the contacts.
18. IN 2 free potential contact or output led 2
19. COM1/2 common for inputs or outputs 1 / 2
20. IN 3 free potential contact or output led 3
Mounting and Wiring hints
21. IN 4 free potential contact or output led 4 General Description
22. COM3/4 common for inputs or outputs 3 / 4 The device configuration (KNX physical address assignment) is done by
29. Bus terminal connector block: pressing the programming push button located on the front of the housing.
Negative = Black / Positive = Red Connecting bus cables
Connect each single KNX/EIB bus core inside the terminal block observing
PROGRAMMING: bus polarity; slip the bus connection into the guide slot placed on the front
30 ETS programming led side of this device and press the block down to the stop.
31 ETS programming switch

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 25


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Inwall 3 Input / 2 Output Module (Relays 10A)
cod. 0KF030010

Product and Applications description Outputs


• 10 A cos φ 1 - 230 Vac
0KF030010 module includes: • 3 A for motors and motor reductors
• 2 digital inputs • Max capacitance @230V: 21μF 5.000 cycles
• 1 analog input • Incandescent lamps max load: 1500W 50.000 cycles
• 2 relay output (bistable) • Fluorescent lamps max load: 6 x18W 25.000 cycles
Digital inputs are intended to be connected to free potential contacts and • Halogen lamps max load: 500W 50.000 cycles
can interface sensors, traditional buttons, etc; they can be used to on/off • Gas discharge lamps max load: 200W 25.000 cycles
commands, dimming, shutter con-trol, scene recall and control, sequences
of 3 objects. Control Elements
Analog input, can manage one temperature probe (with On/Off threshold) • EIB/KNX Red LED and button
or one thermostats to control heating and cooling equipments, valves, 2
and 4 pipes fan coils; etc..
Analog input, alternatively to the temperature sensor, can manage a Mechanical Specifications
Infrared Receiver (IRX) in order to forward to the bus up to 8 channel
coming from a Infrared Remote Control (IRC) with on/off commands, • Case: plastic (Nylon)
scenes, sequences of 2 objects, dimmer and shutter. • Dimensions: (Diameter x Height.): 52 x 28 mm
Outputs include switching function with timed delays, stair-case function, • Weight: approx. 50 g
scene recall, lock or logic function.
• Each output can be configured independently for load control (2 Electrical Diagram
independent channels)
Device 2 outputs on board can be configured:
• Each output can be configured independently for ON / OFF or continuous
switching (PWM) for Electric valves (solenoid actuators) (2 independent
channels)
• Outputs can be configured in pairs for the management of roller shutters
and blinds; (1 channel)
The device is equipped with KNX communication interface.

Application Program

Maximum number of group addresses: 50


This is the maximum number of different group addresses the device is
able to memorize.
Maximum number of associations: 63
This is the maximum number of associations between communication
objects and group addresses the device is able to memorize.
Caution: each transmission object has usually associated a single group
address. If you want to associate to a transmission communication object
other addresses in addition to the first, please note that you can add a
maximum of 13 group addresses of this kind for the whole device.
Electrical Safety
• Degree of pollution (IEC 60664-1): 2
Technical Specifications
• Degree of protection (EN 60529): IP 00
Power Supply • Protection class (according to IEC 1140): III
• Via bus EIB/KNX cable • Overvoltage class (according to IEC 664-1): III
• Voltage 21..30V DC • Bus: safety voltage SELV DC 21…31 V dc
• Current Consumption EIB/KNX < 10mA • Meets EN 50491-3

Digital Input EMC Requirements


• For free potential contacts (dry contacts) • Complied with EN 50491-5-1 and EN 50491-5-2
• Max. length of Connecting Cable: ≤ 30 m (twisted cable)
• Voltage Scanning: 3,3 V DC (internally Generated) Terms of use
• AWG24 cables with 1800 mm length • According to 50491-2
• Ambient temperature during operation: -5 °C + 45 °C
Analog Input for temperature probe • Storage temperature: - 20 °C + 55 °C
• For NTC temperature probe eelectron code • Relative humidity: max 90%
• TS01A01ACC (range from -20°C to +100°C)
• TS01B01ACC (range from -50°C to +60°C) CE Mark
• Max. length of Connecting Cable: ≤ 20 m (twisted cable) According to EMC guideline and low voltage directive

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 26


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Inwall 3 Input / 2 Output Module (Relays 10A)
cod. 0KF030010

Terminals and connections

SCREW TERMINALS:
1. COM OUT 1
2. OUT 1 contact relay 1
3. COM OUT 2
4. OUT2 contact relay 2

Wired Connectors:
1. GREEN IN 1 free potential contact
2. BLACK COMMON IN 1 , IN 2
3. YELLOW IN 2 free potential contact
4. BLACK IN TEMPERATURE SENSOR
5. GREY IN TEMPERATURE SENSOR
6. -- NOT USED

Bus terminal:
Negative = Black / Positive = Red

Output Configuration for Shutter

Installation Instructions
The device may be used for permanent indoor installations in dry locations
within wall box mounts.

WARNING
• Device must be installed keeping a minimum distance of 4mm between
electrical power line (mains) and input ca-bles or red / black bus cable .
• The device must be installed in a location that is accessible only to
qualified installers
• The prevailing safety rules must be heeded.
• The device must be mounted by an authorised installer.
• The applicable safety and accident prevention regula-tions must be
observed.
• The device must not be opened. Any faulty devices should be returned to
manufacturer.
• For planning and construction of electric installations, the relevant
guidelines, regulations and standards of the re-spective country are to be
considered.
• KNX bus allows you to remotely send commands to the system actuators.
Always make sure that the execution of remote commands do not lead to
hazardous situations, and that the user always has a warning about which
commands can be activated remotely.

For temperature probes see page 13.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 27


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module Fancoil Controller Unit 0-10V
cod. 0KD010050

Product and Applications description • Weight: ca. 200 g


• Installation: DIN rail / 4 Modules
The Fan Coil Unit Controller is used to control fan coil units, floor heating Electrical Safety
or switch actuators. Depending on the design of the device, fan coil units • Pollution degree: 2 (according to IEC 60664-1)
are used in 2-pipe or 4-pipe• systems. It controls up to 3 fan speeds (Relay • Protection class IP 20 (according to EN 60529):
or 0-10V outputs) as well as heating or cooling valves (Proportional or • Safety Class III (according to IEC 61140)
electrothermal valve) respectively. The mode of control is based on two- • Over voltage category III (according to IEC 664-1)
step control or a time-discrete PI controller with setpoint/actual value • Bus: Safety extra low voltage SELV
comparison. The valves and the fan can be regulated directly by devices via • Compliant to EN50491-3
the closed loop of this controller. When the Fan Coil Unit Controller is used Electromagnetic compatibility
in floor heating, it can control up to seven channel. All of the floor heating Compliant to: EN50491-5-1, EN50491-5-2
channel control is used a time-discrete PI controller with setpoint / actual Environmental
value comparison. • According to EN 50090-2.2
The following functions can be set in different functions: • Operative temperature: 0°C + 45°C
1. Five channel 10A relay outputs • Storage temperature: - 20°C + 55°C
2. Two channel 0-10V DC outputs • Relative Humidity (not condensing): max 90 %
3. Fan speed: High, Medium, Low CE Mark
4. HVAC working mode: Heating, Cooling In accordance with the EMC and low voltage guidelines
5. HVAC op. mode: Standby, Comfort, Night, Frost protection
6. Fan speed and Valve status report
7. Seven local temperature sampling Terminal and connections
8. BUS temperature sampling
9. Local temperature report SCREW TERMINALS:
10. Seven channel floor heating outputs 1. Output 0-10V DC
11. Five control mode each floor heating channel 2. Input Temperature sensor
12. Seven channel output independently 3. KNX/EIB black/red terminal
13. Channel statistics total ON time 4. System Green LED
14. Channel state response 5. Output relays for heating and cooling valves or general purpose
15. Channel state after bus voltage failure and recovery 6. Output relays for Fan speed or general purpose
16. Staircase light PROGRAMMING:
17. Delay 7. ETS Programming Button and Red LED
18. PWM control output TEMPERATURE SENSOR:
Device is intended to be installed on DIN rail in cabinet for low voltage Order code: 0KD010050
distribution • DIGIT TEMP Yellow cable
• COM Red cable
• COM Black cable
Application Program ETS
Maximum number of group addresses: 254
This is the maximum number of different group addresses the device is able
to store. Installation Instructions
Maximum number of associations: 254 Device must be installed keeping a minimum distance of 4 mm between
This is the maximum number of associations between communication electrical power line (mains - 230V) and red / black bus connector or bus
objects and group addresses the device is able to store. cable
• Device may be used for indoor installations in dry locations.
• Device must be mounted by an authorized installer.
Technical Data • Device must be installed in a location that is accessible
• The applicable safety and accident prevention regulations must be
Power Supply observed.
• Via bus EIB/KNX 21..30V DC • Device must not be opened. Any faulty device should be returned to
• Dynamic current consumption < 20 mA manufacturer.
• Static current consumption < 5 mA • For planning and construction of electric installations, the relevant
Temperature Input guidelines, regulations and standards of the respective country are to be
• Local sensor digital sensor considered.
Max 7 sensors • KNX bus allows you to remotely send commands to the system actuators.
Max cable length 50m Always make sure that the execution of remote commands do not lead to
• Via KNX 1 or 2 group object hazardous situations, and that the user always has a warning about which
Outputs commands can be activated remotely.
• 5 relays outputs 10 A cos φ 1 - 230 V AC
• 2 analog ouputs 0-10V DC 10mA / channel
Connections
• EIB/KNX Bus Terminal
0.8 mm Ø, single core
• Load circuits Screw terminal slotted head
0.2...4 mm² multi- core
0.4...6 mm² single-core
Physical specifications and Dimensions
• Plastic enclosure: Flame-retarded nylon
• Dimensions: (W x H x D): 72 x 90 x 66 mm

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 28


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module Fancoil Controller Unit 0-10V
cod. 0KD010050

Disposal

The crossed-out bin symbol on the equipment or packaging means the product
must not be included with other general waste at the end of its working life.
The user must take the worn product to a sorted waste centre, or return it to the
retailer when purchasing a new one. An efficient sorted waste collection of the
environmentally friendly disposal of the used device, or its subsequent recycling,
helps avoid the potential negative effects on the environment and people’s health,
and encourages the re-use and/or recycling of the construction materials.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 29


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Single-phase Digital Energy meters - Direct connection 63A
cod. 0KD010M10

Product and Applications description Main Menu

• This Energy-meter provides the essential measurement capabilities


required to monitor a single phase electrical installation.
• 0.25-5 (63) A, Class B, 230 VAC 50 Hz, -25 °C ... +55 °C, 4 Quadrants, 2
Tariffs.
• Active Energy Class B (according to EN-50470) and Reactive Energy Class
2
• Direct connected (up to 63 A)
• LCD display and 3 push-button keys (to read Energies, V, I, PF, F, P, Q and
to configure some parameters)
• 1 push botton and 1 LED dedicated to KNX.
• Display with 8 digits.
• Self supplied (by the input voltage itself ).
Device is intended to be installed on DIN rail.

Display

Tariff 1-2 Energy Register List Instantaneous Measurement List

Energy value
kWh / kvarh display
Running tarif,called tarif
Energy export (received)
Energy import (delivered)
Energy value “Partial”
Push botton and LED dedicatet to KNX
Metrological LED

Commands
Energy Register Reset Procedure
Scroll Key: This key is used to scroll pages and to
modify parameters value. Its pushing is accepted
only if it is shorter than 1.5 second..
OK key: This key is used alone to enable a new menu
function or to confirm a parameter value during its
modification. Its pushing is accepted only if shorter
than 1.5 seconds
Diagnostic Message
ESC key: This key is used alone to exit from a sub-
Error Condition
menu, to cancel a parameter modification or to go
If the display shows these messages,
back to the main page. In these cases, its pushing is
the meters has got a malfunction and
accepted only <1.5 seconds
must be replaced.
A long pushing (>1.5 seconds) of the “ESC key” is
used in the Partial Energy Registers Pages to reset
their values. Wiring Diagram
A long pushing (>5 seconds) is used in the Main
Energy Registers Pages to reset their values

Device Switch-on and Main Page

Main Page:
This page appears not only at device switch on, but also in case for 30
seconds no key is pushed. The value is the sum of 2 registers:
Imported Act. Energy Tariff T1 + Imported Act. Energy Tariff T2. (or,
alternatively, the sum of the Exported ones).

