YK-PSW1500w 2000W User Manual
YK-PSW1500w 2000W User Manual
YK-PSW1500w 2000W User Manual
2. Introduction
2-1 Front panel operations 6
2-2 Rear panel operations 7
2-3 Installation 9
2-4 Quick hook – up and testing 10
2-5 AC safety grounding 11
2-6 Making DC wiring connections 12
2-7 Inverter operation 14
2-8 Cooling fan working code 16
3. Maintenance 16
4. Troubleshooting guide 17
5. Warranty 18
7. Appendices A
7-1 Dip switch 19
7-2 Tune VR 19
8. Appendices B
8-1 Powering saving mode 19
1
1. Features
1-1-1 Power tools – circular saws, drills, grinders, sanders, buffers, weed and hedge trimmers,
air compressors.
1-1-3 Household items – vacuum cleaners, fans, fluorescent and incandescent lights, shavers,
sewing machines.
1-1-4 Kitchen appliances – microwave ovens, refrigerators and freezers, coffee makers,
blenders, ice markers, toasters.
1-1-5 Industrial equipment – metal halide lamp, high – pressure sodium lamp.
1-1-6 Home entertainment electronics – television, VCRs, video games, stereos, musical
instruments, satellite equipment.
2
1-2 Electrical Performance:1500W
Specification Model
YK- YK- YK- YK- YK- YK-
Item
PSW12150 PSW24150 PSW48150 PSW12150E PSW24150E PSW48150E
Continuous Output Power 1500W
Maximum Output Power 1650W(3mins)
Surge Rating 3000W
Input Voltage 12V 24V 48V 12V 24V 48V
Input Voltage Range 10-16VDC 20-32VDC 42-62VDC 10-16VDC 20-32VDC 42-62VDC
Dc Input over voltage alarm 15.5VDC 31VDC 61VDC 15.5VDC 31VDC 61VDC
Dc Input over voltage shut-down 16.0VDC 32.0VDC 62.0VDC 16.0VDC 32.0VDC 62.0VDC
Dc Input under voltage alarm 10.5VDC 21.0VDC 43.0VDC 10.5VDC 21.0VDC 43.0VDC
Dc Input under voltage shut-down 10.0VDC 20.0VDC 42.0VDC 10.0VDC 20.0VDC 42.0VDC
Frequency 50/60Hz ± 0.05%( Switch Selectable)
Peak Output Current 25A 11A
Efficiency (full load) 86% 88% 89% 87% 90% 92%
No Load Current Draw 1.2A 0.55A 0.3A 1.6A 0.7A 0.36A
Stand by Current Draw ≦1.5W Power Saving Mode
Output Waveform R Load Pure Sine Wave <3% THD
Output Voltage adjustment 100 ~120V (Tune VR) 200 ~ 240V (Tune VR)
Protection Overload, Short Circuit, Reverse Polarity (Fuse), Over/Under Input Voltage, Over Temperature
Digital Display OVP, UVP, OTP, OLP, VAC, AMP, WATT, VDC, TEMP, Hz
Safety UL 458 (File No.: E228561) EN60950-1
EN55022: 1998/A1:2000/A2:2003(Class B)
EN55024: 1998/A1:2001/A2;2003
EN61000-3-2: 2000
EN61000-3-3: 1995/A1:2001
EMC FCC Class B IEC 61000-4-2:1995/A1: 1998/A2:2000 E-Mark
E9-10R-02,6033
IEC61000-4-3:2002/A1:2002
IEC61000-4-4:2004
IEC61000-4-6:2003/A1:2004
IEC61000-4-8:1993/A1:2000
Power Saving Recovery Time 8 Seconds
Interface Control Port RS-232C With Baud Rate 2400, 4800,9600,19200 (Switch Selectable)
Operating Temperature Range -20℃ to 50℃
Storage Temperature Range -30℃ to 70℃
Dimensions 413(L) ×278(W) ×102(H) mm
Cooling Thermostatically controlled cooling fan
Weight 7.2kgs
3
Electrical Performance:2000W
Specification Model
YK- PSW YK- PSW YK- PSW YK-PSW YK-PSW YK-PSW YK-PSW YK-PSW YK-PSW YK-PSW
Item 12200 24200 48200 110200 220200 12200E 24200E 48200E 110200E 220200E
Continuous Output Power 2000W
Input Voltage 12V 24V 48V 110V 220V 12V 24V 48V 110V 220V
10-16 20-32 42-62 90-140 180-275 10-16 20-32 42-62 90-140 180-275
Input Voltage Range VDC VDC VDC VDC VDC VDC VDC VDC VDC VDC
DC Input over voltage alarm 15.5VDC 31VDC 61VDC 135VDC 270VDC 15.5VDC 31VDC 61VDC 135VDC 270VDC
C Input over voltage shut-down 16.0VDC 32.0VDC 62.0VDC 140VDC 275VDC 16.0VDC 32.0VDC 62.0VDC 140VDC 275VDC
C Input under voltage alarm 10.5VDC 21.0VDC 43.0VDC 95VDC 185VDC 10.5VDC 21.0VDC 43.0VDC 95VDC 185VDC
DC Input under voltage 10.0VDC 20.0VDC 42.0VDC 90VDC 180VDC 10.0VDC 20.0VDC 42.0VDC 90VDC 180VDC
shut-down
Output Voltage adjustment 100 ~120V (Tune VR) 200 ~ 240V (Tune VR)
Frequency 50/60Hz ± 0.05% ( Switch Selectable)
Peak Output Current 35A 16A
Efficiency (full load) 86% 88% 89% 94% 94% 87% 90% 92% 94% 94%
No Load Current Draw 1.25A 0.56A 0.32A 0.38A 0.18A 1.79A 0.87A 0.40A 0.4A 0.2A
Stand by Current Draw ≦1.5W Power Saving Mode
Output Waveform R Load Pure Sine Wave < 3% THD
Protection Overload, Short Circuit, Reverse Polarity (Fuse), Over/Under Input Voltage, Over Temperature
Digital Display OVP, UVP, OTP, OLP, VAC, AMP, WATT, VDC, TEMP, Hz
Safety EN60950-1
EN 55022: 2006, Class A
EN 55024:1998+A1: 2001+A2: 2003
EN 61000-3-2:2006
IEC 61000-4-2 Edition 1.2: 2001-04
EN 61000-3-3:1995+ A1:2001+A2: 2005
EMC FCC Class B IEC 61000-4-3 Edition 3.0: 2006
IEC 61000-4-4: 2004
IEC 61000-4-5 Edition 2.0: 2005
IEC 61000-4-6 Edition 2.2: 2006
IEC 61000-4-8 Edition 1.1: 2001-03
IEC61000-4-11 Second Edition: 2004-03
Power Saving Recovery Time 8 seconds
Interface Control Port RS-232C With Baud Rate 2400, 4800,9600,19200 (Switch Selectable)
Remote Control Unit Optional (RF Remote Control) or (wire Control)
Operating Temperature Range -20℃ to 50℃
Storage Temperature Range -30℃ to 70℃
Dimensions 413(L) ×278(W) ×102(H) mm
Cooling Loading controlled cooling fan
Weight 7.2kgs
Note: The specifications are subject to change without notice.
4
1-3 Mechanical Drawings
5
2. Introduction
The power inverter series are the member of the most advanced line of mobile AC power
systems available.
To get the most out of the power inverter, it must be installed and used properly.
Please read the instructions in this manual before installing and using this model.
6
2-1-4 AC outlet (Outlet sockets available):
7
WARNING!
Do not connect the 12V model to a 24V or 48V battery. The
unit will be destroyed immediately.
2-2-3 RS-232
Connect to remote control unit (option accessory) or connect to computer to remote
control working status.
8
WARNING!
Any damages caused by using incorrect RS232 cable will be
outside of our warranty scope. If you are not sure which one
is correct RS232 cable, please purchase the correct RS232
cable from us directly.
2-2-4 Connect chassis ground terminal to earth or to vehicle chassis using # 8 AWG wire.
WARNING!
Operation of the inverter without a proper ground, connection
may result in an electrical safety hazard.
WARNING!
Shock Hazard. Before proceeding further, carefully check the
inverter is NOT connected to any batteries, and that all wiring
is disconnected from any electrical sources. Do not connect
the output terminals of the inverter to an incoming AC source.
2-3 Installation:
Where to install:
The power inverter should be installed in a location that meets the following requirements.
2-3-1 Dry – Do not allow water to drip or splash on the inverter.
2-3-2 Cool – Ambient air temperature should be between -20°C and 50°C, the cooler the
better.