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 30


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Single-phase Digital Energy meters - Direct connection 63A
cod. 0KD010M10

Technical Specifications According with EN 50470-1, EN 50470-3, EN 62053-23 e EN 62053-31

Disposal

The crossed-out bin symbol on the equipment or packaging means the product
must not be included with other general waste at the end of its working life.
The user must take the worn product to a sorted waste centre, or return it to the
retailer when purchasing a new one. An efficient sorted waste collection of the
environmentally friendly disposal of the used device, or its subsequent recycling,
helps avoid the potential negative effects on the environment and people’s health,
and encourages the re-use and/or recycling of the construction materials.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 31


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Three-phase Digital Energy meters - Direct connection 63A
cod. 0KD030M10

Product and Applications description Diagnostic messages


• This Energy-meter provides the essential measurement capabilities
One or more missing phase:
required to monitor a three phase electrical installation.
In case one or more phase is not detected,
• Direct connected (up to 63 A)
the correseponding icon disappears from
• LCD display and 3 push-button keys (to read Energies, V, I, PF, F, P, Q and to
the bottom row of the display. E.G. L2 is not
configure some parameters)
detected.
• 1 push botton and 1 LED dedicated to KNX.
Phase sequence error:
• Display with 8 digits.
When the three phases are not in the correct
• Self supplied (by the input voltage itself ).
zero-crossing sequence this message appears
and the icons L1 and L2 blink. To make this
Device is intended to be installed on DIN rail.
message to disappears, you can keep pushed
the “Menu key” for at least 4 seconds.
Display Error condition:
When the display shows the message “Error 2
Main Page: or Error 3”, the meter has got a malfunction and
The value of the currently growing Active must be replaced.
3-phase Energy is represented (or the ast one
that has grown). The Energy is always Active, KNX Application and Address programming
and may be Active Imported (right arrow),
Active Exported (left arrow), with Tariff T1 or T2, Once the metering equipment is installed, in order
depending on the current Energy flowing. to have KNX correctly working, the KNX application
(.WD4) and the address writing are required to be
Second Active Energy Page downloaded.

On the top right corner of the metering equipment


Third Active Energy Page front, there are a LED and a push button key
dedicated to the KNX address downloading.
When you turn on the metering equipment, the LED
Fourth Energy Page: should remain OFF. Also, if you push the KNX key
In the second, third and fourth pages the other 3 without connecting the KNX bus to the metering
energy registers are Represented equipment or if the KNX external interface is not
powered, the LED remains OFF.

Firmware Release Page: To prepare the KNX communication, proceed in the


You can read the index of firmware release. following way:
1) With the power supply totally disconnected,
connect both mains and KNX plug-in connector
Firmware CheckSum Page: 2) Turn on the metering equipment
The checksum is periodically calculated to verify 3) Launch the KNX programming tools in a personal
that the firmware is reliable. computer and connect the computer to the meter
by means of a KNX interface.
4) Select the operation (application downloading/
Display Test Page: address writing/application downloading & address
All the display segments are visible. writing)
Whichever the page on the display, if no key 5) If the selected operation involves the address
is pushed for at least 20 sec., the main page writing, push the KNX when required by the tool.
appears again. 6) The KNX LED will turn ON

Partial Counter

Partial Active Energy Counters: 7) Once the operation is completed,


By pushing the “Partial key” partial active energy counters are readable the LED will switch OFF
in the main,second, third and fourth pages (i.e. for monthly energy
consumption).

These counters are resettable, see the energy reset section. By pushing the
“Partial key” in any of the four pages, you go back to the Main menu

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 32


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Three-phase Digital Energy meters - Direct connection 63A
cod. 0KD030M10

Display Wiring Diagram

Energy Value

Running tarif

Energy line (L1-2-3)

Energy value „Partial“

Energy Import

Energy Export
Metrological LED

CT Indicator

Push - Buttons

KNX address writing

Command button for


“Partial” reading selection

Menu key for reading selection

Installation Instructions
Device must be installed keeping a minimum distance of 4 mm between
electrical power line (mains - 230V) and red / black bus connector or bus
cable
• Device may be used for indoor installations in dry locations.
• Device must be mounted by an authorized installer.
• Device must be installed in a location that is accessible
• The applicable safety and accident prevention regulations must be
observed.
• Device must not be opened. Any faulty device should be returned to
manufacturer.
• For planning and construction of electric installations, the relevant
guidelines, regulations and standards of the respective country are to be
considered.
• KNX bus allows you to remotely send commands to the system actuators.
Always make sure that the execution of remote commands do not lead to Dimension Sealable terminal covers
hazardous situations, and that the user always has a warning about which
commands can be activated remotely.

Energy Reset

In all pages representing an Energy value, a pressure


of 20 sec. of the “Menu key” allows to enter in the
zeroing menu, consequently on the display “see
image aside” appears. The key must be released.
In order to confirm the operation and get back to
default visualization, push it again for 4 seconds,
otherwise after 4 sec., the reset will have no effect.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 33


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Three-phase Digital Energy meters - TA connected
cod. 0KD030M20

Product and Applications description Diagnostic messages

This Energy-meter provides the essential measurement capabilities required One or more missing phase:
to monitor a three phase electrical installation. In case one or more phase is not detected,
three-phases digital energy meter with connection by CT .../1 A up to the correseponding icon disappears from
2000/1 A or by CT .../5 A up to 10.000/5 A 0.01-1(6) A 2 tariffs inbuilt KNX the bottom row of the display. E.G. L2 is not
communication 1 S0 pulse output proportional to Active Imported KWh detected.
Phase sequence error:
Device is intended to be installed on DIN rail. When the three phases are not in the correct
zero-crossing sequence this message appears
and the icons L1 and L2 blink. To make this
message to disappears, you can keep pushed
the “Menu key” for at least 4 seconds.
Error condition:
Main Menù
When the display shows the message “Error 2
Main Page: or Error 3”, the meter has got a malfunction and
The value of the currently growing Active must be replaced.
3-phase Energy is represented (or the ast one
that has grown). The Energy is always Active,
and may be Active Imported (right arrow), Pulse rate limit
Active Exported (left arrow), with Tariff T1 or T2,
depending on the current Energy flowing. Pulse output setting
The maximun number of pulses per kWh (Pulse constant) that the meter can
Second Active Energy Page generate through S0 ouputs is limited by the CT ratio and by the ON time of
the pulse.
The relationship is:
Third Active Energy Page

Fourth Energy Page:


In the second, third and fourth pages the other 3 For example, if in your installation you need a CT ratio of 1000/5 = 200 and a
energy registers are Represented ON pulse time of 70 ms, the maximum Pulse constant that you can select is:

Firmware Release Page:


You can read the index of firmware release.

You can always modify the CT ratio and the pulse ON time as you prefer; in
Firmware CheckSum Page: case the Pulse Constant is too high for your selections, it is automatically
The checksum is periodically calculated to verify adjusted to the maxmum allowed value.
that the firmware is reliable.

Display Test Page: Modifiable Parameters


All the display segments are visible. As above mentioned, the following parameters are modifiable:
Whichever the page on the display, if no key is CT Primary Winding and CT Secondary Winding, On-Time and Pulse costant.
pu For example, in the CT Primary Winding page:

Partial Counter

Partial Active Energy Counters:


By pushing the “Partial key” partial active energy counters are readable
in the main,second, third and fourth pages (i.e. for monthly energy Push Start, Down key to decrease,Up key to increase. Push the “Menu key” to
consumption). confirm, otherwise after 8 seconds the modification will be lost.

These counters are resettable, see the energy reset section. By pushing the
“Partial key” in any of the four pages, you go back to the Main menu

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 34


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Three-phase Digital Energy meters - TA connected
cod. 0KD030M20

KNX Application and Address programming Push - Buttons

Once the metering equipment is installed, in order


to have KNX correctly working, the KNX application KNX address writing
(.WD4) and the address writing are required to be
downloaded. Command button for
“Partial” reading selection
On the top right corner of the metering equipment
front, there are a LED and a push button key Menu key for reading selection
dedicated to the KNX address downloading.
When you turn on the metering equipment, the LED
should remain OFF. Also, if you push the KNX key
Energy Reset
without connecting the KNX bus to the metering
equipment or if the KNX external interface is not
powered, the LED remains OFF. In all pages representing an Energy value, a pressure
of 20 sec. of the “Menu key” allows to enter in the
To prepare the KNX communication, proceed in the zeroing menu, consequently on the display “see
following way: image aside” appears. The key must be released.
1) With the power supply totally disconnected, In order to confirm the operation and get back to
connect both mains and KNX plug-in connector default visualization, push it again for 4 seconds,
2) Turn on the metering equipment otherwise after 4 sec., the reset will have no effect.
3) Launch the KNX programming tools in a personal
computer and connect the computer to the meter
by means of a KNX interface.
4) Select the operation (application downloading/
address writing/application downloading & address Wiring Diagram
writing)
The Energy Meter has OVERVOLTAGE CATEGORY lll (according to IEC
5) If the selected operation involves the address
62052-31 that refers to IEC-60664-1 Ed. 2.0:2007), hence its direct
writing, push the KNX when required by the tool.
connection to the Public Electricity
6) The KNX LED will turn ON
Grid is not allowed. The Energy Meter is intended for INDOOR installation
only (according to EN 50470-1 and IEC 62052-31).
The Energy Meter must be installed on a DIN-rail and inside a cabinet with
a protection degree (IP rating) equal to (or better than) IP51.
7) Once the operation is completed,
Direct connection of currents inputs to the Energy Meter is NOT ALLOWED:
the LED will switch OFF
external CTs insertion with proper insulation level are mandatory.

Display

Energy Value

Running tarif

Energy line (L1-2-3)

Energy value „Partial“

Energy Import

Energy Export
Metrological LED

CT Indicator

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 35


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Three-phase Digital Energy meters - TA connected
cod. 0KD030M20

Alternative wiring diagram, with only 2 external CTs. Technical Data


To be used only under the following conditions:
In compliance with CLC/TR 50579 , EN 62059-32-1, EN 50470-1, EN 50470-3
• The load is 3 wires (no neutral) and there is no current leakage (l1 - l2 - l3
= 0)
• Only 3-phase measures (Σ Power and Energies) are meaningful.

(1) The connection of the Neutral Wire to the “N” terminal of the Energy
Meter is mandatory.
Its connection to the Load is optional, but, in the case, only 3-phase
measures (Powers and Energies) are meaningful, while measures referred
to L1, L2, and L3 are meaningless.
(2) These manual disconnect switches are mandatory for safe installing
operation. Their purpose and location must be easily evident to installation
personnel
(3) These fuses are not mandatory, they are recommended to protect the
line, not the device itself.
Use >= 6 A fast (F) or >= 1 A delayed (T).
(4) Earthing of secondary windings of CTs is governed by the laws in force
in the Countries where the device is installed.
Current transformers must not be operated with open terminals since
dangerous high voltages might occur which may result in personal injuries
and property damage; furthermore, in this case the transformers are
exposed to thermal overload.

Installation Instruction

WARNING
Device must be installed keeping a minimum distance of 4mm
between electrical power line (mains - 230V) and red / black bus
connector or bus cable. Dimension Sealable terminal covers
 Device may be used for indoor installations in dry locations.
 Device must be mounted by an authorised installer.
 Device must be installed in a location that is accessible only to qualified
installers
 The applicable safety and accident prevention regulations must be
observed.
 Device must not be opened. Any faulty device should be returned to
manufacturer.
 For planning and construction of electric installations, the relevant
guidelines, regulations and standards of the respective country are to be
considered.
 KNX bus allows you to remotely send commands to the system actuators.
Always make sure that the execution of remote commands do not lead to
hazardous situations, and that the user always has a warning about which
commands can be activated remotely.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 36


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
3 x 300W DIN Rail Dimmer Module
cod. 0KD030040

Product and Applications description Environmental specifications


The 3 channel Dimmer Module is designed to interface variable lighting • Operative temperature: -5°C ÷ + 45 °C
with bus KNX/EIB and allow dimming of incandes-cent loads low voltage LV • Storage temperature: -20°C ÷ + 70 °C
halogen (230 V), extralow voltage halogen (12V or 24V ELV) with electronic • Relative Humidity: max 90 %
or ferromagnetic
transformer, fluocompact dimmable light with builtin supply, dimmable 230 Physical specifications and Dimensions
V LED lamp with builtin supply, or very low voltage dimmable LED lamp (ELV • Dimensions 6 DIN modules
12 V or 24 V) with electronic transformer. • Weight: ca. 300 g.
This product is a universal dimmer with automatic load control and built- • Installation: DIN rail (EN 60715)
in teaching feature for more efficiently fluocompact and 230 V LED lamp
adjustment.
The product has also an “override” mode, which allows to select the desired
dimming mode.
The outputs number depends on switch 7 position.