2-3-3 Safe – Do not install in a battery compartment or other areas where flammable fumes
may exist, such as fuel storage areas or engine compartments.
2-3-4 Ventilated – Allow at least 3 inch of clearance around the inverter for airflow. Ensure the
ventilation openings on the rear and bottom of the unit are not obstructed.
2-3-5 Dust-free – Do not install the inverter in a dusty environments where are dust, wood
particles or other filings/shavings.
These dusts can be pulled into the unit when the cooling fan is operating.
2-3-6 Close to batteries – Avoid excessive cable lengths but do not install the inverter in the
same compartment as batteries.
Use the recommended wire lengths and sizes (see section 2-6).
Also do not mount the inverter where it will be exposed to the gases produced by the
battery. These gases are very corrosive and prolonged exposure that will damage the
inverter.
9
2-4 Quick Hook – Up and Testing:
2-4-1 Unpack and inspect the power inverter, check to see that the power switch in the OFF
position.
2-4-2 Connect the cables to the power input terminals on the rear panel of power inverter.
The red terminal is positive (+) and black terminal is negative (-).
Insert the cables into the terminals and tighten relative nut to clamp the wires securely.
WARNING!
You may observe a spark when you make this connection
since current may flow to charge capacitors in the power
inverter.
Do not make this connection in the presence of flammable
fumes. Explosion or fire may result.
WARNING!
Make sure all the DC connections are tight (torque to 9-10
ft-lbs, 11.7-13Nm). Loose connections will overheat and could
result in a potential hazard.
2-4-3 Before proceeding further, carefully check that cable you have just connected negative
terminal of inverter to the negative output power source.
CAUTION!
Reverse polarity connection will blow a fuse in inverter and
may permanently damage the inverter.
Damage caused by reversing polarity connection is not
covered by our warranty.
2-4-4 Connect the cable from the negative terminal of the inverter to the negative terminal of
the power source. Make a secure connection.
10
WARNING!
You may observe a spark when you make this connection
since current may flow to charge capacitors in the power
inverter.
Do not make this connection in the presence of flammable
fumes. Explosion or fire may result.
2-4-5 Set the power switch to the ON position; you will hear the “bi-bi-bi” sound. At the same
time, the display shows the word “ASIAN” for two times. After that, you will hear the
continuous sound from internal alarm. Then, the AC voltage shows on the display. It
means the device has done the operation.
2-4-6 Set the power switch to the OFF position; the device shuts down completely.
2-4-7 Please use a power meter to accurately measure the true output R.M.S. voltage of
inverter.
Our company uses a power meter such as IDRC CP-350 or ABM 2019 to measure our
product.
WARNING!
Do not operate the power inverter without connecting it to
Ground.
Electrical shock hazard may result.
WARNING!
The installation of a fuse must be on positive cable.
Failure to place a fuse on “+ “cables running between the
inverter and battery may cause damage to the inverter and
will void warranty.
12
1500W
Model No Wire AWG Inline Fuse
YK-PSW12150 #2 200A
YK-PSW12150E #2 200A
YK-PSW24150 #4 100A
YK-PSW24150E #4 100A
YK-PSW48150 #6 50A
YK-PSW48150E #6 50A
2000W
Model No Wire AWG Inline Fuse
YK-PSW12200 #2/0 250A
YK-PSW12200E #2/0 250A
YK-PSW24200 #1/0 125A
YK-PSW24200E #1/0 125A
YK-PSW48200 #2 70A
YK-PSW48200E #2 70A
YK-PSW110200 #8 25A
YK-PSW110200E #8 25A
YK-PSW220200 #16 15A
YK-PSW220200E #16 15A
Also, use only high quality copper wiring and keep cable length short from 3-6 feet.
13
2-7 Inverter Operation:
To operate the power inverter, turn it on using the ON/OFF switch on the front panel.
The power inverter is now ready to deliver AC power to your loads.
If you are operating several loads from the power inverter, turn them on separately after the
inverter has been turned on.
This will ensure that the power inverter does not have to deliver the starting currents for all the
loads at once.