Technical Specifications
Power supply from EIB/KNX bus
• Voltage 21..30V DC
• Current consumption from EIB/KNX < 2,3 mA

Power supply from mains:


• Voltage 230V ~ 50/60 Hz
• Consumption without load 0,7W
• Power dissipation 5,8W

Connections
EIB/KNX: 2 bus terminal 0,8mmØ 1. Switch auto / min / max / manual
2. Status led
Loads and power supply : 3. Local push button
4. Led indicator of overheating protection
5. Led indicator of overload protection / short circuit
Load type / rated output 6. ETS programming push button and led
7. Selector for output number configuration
8. Override dimming mode

Load teaching
Load teaching (product already connected to the mains and bus) allows
to detect load characteristics in order to control it more effectively (in
particular, CFL and LED lamps) :
• with a KNX push button configured for dimming, give 5 short presses (5
ON, 5 OFF or 5 ON/OFF) followed by a long press until the load switches off
• press the pushbutton shortly once to start the teaching procedure. This
operation lasts for about 30 s. and makes the lighting level vary.
After the process has ended, the load switches on to the maximum level
and flickers once to signal teaching completion.
Depending on the connected load, the minimum lighting level can be
modified.

Setting of the minimum and maximum dimming values


1. Set the min or max dimming value by acting either way:
• setting switch 1 in position “manual” and acting on push-button 3 (a
long pressure allows dimming until the desired lighting level is reached,
while a short pressure switches lighting on/off ). Set the switch into position
min or max as desired, or,
The efficiency of the transformer has to be taken into account to
• setting switch 1 in position min or max as desired and set the desired level
calculate the max. number of controlled lamps .
using a communication pushbutton connected to the output (need to
perform the configuration via ETS before)
Standards
2. Record the value set by pressing push-button 3 for more than 3 seconds.
• Protection class IP 30 (according to EN 60529):
Led 2 flicker twice to confirm the recording.
• Compliant to EN60950 and ETSI301 489-1 and 301 489-3
Note 1: If the minimal or maximum values are set out of range, led 2 will
• Safety Class II according EN 61140
flicker after the recording request.
• EIB / KNX
Note 2 : These limits can also be programmed via ETS.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 37


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
3 x 300W DIN Rail Dimmer Module
cod. 0KD030040

Test and start up


Switch auto / min / max / manual (1) and local control pushbuttons (3) When the switch is in this position the
When switch 1 is in position “manual”, pushbuttons 3 can be used dimmer manage only one load (C1)
to control output (a long pressure allows dimming until the desired with a maximum rated power of 900W
illumination level is reached, while a short pressure switches lighting on/
off ). When the switch is in this posi-tion
Use the position “auto” of switch 1 in operation mode or for configuring the dimmer manage two loads: the
the product. first (C1) with a max-imum rated
In position “auto” of switch 1, pushbutton 3 is inactive and the output is power of 600W, the second (C2) with a
controlled by telegrams received from bus KNX/EIB. maximum rated power of 300W.
Status led
Indicators 2 indicate the state of the corresponding outputs: indicator on = When the switch is in this position the
actuated load, indicator flashing for 5 s = no load connected. dimmer manage three loads: C1, C2,
ETS programming push button and led C3 everyone with a maximum rated
Press lighted pushbutton 6 to carry out the physical addressing of the power of 300W.
product or to check bus presence: indicator on = the bus is present and the
product is in physical addressing state.
Protection against overheating, overload and short-circuit
Mounting and Wiring hints
Indicator 4 indicates an overheating condition when switched on in a fixed
position: As the power available is reduced, it is recommended to reduce Device is intended to be used indoor in dry places.
the load and/or to improve dissipation conditions. WARNING:
• When several dimmers are installed side by side, it is recommended to
Indicator 5 signals a short circuit when flashing or an overload condition improve dissipation conditions (i.e. leaving some space between 2 devices)
when switched on in a fixed position: in such cases, the dimmer reduces • This device must be installed only by a qualified electrician.
automatically the power available and no longer controls its load, as • Install in conformity to SELV installation rules.
required. • The applicable safety and accident prevention regulations must be
It is then necessary to check wiring and/or to decrease the load. observed.
• The device must not be opened. Any faulty devices should be returned to
Dimming mode override manufacturer.
• For planning and construction of electric installations, the relevant
To access this function, the product must already be con-nected to the guidelines, regulations and standards of the respective country are to be
mains and the bus. considered.

• Give one long press on button 8 until the status indicator lamps flash
• select the channel for which you wish to change the dimmer mode by
pressing on button3
• perform short repeat pressure for selecting the desired dimming mode :
! On “Yellow” mode validation, lighting can be disturbed for a short time.
The dimmer adjusts its characteristics to the connected lamps
• perform extended pressure on button 8 to confirm the selected mode, the
indicator luminous will stop flickering.
If no action is occurs within 2 minutes after extended pressure has ended,
the product returns to the previous dimming mode. If the validated
mode is not compatible with the con-nected load, the dimmer will return
automatically to the “factory” mode.

Displaying the current dimming mode


A single press on button 8 followed by a press on button 3 of the channel
concerned, allows the current dimmer mode to be consulted.

Selection of the number of outputs


Selection of the numbers of
outputs is configurable through
switch 7, as described below:

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 38


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Rail 3 Out Dimmer Module 1-10V
cod. 0KD030041

Environmental specifications
Product and Applications description • Operative temperature: 0°C ÷ + 45 °C
Dimmer used to control lighting circuits via a 1/10V connection, acting upon • Storage temperature: -20°C ÷ + 70 °C
remote control dimmers or electronic ballasts. • Relative Humidity: max 90 %
Device is intended to be installed on DIN rail.
The device configuration for commissioning in terms of physi-cal address, Physical specifications and Dimensions
group addresses and parameters is done with ETS (Engineering Tool • Dimensions 4 DIN modules
Software) through a download of the Application Program. • Weight: ca. 300 g.
• Installation: DIN rail (EN 60715)
Application program
Maximum number of group addresses: 254
This is the maximum number of different group addresses the device is able
to memorize.
Maximum number of associations: 255
This is the maximum number of associations between communication
objects and group addresses the device is able to memorize.

Technical Specifications
Power supply from EIB/KNX bus
• Voltage 29V DC
• Current consumption from EIB/KNX < 5 mA

Power supply from mains:


• Voltage 230V ~ 50/60 Hz
• Consumption without load 5W
Setting of the minimum and maximum dimming values
Connections
EIB/KNX: 2 bus terminal 0,8mmØ These values are set by the output and are independent.
1. Set dimming minimum or maximum value by: setting switch 1 at
Loads and power supply : position Manu and using pushbutton 5 of desired channel (a long pressure
brings lighting up to the desired setting, a short pressure switches lighting
On /Off ). Set switch 1 in position min or max according to requirement,
Load type / rated output or by setting switch 1 at position Auto and using a communication
pushbutton connected to the selected output to get the desired value (Set
configuration beforehand via ETS).
2. Memorize the chosen value by holding the pushbutton 5 of the desired
output for more than 3 seconds. Storage of value is confirmed by a double
flashing of the LED 4 associated to the output.
Note 1: If dimmer minimal or maximum value is set out of limits, LED 4
associated with the channel will flicker after BP 5 of the desired channel is
released.
Note 2: These limits can also be programmed directly via interface ETS.

Mounting and Wiring hints


While switch 1 is in menu position, BP 5 can be used to control the
connected load for on/off or dimming position. LED 4 displays the state of
the channel: switched on = the channel is currently in use. While switch 1 is
in auto position, BP 5 is inactive. LED 4 indicates the state of the channel.
LED 3 switches on and displays the presence of the bus after pressing BP 2.
While switch 1 is in auto position, one LED 4 flickers and signals loading of
wrong application software. Physical addressing is done by using BP 2 and
signalled by LED 3 switch-on. Device is intended to be used indoor in dry
places.
IMPORTANT
• This device must be installed only by a qualified electrician.
The efficiency of the transformer has to be taken into account to
• Install in conformity to SELV installation rules.
calculate the max. number of controlled lamps .
• The applicable safety and accident prevention regulations must be
observed.
Standards
• The device must not be opened. Any faulty devices should be returned to
• Protection class IP 30 (according to EN 60529):
manufacturer.
• Compliant to EN 60950 and ETSI 301 489-1 and ETSI 301 489-3
• For planning and construction of electric installations, the relevant
• Safety Class II according EN 61140
guidelines, regulations and standards of the respective country are to be
• EIB / KNX
considered.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 39


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Dimmer 1 Channel 700W
MASTER & SLAVE
cod. 0KD010010 e 0KD010011

Product and Applications description Allowed loads


0KD010010 is a KNX power dimmer 1-channel acting as a Master Dimmer
to which you can connect up to two Slave Modules (cod. 0KD010011) with
identical characteristics to the Master power dimmer and connected to it by
a local two wires bus.
Device installation diagram:

3 Channel
configuration
( Master + 2 Slave)

Slaves modules are


optional

Dimmer 0KD010010 can be used in one of the following configurations:


• Trailing Edge: The dimmer turns off part of the final part of the waveform of
the input voltage resulting in reduced lamp output.
(3) DO NOT CONNECT THE TRASFORMER WITHOUT CONNECTING THE
This load regulation is used for resistive or capacitive loads (typically halogen
LAMP ON THE SECONDARY WINDING TO AVOID OVERVOLTAGE THAT
lamps with electronic transformer or incandescent lamps)
MAY CAUSE DAMAGING TO THE DEVICE
• Leading Edge: The dimmer turns off part of the initial part of the
(4) FOR LED LAMPS OR ESL, THE CORRECT OPERATION STRICTLY
waveform of the input voltage, resulting in reduced lamp output.
DEPENDS FROM THE LAMP USED; SO THERE IS NO GUARANTEE IN
This load regulation is used for inductive loads (typically ferromagnetic
ADVANCE THE PROPER OPERATION OF THIS KIND OF LAMPS, EVEN
transformers or toroidal)
IF THEY ARE DECLARED AS DIMMERABLE.
The three channels are independent and can therefore operate on
different phases of the same three phase systems respecting the limit
Mechanical data
of 230Vac between phase and neutral.
• Plastic enclosure PPO - HFFR
The product is intended for installation on DIN rail in electrical
• Installation: DIN Rail
distribution cabinets.
• Dimensions: 4 Modules
• Weight (approx.): 230 g.
ETS Application Program Electrical Safety
Maximum number of group addresses: 53 • Degree of pollution (IEC 60664-1): 2
This is the maximum number of different group addresses the device is able • Degree of protection (EN 60529): IP 20
to memorize. • Protection class (according to IEC 1140): III
Maximum number of associations: 60 • Overvoltage class (according to IEC 664-1) III
This is the maximum number of associations between communication • Bus (safety voltage) SELV
objects and group addresses the device is able to memorize. • Compliant to EN50491-3
Caution: there is a limit to the number of associations that can be created, EMC compatibility
on the same device, between transmission communications objects (i.e. • Compliant to EN50491-5-1, EN50491-5-2
output feedback) and receiving communication objects (i.e. outputs). Environmental characteristics
If you want, on the same device, add a group address linked to • Compliant to EN 50491-2
a transmission communication object (feedback) to a receiving • Ambient temperature (Fig.1): 0 to + 45°C
communication object (output) which already has a different group • Storage temperature: - 20 to +55 °C
address associated, please note that you can add a maximum of 7 group • Relative humidity (not condensing): 90% max.
addresses of this kind for the whole device.
ETS programming of the Master device can be performed without slave CE MARK
modules (can be connected later), and without the mains voltage. In accordance with the EMC and low voltage guidelines

Technical Specifications
Power Supply
From EIB/KNX bus (1) 21...32V DC
Current consumption from KNX (1) ≤ 10mA
From mains (2) 230Vac 50/60 Hz
When output is OFF (2) 1W max.
Dissipated power (2) 1.2 % of load nominal power
(1) = REFERRED TO 0KD010010 MASTER CHANNEL ONLY
(2) = REFERRED TO BOTH 0KD010010 MASTER AND 0KD010011
SLAVE MODULES
Connections
• Power supply / load cable: max 2,5 mm2 – AWG 14
• Local bus length: max. 2 m. between 2 mod.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 40


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Dimmer 1 Channel 700W
MASTER & SLAVE
cod. 0KD010010 e 0KD010011

Visual and command elements AUTOMATIC IDENTIFICATION OF MAINS FREQUENCY


Every time devices are powered on they automatically recognize if the
power-line frequency is 50Hz or 60Hz; LEDs L1 and L2 flash alternately
for a few seconds; at the end of the procedure only one LED remains on
indicating the detected frequency (L1 = 50Hz, L2 = 60Hz)
WARNING: The automatic recognition of power-line frequency is
performed only if the load is connected.

Installation instructions
WARNING: device must be installed keeping a minimum
distance of 4mm between electrical power line (mains - 230V)
and red / black bus connector or bus cable.
• Device may be used for indoor installations in dry locations.
• Only an authorised installer shall install the device.
• Device must be installed and commissioned only by qualified installers.
• The applicable safety and accident prevention regulations must be
observed.
LOAD TYPE SETTING (MASTER AND SLAVE MODULES) – PROG LOAD • Device must not be opened. Any faulty device should be returned to
manufacturer.
The load type setting can be done by ETS parameter or manually with • For planning and construction of electric installations, the relevant
the procedure here described. It is also possible to perform an automatic guidelines, regulations and standards of the respective country are to be
recognition of the load type on the device. To perform the manual/ considered.
automatic load type setting on the device, ETS parameter “Manual local • KNX bus allows you to remotely send commands to the system actuators.
setting” must be selected. Always make sure that the execution of remote commands do not lead to
Press button P1 for at least 5sec to enter load programming mode: (PROG hazardous situations, and that the user always has a warning about which
LOAD); LED L1 and L2 show actual setting: L1 ON means resistive and commands can be activated remotely.
capacitive loads, L2 ON means inductive loads.

On every press on P1 (SET LOAD) LED L1 and L2 changes as


follows:
L1 ON (Resistive and capacitive) --> L2 ON (Inductive) --> L1 ON +
L2 ON (Automatic load recognition)

After 5sec from the last button press, device exit this manual setting
mode and the last set mode is saved in memory. If the selected mode is
“Automatic load recognition” the recognition procedure start immediately,
during this procedure it is possible to see the load switched ON and OFF;
after this, the identified mode is saved in memory and can be changed
manually by repeating the procedure.

SLAVE ADDRESS SETTING (SLAVE MODULES) - PROG ADDR


The address setting is only for slave modules.
WARNING: ADDRESS SETTING MUST BE DONE BEFORE ETS
DOWNLOAD.
If you want to change the slave address local buttons must be set as
“enabled”
The module 0KD010010 (Master) can work with a maximum of two
additional modules 0KD010011 (Slave); an address is assigned to each
slave: 1 (slave 1) or 2 (slave 2). The procedure described here should be
performed only on module 0KD010011 (Slave).

To assign the address, press simultaneously buttons P1 and P2 for at least


10s: the module enters the address setting mode (PROG ADDR) and LEDs
L1 and L2 show the current setting: L1 ON means slave 1 L1, L2 on means
slave 2. Each press of P2 (SET ADDR) changes the slave address and light up
alternately L1 and L2, corresponding to the addresses 1 and 2. After 5s from
the last button is pressed, the module leaves the assignment mode and
save the address.

WARNING: set a different address for the 2 slave modules


in order to avoid undesired behaviour at the outputs.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 41


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Dimmer 4 Output x 300W
cod. 0KD040040

Product and Applications description Connections


0KD040040 is a KNX universal power dimmer 4-channels with automatic • Power supply / load cable: max 4 mm2 – AWG 11
identification of load type and with settable parameters to optimize control
of different lamps like LED, incandescent and halogen, CFL dimmable lights, Allowed loads
low voltage lamps with electronic or ferromagnetic transformer.
Device installation diagram:

(1) DO NOT CONNECT THE TRASFORMER WITHOUT CONNECTING


Each channel of 0KD040040 can be used in one of the following
THE LAMP ON THE SECONDARY WINDING TO AVOID
configurations:
OVERVOLTAGE THAT MAY CAUSE DAMAGING TO THE DEVICE.
• Trailing Edge: The dimmer turns off part of the final part of the waveform
(2) FOR LED LAMPS OR ESL, THE CORRECT OPERATION STRICTLY
of the input voltage resulting in reduced lamp output. This load regulation
DEPENDS FROM THE LAMP USED; SO THERE IS NO GUARANTEE IN
is used for resistive or capacitive loads (typically halogen lamps with
ADVANCE THE PROPER OPERATION OF THIS KIND OF LAMPS, EVEN
electronic transformer or incandescent lamps).
IF THEY ARE DECLARED AS DIMMERABLE.
• Leading Edge: The dimmer turns off part of the initial part of the
(3) DIMMABLE LED LAMPS WITH INTERNAL TRANSFORMER CAN BE
waveform of the input voltage, resulting in reduced lamp output.This load
DETECTED AND DRIVEN ALSO IN RC MODE.
regulation is used for inductive loads (typically ferromagnetic transformers
or toroidal).
Mechanical data
Product is intended for installation on DIN rail in electrical distribution
• Plastic enclosure PC/ABS FR
cabinets and in vertical position with the bus connector on the
Installation: DIN Rail
bottom side as shown in figure; it is recommended to ensure adequate
• Dimensions: 8 Modules
dissipation conditions in free air.
• Weight (approx.): 230 g.
Electrical Safety
ETS Application Program
• Degree of pollution (IEC 60664-1): 2
Maximum number of group addresses: 53 • Degree of protection (EN 60529): IP 20
This is the maximum number of different group addresses the device is • Protection class (according to IEC 1140): III
able to memorize. • Overvoltage class (according to IEC 664-1) III
Maximum number of associations: 60 • Bus (safety voltage) SELV
This is the maximum number of associations between communication • Compliant to EN50491-3
objects and group addresses the device is able to memorize. EMC compatibility
Caution: there is a limit to the number of associations that can be created, • Compliant to EN50491-5-1, EN50491-5-2
on the same device, between transmission communications objects (i.e. Environmental characteristics
output feedback) and receiving communication objects (i.e. outputs) • Compliant to EN 50491-2
If you want, on the same device, add a group address linked to • Ambient temperature (Fig.1): 0 to + 45°C
a transmission communication object (feedback) to a receiving • Storage temperature: - 20 to +55 °C
communication object (output) which already has a different group • Relative humidity (not condensing): 90% max.
address associated, please note that you can add a maximum of 7 group CE MARK
addresses of this kind for the whole device. In accordance with the EMC and low voltage guidelines
ETS programming can be performed before installation in field without
connecting the device to the mains voltage.

Technical Specifications
Power Supply
From EIB/KNX bus 21...32V DC
Current consumption from KNX ≤ 10mA

From mains (2) 230VAC 50/60 Hz


When output is OFF 4W max. (1W x channel)
Dissipated power 6.8W max (1.7W x channel)

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 42


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Universal Dimmer 4 Output x 300W
cod. 0KD040040

Visual and command elements

• Device must not be opened. Any faulty device should be returned to


manufacturer.
• For planning and construction of electric installations, the relevant
guidelines, regulations and standards of the respective country are to be
considered.
• KNX bus allows you to remotely send commands to the system actuators.
Always make sure that the execution of remote commands do not lead to
hazardous situations, and that the user always has a warning about which
commands can be activated remotely.
• Device must be installed in vertical position respecting top and bottom
side as indicated in the drawing.

LOAD TYPE SETTING – PROG LOAD


The load type setting can be done by ETS parameter or manually with
the procedure here described. It is also possible to perform an automatic
recognition of the load type on the device. To perform the manual/
automatic load type setting on the device, ETS parameter “Manual local
setting” must be selected.

Press button P1 for at least 5sec to enter load programming mode: (PROG
LOAD); LED L1 and L2 blink together for 1 second then show actual setting:
L1 ON means resistive and capacitive loads, L2 ON means inductive loads.

On every press on P1 (SET LOAD) LED L1 and L2 changes as follows: Disposal


L1 ON (Resistive and capacitive) L2 ON (Inductive) L1 ON + L2 ON
(Automatic load recognition).

After 5sec from the last button press, device exit this manual setting mode The crossed-out bin symbol on the equipment or packaging means the
and the last set mode is saved in memory; exit from LOAD PROG mode product must not be included with other general waste at the end of its
is shown by the simultaneous blinking of LEDs L1 and L2 for 1 second. If working life.
“Automatic load recognition” mode is selected the recognition procedure The user must take the warn product to a sorted waste center, or return
start immediately, during this procedure it is possible to see the load it to the retailer when purchasing a new one. An efficient sorted waste
switched ON and OFF; after this, the identified mode is saved in memory collection for the environmentally friendly disposal of the used device,
and can be changed manually by repeating the procedure. or its subsequent recycling, helps avoid the potential negative effects on
the environment and people’s health, and encourages the re-use and/or
AUTOMATIC IDENTIFICATION OF MAINS FREQUENCY recycling of the construction materials.
Every time devices are powered on they automatically recognize if the
power-line frequency is 50Hz or 60Hz; LEDs L1 and L2 flash for a few
seconds; at the end of the procedure only one LED remains on indicating
the detected frequency (L1 = 50Hz, L2 = 60Hz).
WARNING: The automatic recognition of power-line frequency is
performed only if the load is connected.

Installation instructions
WARNING: device must be installed keeping a minimum
distance of 4mm between electrical power line (mains - 230V)
and EIB/KNX red / black bus connector.

• Device may be used for indoor installations in dry locations.


• Only an authorised installer shall install the device.
• Device must be installed and commissioned only by qualified installers.
• The applicable safety and accident prevention regulations must be
observed.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 43


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Inwall 2IN-2OUT and 4IN-4OUT LED Module
cod. 0KF020010 e 0KF040010

Product and Applications description


Device 0KF040010 includes 4 digital inputs for dry
contacts and 4 outputs for LEDs.
0KF020010 includes the same software functions of 0KF040010 with 2
inputs and 2 LEDs outputs.
These devices are extremely compact size (only 34 x 34 x 11 mm) and can
also be used in installations where the inwall space available is reduced.
The digital inputs can interface sensors, traditional buttons, etc; the 4 low
voltage output channels can drive LEDs for synoptic panels or switches.
For each input channel the following functions are available:
• Sending telegrams of closing / opening contact Technical Specifications
• Sending telegrams of short / long press
• Dimming control Power Supply
• Blinds / venetians control Via bus EIB/KNX 21..31V DC
• Scene control Current consumption < 5 mA
• 3 commands sequences with short / long press Control Elements
• 3 command sequences with toggling EIB/KNX red LED and button
• Step by step on/off combinations over 2 or 3 objects Connections
• Pulse counter on rising and/or falling edge 12 cable connector AWG24
• Enable / disable object for each input EIB/KNX terminal
Outputs can drive low voltage LED; if possible use high-efficiency LED Inputs
Number: 6–4–2
Device is equipped with KNX communication interface. Maximum cable length: ≤ 10m (twisted cable)
Reading voltage: 3,3V
Outputs
Number: 4-2
Current / voltage for leds 0,5mA / 3,3V
Mechanical data
ETS Application Program Plastic enclosure: PC / ABS
Installation: flush mounted wall box
Maximum number of group addresses: 53 Dimensions: 34 x 34 x 11 mm
This is the maximum number of different group addresses the device is Weight with package (approx.): 38 g.
able to store. Environmental Specification
Maximum number of associations: 60 According to EN 50491-2
This is the maximum number of associations between communication Ambient temperature during operation: -5 °C + 45 °C
objects and group addresses the device is able to memorize. Storage temperature: - 20 °C + 55 °C
Caution: there is a limit to the number of associations that can be created, Relative humidity (not condensing): max. 90%
on the same device, between transmission communications objects (i.e. Electromagnetic compatibility
output feedback) and receiving communication objects (i.e. outputs). Compliant with EN 50491-5-1 and EN 50491-5-2
If you want, on the same device, add a group address linked to Electrical Safety
a transmission communication object (feedback) to a receiving Degree of pollution (according to EN 60664-1):
communication object (output) which already has a different group Degree of protection (according to EN 60529):
address associated, please note that you can add a maximum of 8 group Safety Class (according to IEC 1140):
addresses of this kind for the whole device. Overvoltage class (according to IEC 664-1):
Bus: safety extra low voltage SELV DC 21…31 V DC
schema cablaggio 0KF040010 schema cablaggio 0KF020010 Compliant with EN 50491-3
CE Mark
According to EMC guideline and low voltage directive

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 44


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Inwall 4IN digital/4IN analogic - 4OUT LED Module
cod. 0KF040020

Product and Applications description Electrical Safety


• Degree of pollution (IEC 60664-1): 2
0KF040020 module includes 4 digital inputs to interface free potential • Degree of protection (EN 60529): IP 20
contacts; 4 analog / digital inputs for free potential contacts or temperature • Protection class (according to IEC 1140): III
sensors and 4 led outputs. • Overvoltage class (according to IEC 664-1): III
Digital inputs can interface sensors, traditional buttons, etc; 4 led output • Bus: tensione di sicurezza SELV DC 21..31 V DC
channels at low voltage can drive LED for synoptics panels or switches. • Meets EN 50090 and IEC 664-1: 1992
Inputs 5 ÷ 8, set as analog inputs, can enable up to 2 temperature probes EMC Requirements
(with On/Off threshold) and 2 thermostats to control heating and cooling • Complied with EN 50081-1, EN 50082-2 and EN 50090-2.2
equipments, valves, 2 and 4 pipes fan coils; etc.. Terms of use
The device is equipped with appropriate communication interface with • According to EN 50090-2.2
the bus type TP1 (twisted pair) KNX European standard, according CEI EN • Ambient temperature during operation: 0 °C + 45 °C
50090. • Storage temperature: - 20 °C + 55 °C
• Relative humidity: max 90%
ETS Application Program CE Mark
Maximum number of group addresses: 50 According to EMC guideline and low voltage directive
This is the maximum number of different group addresses the device
is able to memorize.
Maximum number of associations: 63 For Temperature Probes see page 13.
This is the maximum number of associations between communication
objects and group addresses the device is able to memorize.
Caution: there is a limit to the number of associations that can be created,
on the same device, between transmission communications objects (i.e.
output feedback) and receiving communication objects (i.e. outputs).
If you want, on the same device, add a group address linked to
a transmission communication object (feedback) to a receiving
communication object (output) which already has a different group address
associated, please note that you can add a maximum of13 group addresses
of this kind for the whole device.

Technical data
Power Supply
Via bus EIB/KNX cable
• Voltage 21..32V DC
• Current consumption EIB/KNX ≤ 10 mA
Digital Input 1 - 2 - 3 - 4
• For free potential contacts (dry contacts)
• Max. length of Connecting Cable: ≤ 30 m (twisted cable)
• Voltage Scanning: 3,3 V DC (internally Generated)
• AWG24 cables with 180 mm length
Digital Input 5 - 6 - 7 - 8
• For free potential contacts (dry contacts)
• Max. length of Connecting Cable: ≤ 10 m (twisted cable)
• Voltage Scanning: 3,3 V DC (internally Generated) Indicators and Control Elements
• 6 poles terminal with screws.
WIRED CONNECTORS:
Analog Input 5 – 6 – 7 - 8
1. BLACK Common IN/OUT 1
• For NTC temperature probe eelectron code:
2. WHITE IN 1
• 0KA000000 (range from -20°C to +100°C)
3. YELLOW OUT 1
• 0KA000001 (range from -50°C to +60°C)
4. BLACK Common IN/OUT 2
• Max. length of Connecting Cable: ≤ 20 m (twisted cable)
5. RED IN 2
• 6 poles terminal with screws.
6. ORANGE OUT 2
Digital Led Output 9 – 10 – 11 -12
7. BLACK Common IN/OUT 3
• 4 outputs for drive led – Max 0,3 mA
8. GREEN IN 3
• AWG24 cables with 180 mm length
9. BLUE OUT 3
Control Elements
10. BLACK Common IN/OUT 4
• EIB/KNX Red LED and button
11. VIOLET IN 4
• Bus: tensione di sicurezza SELV DC 21..31 V DC
12. GREY OUT 4
Mechanical Data
13. - IN / Temperature sensor 5
• Case: plastic/nylon
14. - IN / Temperature sensor 6
• Protection class: II in accordance with EN 61140
15. - Common 5-6
• Dimensions: (width x height. X depth.): 43 x 36 x 24 mm
16. - IN / Temperature sensor 7
• Weight: approx. 35 g

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 45


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Inwall 4IN digital/4IN analogic - 4OUT LED Module
cod. 0KF040020

17. - IN / Temperature sensor 8


18. - Common 7-8
19. - ETS Programming switch
20. - ETS Programming LED
21. - EIB/KNX Connector
- BLACK Bus Negative
+ RED Bus Positive

Installation Instructions
The device may be used for permanent indoor installations in dry locations
within wall box mounts.
WARNING
• Device must be installed keeping a minimum distance of 4mm between
electrical power line (mains) and input cables or red / black bus cable .
• The device must not be connected to 230V cables.
• The prevailing safety rules must be heeded.
• The device must be mounted and commissioned by an authorised
installer.
• The applicable safety and accident prevention regulations must be
observed.
• The device must not be opened. Any faulty devices should be returned to
manufacturer.
• For planning and construction of electric installations, the relevant
guidelines, regulations and standards of the respective country are to be
considered.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 46


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Temperature probe (int-ext)
cod. 0KA000000 e 0KA000001

(int/ext)

Dimensions in millimetres.
Warning: keep at least 6 mm from all live parts
NTC resistance tolerance: ± 3%
Measure range -20°C ÷ +100°C
Cable: 2 wire single insulation
Cable colour: Black
NTC colour: Black

D1 = 9 mm D2 = 4 mm L2 = 49 mm L1 = 1250 mm

Warning: keep at least 3 mm from all live parts


NTC resistance tolerance: ± 2%
Measure range -50°C ÷ +60°C
Cable: 2 wire double insulation
Cable colour: White
NTC colour: White

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 47


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Inwall Presence and Brightness sensor for ceiling
cod. 0KD010S10

Product and Applications description • Mounting in an UP socket with screw fixing


• Mounting with fixing claws in suspended ceiling
The device is a presence and motion detector with integrated brightness Connecting the detector
sensor. The device communicates via KNX. It is designed for ceiling (see figure 3)
mounting.

Commissioning / Factory default


After the device is connected to the bus voltage, the sensor must first
“Restart”, i.e. the motion sensor will be initialized.
Factory default
In the delivered state, the parameter Operating Mode is set to setting
mode.
While the device is in “Setting Mode”, the integrated programming LED
displays the PIR sensor state. (flashes briefly with motion).
Programming mode
A short push of learning button (< 2 s) enables the programming mode.
This will be indicated by a continuous light at the programming mode LED.
A second push disables this mode.
Behavior after programming D1 Device
The behavior of the device after programming with the ETS is dependent D2 Bus terminal
on the configuration. The description of the features, parameters and D2.1 (-) Terminal (grey)
objects is in the application program description (APB) of the device. D2.2 (+) Terminal (red)
D2.3 Test contact
Location / Function of the Display and Operating Elements D2.4 Bus line wire
Connecting:
A1 Device Plug wires into the bus terminal. Ensure you have stripped the insulation
A2 Fixing clamps back!
A3 Detector lens Push the bus terminal on the plug in the device (see figure 3)
A4 Learning button Disconnecting:
A5 Shade Separate the bus terminal from the device (use a screwdriver if necessary)
A6 Bus terminal Separate the wires from the bus terminal by turning.
A7 Design ring
A8 Programming mode LED
Mounting
behind lens
Installation in UP socket using screws
(see figure 4)
E1 Device
E2 Socket fixing screws
E3 UP socket Depth: min. 40 mm, 60 mm
The device is secured with fixing screws in the UP socket. The device can be
installed offset by 90° with the additional fixing holes.
Mounting and Connecting Note:
Fixing clamps must not be mounted!
DANGER Mounting the fixing clamps for mounting the device in suspended
When connecting the device, it should be ensured that the device can be ceilings
isolated. (see figure 5)
The device must not be opened. G1 Device
The device is intended for ceiling mounting. G2 Fixing clamp
Recommended mounting height: 2.4m – 3.0m Extend the fixing claws slightly and push over the lugs on the device.
There are the following options for this:
(see figure 2):

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 48


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Inwall Presence and Brightness sensor for ceiling
cod. 0KD010S10

Installation in suspended ceilings with fixing clamps Installation notes


(see figure 6)
F1 Suspended ceiling (max. thickness of the suspended ceiling: 30mm) Detection range
F2 Fixing clamps The detection range is divided in following areas:
F3 Device Detection of a person
Press the fixing clamps together (see figure 6) and push the device into the a) sitting in working desk height (0.8m)
opening (0 60mm - 65 mm) with the fixing clamps in front. b) walking straight to the detector
The fixing clamps hold the device on the ceiling. c) walking across the detector
Max. thickness of the suspended ceiling: 30mm d) Area of the brightness measuring in working desk height (0.8m)
Caution: Table 1 shows the maximum reachable diameter in meter of the different
When dismounting the device hold it where the two housing parts are areas for different installation heights (M).
joined together. Otherwise, the fixing clamps may hit your fingers.
Mounting site
Brightness measurement in particular
The daylight measurement determines an average brightness value in the
room, which can differ from the brightness on the worktop. You should
therefore avoid mounting sites with extreme light ratios.
If the detector is fitted near lights with a high proportion of indirect light,
the artificial light level at the detector mounting point must not exceed
the wanted nominal lighting level in the room. This can be compensated
by increasing the separation between the light cone and the detector. For
constant lighting control, direct artificial light on the detector should be
avoided.
Cutting the shade It is recommended to orientate the learning button of the device to the
(see figure 7) window, if possible. With increasing mounting height the sensitivity of the
If the detection range of the motion sensor brightness measuring is reduced. Especially at mounting height > 3.0m a
must be reduced, a shade can be used. test application on site is recommended.
The shade is cut out in the wanted sectors
with a knife. Presence-motion detection in particular:
Caution: Normally, the switching pattern is determined by people in the detector’s
Do not cut out the mounted shade! Only cut catchment area.
out the dismounted shade! In exceptional cases, however, it can be switched on inadvertently through
“outside factors”. Accordingly, potential “sources of interference” should be
Mounting / Dismounting the shade corrected during planning or before mounting.
(see figure 8)
Put the shade H2 over the lens of the device H1and fix it with the design Basics:
ring H3. The PIR - sensor reacts to temperature differences.
Note: The lower the temperatures difference between the ambient temperature
The learning button be reached only partly when the shade is mounted. and the moving object, the less sensitive the analysis. In other words,
Mounting the design rings moving objects will not then be detected as efficiently and the catchment
(see figure 8) area is restricted.
The design ring H3 is clipped on to the device H1 from below, until the
snaplock hooks on the design cover engage on the outer edge of the Note:
device with an audible click. • There must be an unobstructed line of sight to the person in the
Dismounting the design ring catchment area. People behind walls, etc. (including glass) cannot be
The design ring is dismounted by pulling downwards. Use a screwdriver to detected!
help with this operation. • Obstacles such as party walls, plants or shelves can limit the catchment
Caution: Be careful when handling the screwdriver. There is a risk of area.
scratching the ceiling or the design cover. Accordingly, be gentle while • Hanging lights cause shadows in the catchment area if they are mounted
working in the immediate vicinity of the presence detector.
Interference factors to be avoided:
• Rapid temperature changes in the vicinity of the detector, caused by fan
heaters being switched on or off, fans, etc., simulate motion.
• Lights being switched on or off in the immediate catchment area (mainly
incandescent and halogen lamps) simulate motion.
• Moving objects such as machines, robots, hanging posters, falling flower
petals, hot paper from laser printers, animals, etc.
• The mounting site must not be exposed to vibrations or motion.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 49


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Inwall Presence and Brightness sensor for ceiling
cod. 0KD010S10

Technical data
Power supply
via bus line
Current drain approx. 10 mA

Connections
Bus terminal

Mechanical specifications
Dimensions (see figure 10)
Weight: approx. 62g

Presence detection
Type: Passive infrared (PIR)
288 sectors for detection

Range: see figure 9 / table 1

Brightness measurement
Type: Contrast measurement

Electrical safety
Protection class (to EN 60529): IP 20

Environmental specifications
Ambient temperature in operation: -5°C ... +45°C
Storage temperature: -20°C ... +70°C
Relative humidity (non-condensing): 5% to 93%

Installation notes

• Device must be installed keeping a minimum distance of 4 mm between


electrical power line (mains - 230V) and red / black bus connector or bus
cable
• Device may be used for indoor installations in dry locations.
• Device must be mounted by an authorized installer.
• Device must be installed in a location that is accessible only to qualified
installers.
• The applicable safety and accident prevention regulations must be
observed.
• Device must not be opened. Any faulty device should be returned to
manufacturer.
• For planning and construction of electric installations, the relevant
guidelines, regulations and standards of the respective country are to be
considered.
• KNX bus allows you to remotely send commands to the system actuators.
Always make sure that the execution of remote commands do not lead to
hazardous situations, and that the user always has a warning about which
commands can be activated remotely.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 50


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Presence and Brightness sensor for ceiling
cod. 0KD010S20

Product and Applications description


0KD010S20 is a KNX occupancy detector with integrated function of
motion detection and light sensor.
Three operation mode are available:
• Automatic or semi-automatic mode with daylight depending constant
light control or switching output
• Slave mode
• Occupancy independent dimming regulating mode
Other characteristics:
• Up to three additional switching channels for lights or HVAC devices –
daylight dependent or not
• Threshold values and follow-up times can be changed for all channels
using communication objects
• Burn-in function with adjustable burn-in time from 1 to 100 hours,
activatable via communication object, in order to profit from the entire
operating time of the controlled lamps
• Activatable motion LED, deactivatable via ETS parameter or Installation Instructions
communication object The device may be used for permanent indoor installations in dry locations
Motion Detection: within wall box
0KD010S20 uses passive infrared system which registers heat movements. mounts.
• The presence detector should be installed so that the main direction of WARNING
movement is always tangential. • The device must not be connected to 230V cables
• For detecting very small movements (for example a person working on • The prevailing safety rules must be heeded.
PC) it is recommended to install 0KD010S20 directly above the desk. • The device must be mounted and commissioned by an authorized
• Avoid sources of interferences as : Radiators; Ventilation system or fan coils installer.
or equipments blowing warm air; Lamps very close to detection area to • The applicable safety and accident prevention regulations must be
avoid optical feedback. observed.
Light Sensor: • The device must not be opened. Any faulty devices should be returned to
0KD010S20 measures light value (LUX) and provide data to the KNX bus; manufacturer.
then this value can be used to switch lights on when the occupancy • For planning and construction of electric installations, the relevant
detector detects a motion and the light value is below a a target value. guidelines, regulations and
This data can also be used to set a dimming value to a dimmer in order to standards of the respective country are to be considered.
maintain a target light value.

Technical data Mounting

Power Supply: The device configuration (KNX physical address assignment) is done by
Via bus EIB/KNX cable pressing the programmingpush button located in the front side of the
• Voltage 21..30V DC housing. Please take care during installation toleave connection wires long
• Current Consumption EIB/KNX 10mA enough in order to remove the device easily from the wall box .
Control Elements
• Red LED and button EIB/KNX for programming the physical address 0KD010S20 is designed especially for suspended ceilings; a rounded hole of
Mechanical Data 68mm in the ceiling is request for installation. Spring clips must be opened
• Case: UV and shock resistant polycarbonate before inserting.
• Dimensions: (height. x diameter.)
0KD010S10 : 65 x 80 mm 0KD010S20
0KD010S20 : 50 x 97 mm
• Degree of protection: IP20
Electrical Safety & CE Mark
• According to EMC guideline2004/108/EC and low voltage directive
2006/95/EC
• KNX certificate
Terms of use
• Ambient temperature: - 25 °C + 55 °C
• Storage temperature: - 25 °C + 55 °C
• Relative humidity: max 90% not condensing

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 51


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module USB-KNX Interface
cod. 0KD010003

Applications area
This interface is for establish a bidirectional connection between a PC and
the EIB/KNX installation bus. The USB connector has a galvanic separation
from the EIB/KNX bus. Both ETS (Engineering Tool Software) versions ETS3
or later and some Visualization tools support this interface.

Applications Programs
Requires no application programs.

Technical Specifications
Electrical Safety
• Protection (acc. EN 60529): IP 20
• Bus safety extra low voltage SELV DC 24 V
EMC requirements
• Complies with EN 61000-6-2, EN 61000-6-3 and EN 50090-2-2
Environmental requirements
• Ambient temp. operating: - 5 ... + 45 °C
• Ambient temp. Non-op.: - 25 ... + 70 °C
• Rel. humidity (non-condensing): 5 % … 93 %
Certification
• EIB/KNX
CE norm
• Complies with the EMC regulations (residential and functional buildings)
and low voltage directive
Physical specifications
• Housing: Plastic
• DIN rail mounted device, width: 36 mm
• Weight: approx. 100 g
• Fire load: approx. 1000 kJ
Indicators
• Signal-LED (green) for USB-Connection
• Signal-LED (yellow) for Communication
Power supply
• The part of circuit for communication over USB is supplied by the
connected PC / Laptop, correct operation is signalled by the green LED
(USB).
• Power consumption: < 200 mW
• The part of circuit for communication over EIB/KNX is supplied by EIB/KNX
bus.
• Power consumption: < 300 mW
Connectors
• EIB/KNX connection terminal
• USB: USB connector type B
• Wire length max. 5 m

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 52


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module Router PoE IP-KNX
cod. 0KD010002

Applications area
The KNXnet/IP router allows forwarding of telegrams between different Connectors
lines through a LAN (IP) as a fast backbone. • EIB/KNX connection terminal
In addition this device is suited to connect a PC to the KNX/EIB network e.g. • LAN RJ-45 socket
for ETS programming. • Screw connector for power supply
The IP address can be obtained by a DHCP server or by manual
configuration (ETS) respectively.

This device works according to the KNXnet/IP specification using the core,
the device management, the tunneling and the routing part.
The KNX IP Router has a filter table and is able to buffer up to 150 telegrams.

Technical Specifications
Electrical Safety
• Protection (acc. EN 60529): IP 20
• Bus safety extra low voltage SELV DC 24 V
EMC requirements
• Complies with EN 61000-6-2, EN 61000-6-3 and EN 50090-2-2
Environmental requirements
• Ambient temp. operating: - 5 ... + 45 °C
• Ambient temp. Non-op.: - 25 ... + 70 °C
• Rel. humidity (non-condensing): 5 % … 93 %
Certification
• EIB/KNX
CE norm
• Complies with the EMC regulations (residential and functional buildings)
and low voltage directive
Physical specifications
• Housing: Plastic
• DIN rail mounted device, width: 36 mm
• Weight: approx. 100 g
• Fire load: approx. 1000 kJ
Operating controls
• Learning key for EIB/KNX
Indicators
• Learning-LED (red)
• Signal-LED (green) for EIB/KNX
• Signal-LED (green) for LAN
Ethernet
• 10BaseT (10Mbit/s)
• Supported internet protocols ARP, ICMP, IGMP, UDP/IP and DHCP
Power supply
• External supply 12-24V
• Alternative: Power-over-Ethernet
• Power consumption: < 800 mW

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 53


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module IP-KNX Interface
cod. 0KD010001

Descrizione del prodotto e suo funzionamento

The KNXnet/IP-Interface is used to connect a PC to the KNX/EIB network.


The connection is made through LAN (IP).
The IP address can be obtained by a DHCP server or by manual
configuration (ETS) respectively.

Il dispositivo è progettato per essere installato su barra DIN in scatole per la


distribuzione in bassa tensione.

Dati Tecnici

Electrical safety
• Protection (EN 60529): IP 20
• Safety extra low voltage SELV DC 24 V

EMC requirements
• Complies with EN 61000-6-2, EN 61000-6-3 and EN 50090-2-2 This device works according to the IP/ KNXnet specification using the core,
the device management und the tunneling part.
Environmental requirements
• Ambient temp. operating: - 5 ... + 45 °C
• Ambient temp. Non-op.: - 25 ... + 70 °C
• Rel. humidity (non-condensing): 5 % ... 93 %

Certification
• EIB/KNX

Physical specifications
• Housing: Plastic
• Rail mounted device
• Width: 36 mm
• Weight: approx. 100 g
• Fire load: approx. 1000 kJ

Operating controls
• Learning key for EIB/KNX

Indicators
• Learning-LED (red)
• Signal-LED (green) for EIB/KNX
• Signal-LED (green) for LAN

Ethernet
•10BaseT (10Mbit/s)
•Supported internet protocols ARP, ICMP, IGMP, UDP/IP and DHCP

Power supply
• External supply 12-24V
• Alternative: Power-over-Ethernet
• Power consumption: < 800 mW

Connectors
• EIB/KNX connection terminal
• LAN RJ-45 socket
• Screw connector for power supply

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 54


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module Gateway KNX-DMX 512 Interface
cod. 0KD010G10

Active Principle and Application Area


The KNX-DMX Gateway is an Interface between the KNX bus and the DMX
bus.
It combines elements of building automation with a multitude of lighting
and special effects devices for every need.

Active Principle and Application Area Automatic Dimming Function


The KNX-DMX Gateway is unidirectional, receives data telegrams on the Automatic dimming function can be switched on or off for all channels
KNX bus and transmits the data onto the DMX512 bus. The interface allows using an object, or can be parameterized by S3 when booting up.
the DMX512 actuators to communicate via the KNX bus using the full range Thereby the properties are controlled when a dimming telegram (DPT
of the channel. 3.007) appears.
The KNX-DMX Gateway contains 8 adjustable sequence positions within the • Automatic function Off ( S3 = 0 )
whole channel range. Individual scenes with all 512 channels can be saved A dimming object (4 bit) value range +7 .. -7 singularly reduces or increases
and retrieved using KNX group addresses. This function allows all channels the DMX value percentagewise.
to be connected simultaneously to one single object without causing any Appropriate for MicroVis dimming function (Standard 6% per rotary click) or
undo load on the KNX bus. similar rotary device.
The sequences are saved internally and can be retrieved even after a power • Automatic function On ( S3 <> 0 )
outage. (A sequence can only be saved 10000 times during the lifetime of A uniquely transmitted dimming setting is repeated during a time period
the device. The automatic save function should not be set for short (dimmer repetition) until it reaches a value of 0 or 100% or until it is
intervals.) The set value in sequence 8 is also “on“ for all channels when manually stopped. When 100% is transmitted, the preset value ‘in dimming
using 1 bit objects. curve“ is used (basic setting 1%).
The KNX-DMX Gateway is ready to use and can be positioned to the main This function allows the integration of the KNX-Gateway for an installation
group addresses with an S1 rotary switch. It is not necessary to project via with standard key buttons. A standard key button transmits a 100%
the ETS. upward or downward command in dimming function when pushed and
The KNX-DMX Gateway has 1556 objects with three types of telegrams held and a stop command when let go. A dimming setting can thus be
available: set. The dimming time period can be adjusted separately using either the
parameter repetition or the dimmer curve.
DPT 1.001 (1bit; switch) single channel The basic setting after booting up is 1% dimming. The repetition rate is
DPT 1.001(1bit; switch) save sequence and retrieve controlled by the rotary switch S3 and gives a dimming time result of circa
DPT 3.007 (4bit; relative dimming) single channel 1.5 sec * switching value (S3 = 1 .. 15 (F).
DPT 5.001 (1byte; show value) single channel
Address Diagram
The S2 rotary switch adjusts the transition period from one preset
brightness to the next, 15 (F) being immediate, 0 a time period of 1 second The KNX-DMX Gateway is a master device in the DMX bus. It possesses an
from 0% to 100%. internal data memory and constantly transmits the data at a DMX rate of
250k baud to all 512 DMX channels. When receiving valid KNX telegrams
The S3 rotary switch automatically sets the dimming function (s.u.) the values in the memory are changed.
parameters, 0 is no automatic dimming, otherwise dimming time = 1.5 sec * The transfer of the KNX telegram is preconfigured so that individual
switch value (S3 = 1 .. 15 (F) ) in increments of 1% (dimming value programming is not necessary. The KNX data points are managed in 3
0111b or 1111b). address rooms. That means that switching or dimming can be accessed on
The rotary switch settings will be prompted when starting and can be every channel.
readjusted during operation by using the T1 button. The group addresses diagram must be set up using the S1 rotary switch
Necessary requirements are a KNX bus, DMX 512 bus and a power supply. before initial operation (voltage supply). Changes become effective after
a reboot. The main group addresses from 0 – 15 are set up with the 16
The KNX-DMX Gateway in REG casing IP20 is available in sizes of 6 units. stage rotary switch. The middle and lower group addresses are set by the
Firmware upgrades can be done with ArcSuite via USB port. predetermined address rooms (see table 1). The DPT 5.001 allocates the
first 512 address on the KNX bus. After that the DPT 1.001 and DPT 3.007.
Finally, the sequence commands, a test function and dimming parameters
are coded.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 55


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module Gateway KNX-DMX 512 Interface
cod. 0KD010G10

Group Address Allocation Lower Group (bi-level KNX Address Room) Central On: with DPT 1.001 1 bit Value (Switch)
Address: 1552
Set Channel Value: with DPT 5.001 1 byte value ( 0 .. 100% ) All 512 channels display 100% when a 1 is transmitted and 0% when a 0 is
Addresses 0 - 511 transmitted.
To set a 1 byte value, use the lower group addresses 0-511 which
correspond to the channels 1-512 on the DMX bus. Dimmer Repetition Rate: with DPT 5.001 1 byte Value ( 0 .. 250 )
Address: 1553
Switch Channel Value: with DPT 1.001 1 bit value (switch) Set repetition rate parameters
Addresses 512 - 1023 The repetition rate affects the dimming time. At increments of 1%, a
Using a switch, this function can be used to switch every channel dimming time of 1.5 sec * is achieved.
separately. When the value is 0 the channel is switched off (0), when it is 1 Standard settings can be set using S3 (1 .. 15 (F) ).
the saved value in sequence 8 is accessed and transmitted to the DMX512 Suggested values are 2-40.
bus.
Every DMX channel can be independently switched. Downwards Dimming Curve: with DPT 3.007 4 bit Value (Dimming)
Before the values are transmitted, there must be defined values saved in Address: 1554
Sequence 8. This is the case for default settings at the time of delivery (255 Set dimming down to 100%.
for all channels). To reset the default settings use either the defined value When the automatic dimming function is chosen, the command “0001b”
with DPT 5.001 (group address x/0-511) or the function “Central On“ (group (100% dim down) is received and the programmed dimming setting will be
address x/1552) all values to 255. Then save this to Sequence 8 (group repeated (see Repetition Rate Object 1553) until 0 has been reached or
address x/1551). This establishes a maximum value for every channel. until it is manually stopped.
Standard setting “0111b“ = -1%
Dimming Channel: with DPT 3.007: 4 bit Value (Dimming) Possible dimming values as 4 bit object, see table 1
Addresses 1024 - 1535
Upwards Dimming Curve: with DPT 3.007 4 bit Value (Dimming)
Table 1: Address: 1555
Possible Dimming Value as 4 bit Object: Set dimming up to 100%.
0 = Stop When the automatic dimming function is chosen, the command “1001h”
1 = 100% down (100% dim up)is received and the programmed dimming setting will be
2 = 50% down repeated (see Repetition Rate Object 1553) until 255 has been reached, or
3 = 25% down until it is manually stopped.
4 = 12% down Standard setting “1111b“ =+1%
5 = 6% down Possible dimming values as 4 bit object, see table 1
6 = 3% down
7 = 1% down Activate Automatic Dimming: with DPT 1.001 1 bit Value (Switching)
8 = Stop Address: 1556
9 = 100% up Automatic Dimming
10 = 50% up Standard setting 0 if S3=0, otherwise 1
11 = 25% up 0 = automatic dimming switches off, no repetition of dimming.
12 = 12% up 1= automatic dimming switches on, repetition of dimming.
13 = 6% up
14 = 3% up
15 = 1% up Initial Operation
Using the automatic dimming function affects the performance when a
Circuit Points
dimming telgram is received.
Clamp RS485 /DMX (Bild1)
Choose Sequence: with DPT 1.001 1 bit Value (Switch)
1 DMX specific mass (0V)
Addresses 1536 - 1543
2 DMX Data - (B)
A complete sequence with 512 channels can be output via the DMX bus.
3 DMX Data + (A)
All previously saved values are displayed on channels 1-512.
There is a choice of 8 sequences at the addresses 1536-1543.
Clamp DC IN (9...30V)
The default value at the time of delivery is 255 for sequence 8 and 0 for
1 - DC 0V
sequences 1-7.
2 + DC 9-30V
Save Sequence: with DPT 1.001 1 bit Value (Switch) Clamp KNX BUS
Addresses 1544-1551 Switch on the voltage supply.
Here the current DMX values can be saved in one of the 8 sequences. The The group addresses are coded by S1 when the DC voltage in KNX-DMX
current brightness will be saved. Gateway is switched on. Soft-start (slow start-up to protect lights) can be
There is a choice of 8 sequences at the addresses 1544-1551. adjusted using S2 and S3 sets the dimming function.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 56


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module Gateway KNX-DMX 512 Interface
cod. 0KD010G10

Turning the rotary switch afterwards has no Effect unless restarting the
device or pushing the T1-Button. When pushing the T1. Table 1 Group Addresses Diagram (three stages)
Button you can switch all DMX-Channels simultaneously on/off.

The prog-button on the mainboard inputs the physical addresses via a


dummy application into the ETS.
The Jumper J1 (120R TERM) times the RS485 Bus with 120 Ohm load
resistance in its initial state.
The KNX bus is galvanically separated from the DMX 512 bus!
The power supply is galvanically separated from the DMX 512 bus and the
KNX bus.

Technical Specifications

Measurements: 107x75x31mm
Degree of Protection: I IP20
Mounting: modular device with 92 mm
Surrounding Temperature: -5 °C to 45 °C
Control Element: 3 x 16 staged rotary switch, 1 x Push Button (User) , 2 x LED
(User), 1 x EIB-Push Button + LED

KNX Connection: KNX clamp block


KNX Power Supply: 20 - 32V DC, approx. 150 mW
DMX Connection: 3 screw clamps 0.8mm²

KL1 GND, KL2 Data – (B) , KL3 Data+ (A)

Load Resistance DMX512: 120 Ohm via Jumper

Forth Programming: USB Slot and PC Software ArcSuite (Only Forth Users,
for additional tools)

Power Supply: 9-30V DC, 100mA, internal galvanically separated 2 screw


clamps

KL1 - GND, Table 1 Group Addresses Diagram (three stages)


KL2 - +V

DMX512 Bus: RS485 - 250Kbaud, incl. galvanic separation

DMX512 log

Please note the DMB512 specific connecting configurations (bus


connection, number of receiving slaves, bus topology)

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 57


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module DALI Gateway
cod. 0KD010G20

Safety instructions
Electrical equipment may only be installed and fitted by electrically
skilled persons. Serious injuries, fire or property damage possible. • Read out DALI device state via KNX, e.g. brightness or luminaire error
Please read and follow manual fully. • Manual operation of the DALI groups
Danger of electric shock. Always disconnect before carrying out work • Restraint
on the devise or load. At the same time, take into account all circuit • Feedback of switching state and brightness value in bus and manual mode
breakers that supply dangerous voltage to the device or load. • Collective feedback
Danger of electric shock. Device is not suitable for disconnection from • Central switching function
supply voltage. • Disabling function for each DALI group
The DALI control voltage is a functional extra-low voltage (FELV). On • Separate ON and OFF delay
installing, ensure safe isolation between KNX and DALI. • Staircase lighting timer with run-on time
These instructions are an integral part of the product, and must remain • Corridor function: when combined with motion detectors, reduced
with the end customer. continuous lighting, if no motion is detected
• Online or offline project planning of the DALI devices with ETS plug-in
Device components • Short circuit protection
• Surge protection
• Overload protection
• Operating hours counter
• Signal of the global switching status of the DALI devices, e.g. to switch off
the mains voltage of the DALI devices to avoid standby losses
• An individual DALI device can be exchanged during operation without
software.
• Delivery state: construction site mode, the DALI groups can be operated
using button field. All DALI devices are controlled jointly.

Operation
Operating elements
(1) Button field for manual operation
(2) Programming button and LEDs
(3) KNX connection
(4) Display of DALI devices or DALI group
(5) Connection for mains supply
(6) DALI output

Function
System information
This device is a product of the KNX system and complies with the KNX
directives. Detailed technical knowledge obtained in KNX training courses In operation with the button field the device distinguishes between a short
is a prerequisite to proper understanding. and a long press.
The function of this device depends upon the software. Detailed • Short: pressing for less than 1 second
information on loadable software and attainable functionality as well as the • Long: Pressing for between 1 and 5 seconds
software itself can be obtained from the manufacturer´s product database.
0KD010G20 - DALI gateway 1/9
Planning, installation and commissioning of the device are carried out with
the aid of KNXcertified software. Full functionality with KNX commissioning
software version ETS3.0f onwards.
An updated version of the product database, technical descriptions and
conversion programs and other auxiliary programs are available on our
Internet website.
Intended use
• Controlling of luminaires and other applications with DALI operating
device in KNX installations e.g. electronic ballast
• Installation on DIN rail according to EN 60715 in distribution boxes.
Product characteristics
• Control of up to 64 DALI devices in up to 32 groups
• Individual, group or central addressing
• Suitable for operation in emergency lighting systems
• 16 light scenes
• Effect control for dynamic lighting effects or colour games

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 58


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module DALI Gateway
cod. 0KD010G20

Operating modes
• Bus operation: Operation via push-button sensors or other bus devices Information for electrically skilled persons
• Short-term manual operation: Manual operation locally with button field,
automatic return to bus operation. Fitting and electrical connection
• Continuous manual mode: Exclusively manual operation on the device
No bus operation is possible in manual mode.
• No manual mode is possible in case of bus failure.
• After a bus failure and restoration the device switches to bus operation.
• After a power failure and restoration the device switches to bus operation.
• The manual mode can be disabled in ongoing operation via a bus Fitting the device
telegram. Observe the temperature range. Ensure adequate cooling.
• Mount device on DIN rail. Output terminals must be at the top.
Switching on the temporary manual control
Connecting the device

Control cable: appropriate type, cross-section and routing for the


specifications for 250 V cables. DALI and mains voltage wires can be run
together in a cable, e.g. NYM 5x1.5 mm².
• DALI participants from some manufacturers have expanded functions
and can e.g. be controlled via mains voltage on the DALI connection. When
existing DALI installations are refitted, remove all corresponding operator
controls.
• The DALI control voltage is a functional extra-low voltage (FELV). When
performing installation, perform the installation in such a way that when
an area is disconnected the lines carrying both the DALI and also the mains
voltage are disconnected.
• Connect device as shown in the connection example (Figure 3). 5/9 - DALI
gateway
• If multiple miniature circuit breakers supply dangerous voltages to the
device or load, couple the miniature circuit breakers or label them with a
warning, to ensure disconnection is guaranteed.
• Connect bus line with connecting terminal.
• DALI devices can be connected to various phase conductors.

Operation in emergency lighting systems


The device can be used in decentrally-powered or in centrally-powered
emergency lighting systems.
In decentrally-powered emergency light systems, emergency luminaires
with individual batteries and special DALI devices are used.
• Observe the number of DALI devices in the emergency luminaires used.
Emergency lighting systems with a central safety supply are required in
buildings larger than 2000 m². Depending on the scope of functions of the
system, only the emergency luminaires are supplied by the central safety

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 59


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module DALI Gateway
cod. 0KD010G20

supply (Figure 4), or the KNX system and DALI gateway are also supplied
(Figure 5). In the latter case, in emergency operation, the DALI gateway can Technical data
transmit the appropriate fault messages to a central system and other DALI Supply
gateways in the system. Rated voltage AC 110 ... 240 V ~
Mains frequency 50 / 60 Hz
Rated voltage DC DC 110 ... 240 V
Power loss max. 3 W
Ambient conditions
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
DALI
DALI rated voltage DC 16 V (typical)
Number of DALI subscribers max. 64
DALI transmission rate 1.2 kbit/s
DALI protocol EN 62386
Cable type Sheathed cable 230 V, e,g. NYM
DALI cable length
with Ø 1.5 mm² max. 300 m
with Ø 1.0 mm² max. 238 m
with Ø 0.75 mm² max. 174 m
with Ø 0.5 mm² max. 116 m
Housing
Fitting width 72 mm / 4 modules
Connection of power supply and DALI
Connection mode Screw terminal
single stranded 0.5 ... 4 mm²
Installing the cover finely stranded without conductor sleeve 0.5 ... 4 mm²
It is necessary to install a cover to protect the bus connection against Finely stranded with conductor sleeve 0.5 ... 2.5 mm²
hazardous voltages in the connection area. KNX
KNX medium TP
Commissioning mode S-mode
Rated voltage KNX DC 21 ... 32 V SELV
Power consumption KNX typical 150 mW
Connection type for bus Connection terminal

Troubleshooting
Display shows “Er”, connected DALI devices have no function, no
operation possible
• Route the bus line towards the rear. Cause: Mains voltage on DALI cable.
• Install cover on top of the bus terminal so that it snaps into place (Figure 6). Installation error. Disconnect device and connected DALI devices from
• Press the cover to the side and pull it off (Figure 7). mains voltage and disconnect bus voltage. Correct installation.
Display shows “bc” in manual mode, control of individual luminaires
Installing the cover not possible.
It is necessary to install a cover to protect the bus connection against Cause: The device has not been programmed or is programmed to
hazardous voltages in the connection area. “Broadcast”.
Check the device status. If necessary, program the device and put DALI
Commissioning system into operation.
Individual DALI devices have no function
Load the address and the application software
Cause 1: Load is defective, e.g. lamp.
• Switch on mains voltage.
Exchange load.
• Switch on the bus voltage.
Cause 2: DALI device is defective.
• Assign physical address and note on the device label.
Exchange defective device.
• Commission DALI system using commissioning software.
Switch on voltage.
• For more detailed information on commissioning of the DALI system, see
Press and ALL OFF buttons together for at least 10 seconds.
the technical product information for this device.
The device detects the exchanges DALI device and loads in the necessary
• Load the application software into the device.
data. The display (4) shows LE.
• No programming is possible if no mains voltage is connected.
• Simultaneous exchange of multiple DALI devices is only possible with
commissioning software and project data.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 60


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
DIN Module DALI Gateway
cod. 0KD010G20

None of the DALI groups can be operated.


Cause 1: All DALI groups disabled via bus or manual operation.
Cancel disabling.
Cause 2: Continuous manual mode switched on.
Switching off permanent manual control
Cause 3: Application software has been stopped, programming LED is
flashing.
Perform reset: Disconnect device from bus, switch on again after approx. 5
seconds.
Cause 4: Application software missing or faulty.
Check programming and correct.

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 61


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Touch Panel 3,5”
cod. 0KE010T10 e 0KE010T11

Product and application description Technical data


The touch panel is equipped with a 3,5 inches coloured display; Power Supply
dimming, status, values, lighting, shutters and timers are Auxiliary supply: 9 ..32 V DC
controlled and password protected when needed. Using the Current Consumption: typ 55 mA @ 24V DC
embedded temperature sensor and the embedded room Via bus EIB/KNX cable 21..31V DC
temperature controller function is possible to manage valves, Current Consumption EIB/KNX < 5 mA
fancoil or other HVAC equipments. RGB coloured Led or lights Control and visualization elements
are controlled with dedicated control elements and a proper 1 white signalling led (eelecta series)
KNX interface (DMX, 1-10V and DALI available); The device 1 buzzer for acoustic signalling
includes a number of pre-programmed logic including control of EIB/KNX Red LED and button
electrical loads with automatic power-off priority, (this feature is Connections and terminals
available in combination with eelectron KNX power measuring Wago red/grey to connect to EIB/KNX bus
device). Wago white/yellow to connect to aux supply
The panel 3.5 “Touch has an LED for status display (eelecta Mechanical data
series) and a buzzer to give sound signals with alarm function. Plastic parts: PC / ABS
Available in various colours and finishes is based on Linux OS Installation: wall box:
but can be programmed using only ETS without any additional 2 or 3 modules Italian
SW. German box
Device is equipped with KNX communication interface. Swiss box
Dimensions - eelecta: 112 x 110 x 48 mm apx.
Dimensions - 3025: 112 x 112 x 48 mm apx.
ETS Application program Weight (depends from code): 250 .. 300 g.
Environmental Specification
Main features
According to EN 50491-2
• 6 display pages, each with up to 8 control elements
Ambient temperature during operation: -5 °C + 45 °C
• for each element up to 4 KNX objects used
Storage temperature: - 20 °C + 55 °C
• wide range of control elements: pushbuttons / switches (with
Relative humidity (not condensing): max. 90%
status report), slide controllers, +/- push button for value
Electromagnetic compatibility
settings ( set points etc. )
Compliant with EN 50491-5-1 and EN 50491-5-2
• elements for dimming with switching function shutter/blinds
Electrical Safety
controller, clock timer, timer etc.
Degree
• of pollution : (according to EN 60664-1) 2
• 6th display page for alarm objects
Degree of protection: (according to EN 60529) IP20
• each page and each control element can be protected by
Safety Class : (according to IEC 1140) III
password
Overvoltage class: I (according to IEC 664-1) III
• various user interfaces, layouts and standby options
Bus: safety extra low voltage SELV DC 21…31 V DC
selectable on the device
Compliant with EN 50491-3
• the device includes a thermostat with a temperature probe
to manage the following main functions:
• control algorithm PI or P: 2-point on / off; PWM; Continuous Installation Instructions
monitoring / control fan coil 2 and 4 pipes.
• different modes: automatic HVAC / HVAC Manual Device must be installed keeping a minimum distance
• functions for managing a window contact or forcing in of 4mm between electrical power line (mains) and input
comfort cables or red / black bus cable .
• ability to manage via the data bus from an additional • The device must not be connected to 230V cables
sensor temperature • The prevailing safety rules must be heeded.
• The device must be mounted by an authorized installer.
• The applicable safety and accident prevention regulations
Technical data
must be observed.
• The device must not be opened. Any faulty devices should
Alimentazione
be returned to manufacturer.
• For planning and construction of electric installations, the
Alimentazione ausiliaria: 9 ..32V DC
relevant guidelines, regulations and standards of the
Corrente assorbita: typ 55 mA @ 24V DC
respective country are to be considered.
• KNX bus allows you to remotely send commands to the
Bus EIB/KNX 21..31V DC
system actuators. Always make sure that the execution of
Corrente assorbita da EIB/KNX: < 5 mA
remote commands do not lead to hazardous situations, and
that the user always has a warning about which
Elementi di comando e visualizzazione
commands can be activated remotely.
1 led bianco di segnalazione (serie eelecta) 1 buzzer per segnalazioni
acustiche Pulsante e led EIB/KNX

Terminali e connessioni
Connettore wago nero/grigio per connessione bus EIB/KNX Connettore
wago bianco/giallo per connessione ausiliaria

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 62


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Functionalities

Installation Outputs Relè Digital Load Shutter Fancoil Fancoil Fancoil Electric Motor
Rating Inputs Control Control 2 Pipes 4 Pipes 4 Pipes Valve Reductor
3/2/1 speed 2/1 speed 3 speed Driver

0KD040021 DIN RAIL 4 16A


4 modules

0KD080021 DIN RAIL 8 16A


4 modules

0KD120020 DIN RAIL 12 16A


9 modules

0KD080020 DIN RAIL 8 16A


4 modules

0KD040020 DIN RAIL 4 16A


4 modules

0KD040030 DIN RAIL 4 16A 4


4 modules

0KD040031 DIN RAIL 4 16A 4


4 modules

0KD080030 DIN RAIL 8 16A 8


4 modules

0KD080031 DIN RAIL 8 16A 8


4 modules

0KD030040 DIN RAIL 3 (300W)


6 modules

0KD030041 DIN RAIL 3 (1-10V)


4 modules

0KD010010 DIN RAIL 1 (700W)


4 modules

0KD010011 DIN RAIL 1 (700W)


4 modules

0KD040040 DIN RAIL 4 (300W)


8 modules

0KF020010 INWALL 2 2

0KF040010 INWALL 4 4

0KF040020 INWALL 4 4 4

0KF030010 INWALL 2 10A 3

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 58


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
Index for code

Code Description Page

Various Interfacce VITRUM EU KNX Series 1


Various Interfacce VITRUM BS KNX Series 2
Various Interfacce VITRUM EU Clima Control KNX Series 3
Various Interfacce VITRUM BS Clima Control KNX Series 4
0KD010020 Power Supply Unit 160 mA 5
0KD010024 Power Supply Unit 320 mA 6
0KD010021 Power Supply Unit 640 mA 7
0KD010000 Line Coupler BUS line KNX 8-9
0KD010022 Transformer 230V-12/15VAC (max 6 devices) 10
0KD010020 Transformer 230V-12/24VAC (max 12 devices) 10
0KD040020 Universal Module 4 Output with Manual Control 11
0KD010021 Universal Module 4 Output 12-13
0KD080020 Universal Module 8 Output with Manual Control 14
0KD080021 Universal Module 8 Output 15-16
0KD120020 Universal Module 12 Output with Manual Control 17
0KD040030 DIN Module 4 Input / 4 Output 18-19
0KD040031 Universal DIN Module 4 inputs / outputs 20-21
0KD080030 DIN Module 8 Input / 8 Output with Manual Control 22-23
0KD080031 Universal DIN Module 8 Input / 8 Output 24-25
0KF030010 Inwall 3 Input / 2 Output Module (relè 10A) 26-27
0KD010050 DIN Module Fancoil Controller Unit 0-10V 28
0KD010M10 Single-phase Digital Energy meters Direct connection 63A 30-31
0KD030M10 Three-phase Digital Energy meters Direct connection 63A 32-33
0KD030M20 Three-phase Digital Energy meters - TA connected 34-35-36
0KD030040 3 x 300W DIN Rail Dimmer Module 37-38
0KD030041 DIN Rail 3 Out Dimmer Module 1-10V 39
0KD010010 Universal Dimmer 1 Channel 700W (Master & Slave) 40-41
0KD010011 Universal Dimmer 1 Channel 700W (Master & Slave) 40-41
0KD040040 Universal Dimmer 4 Outputs 300W 42-43
0KF020010 Inwall 2 In / 2 Led Out - 4 In / 4 Out LED module 44
0KF040010 Inwall 2 In / 2 Led Out - 4 In / 4 Out LED module 44
0KF040020 Inwall 4 In digital - 4 In analogic / 4 Out LED module 45-46
0KA000000 Temperature probe (int-ext) 47
0KD010S10 Inwall Presence and Brightness Sensor for ceiling 48-49-50
0KD010S20 Presence and Brightness Sensor for ceiling 51
0KD010003 DIN Module USB-KNX Interface 52
0KD010002 DIN Module Router PoE IP-KNX 53
0KD010001 DIN Module IP-KNX Interface 54
0KD010G10 DIN Module Gateway KNX-DMX 512 Interface 55-56-57
0KD010G20 DIN Module DALI Gateway 58-59-60-61
0KE010T10 Touch Panel 3,5’’ white 62
0KE010T11 Touch Panel 3,5’’ black 62

HEADQUARTERS ADMINISTRATION OFFICE vitrum.com 64


Viale Pasubio, 6A Viale Lino Zanussi, 3
20154 • Milano IT 33170 • Pordenone IT
T +39 02 65560029 T +39 0434 516216
THINK SIMPLE S.r.l.

Sede Amministrativa e Operativa


Viale Lino Zanussi, 3 - 33170 Pordenone (PN)
T +39 0434 516216
F +39 0434 516230

Sede Legale e Commerciale


Viale Pasubio, 6A - 20154 Milano (MI)
T +39 02 65560029
F +39 02 45498295

info@thinksimple.it

vitrum.com

Copyright 2016©Think Simple S.r.l.


Tutti i diritti riservati | All rights reserved