YK-PSW12150 YK-PSW12200
16.0VDC 15.5VDC 10.5VDC 10.0VDC
YK-PSW12150E YK-PSW12200E
YK-PSW24150 YK-PSW24200
32.0VDC 31.0VDC 21.0VDC 20.0VDC
YK-PSW24150E YK-PSW24200E
YK-PSW48150 YK-PSW48200
62.0VDC 61.0VDC 43.0VDC 42.0VDC
YK-PSW48150E YK-PSW48200E
YK-PSW110200
--------- 140VDC 135VDC 95VDC 90VDC
YK-PSW110200E
YK-PSW220200
---------- 275VDC 270VDC 185VDC 180VDC
YK-PSW220200E
14
2-7-5 Input DC Voltage indicator
LED displays light on VDC as show as input DC voltage value
3. Maintenance:
Very little maintenance is required to keep your inverter operating properly.
You should clean the exterior of the unit periodically with a dry cloth to prevent accumulation
of dust and dirt. At the same time, tighten the screws on the DC input terminals.
16
4. Troubleshooting Guide:
WARNING!
Do not open or disassemble the inverter. Attempting to service
the unit yourself may result in a risk of electrical shock or fire.
l Make sure that the chassis ground lug on the back of the power inverter is solidly
connected to the ground system of your vehicle, boat or home.
l Do not operate high power loads with the power inverter while watching television.
l Make sure that the antenna feeding your television provides an adequate (“snow free”)
signal and that you are using good quality cable between the antenna and the
television.
l Move the television as far away from the power inverter as possible.
l Keep the cables between the battery and the power inverter as short as possible and
twist them together about 2 to 3 twists per foot. This mini radiated interference from the
cables.
17
5. Warranty:
We warrant this product against defects in materials and workmanship during warranty period
and will repair or replace any defective power inverter when directly returned (postage paid) to
us.
This warranty will be considered void if the unit has suffered any obvious damage by natural
and man-made factors or alteration either internal or external and does not cover damage
arising from improper use such as plugging the unit into an unsuitable power sources attempts
to operate products with excessive power consumption requirement, or use in unsuitable
environments. This is the only warranty that the company makes.
No other warranties express or imply including warranties of merchantability and fitness for a
particular purpose. Repair and replacement are your sole remedies and the company shall
not be liable for damages, whether direct, incidental, special or consequential, even though
caused by negligence or other fault.
WARNING!
Before you install and use your inverter, be to read and save
these safety instructions.
6-1-2 To avoid a risk of fire and electronic shock. Make sure that existing wiring is in good
electrical condition; and that wire size is not undersized. Do not operate the inverter with
damaged or substandard wiring.
6-2-3 Do not drop a metal tool on the battery. The resulting sparks or short-circuit on the
battery or other electrical part may cause an explosion.
6-2-4 Remove personal metal items such as rings, bracelets, necklaces, and watches when
working with a lead-acid battery.
A lead-acid battery produces a short-circuit current high enough to weld a ring or the
like to metal, causing a severe burn.
18
7. Appendices A
7-1 Dip Switch (at the left side of inverter)
S1 FREQ. (Hz) S2 S3 BAUD RATE S4 POWER SAVING ACV-ADJ
H--------L
ON 60 ON ON 2400 ON DISABLE
240V 200V
H--------L
OFF 50 OFF ON 4800 OFF ENABLE
120V 100V
---- ---- ON OFF 9600 ---- ----- ----
8. Appendices B
8-1 Power Saving Mode
MICROPROCESSOR BASED SINE WAVE INVERTER SERIES ENABLING AND
DILSABLING POWER SAVING MODE
8-1-1 When an inverter is powered on and is running in idle condition (there is no load or the
load connected to the inverter has been switched off), it will still draw some power from
the batteries for keeping the system alive.
8-1-2 This inverter features a power saving “sleep“mode for conserving the battery power
during idle conditions. When this mode is enabled, the inverter senses the output power
being drawn and if this is less than 2 to 15 watts, the inverter shuts down the output
power. Only essential systems are kept alive to reduce power consumption from the
batteries to a very low value of only about 1.5 watts. As soon as a load is switched on,
the inverter wakes up from its “sleep” condition and restores the output power after a
response time of about 8 seconds. Please note that on waking up from the power
saving “sleep” mode, the inverter requires some time to prepare all the systems before
it can start delivering power to the load. Hence, the output power will not be available
immediately but after a time lag of approx. 15 to 18 sec.
If using a hand tool or other appliance with a trigger, keep the trigger pressed for some
time till the power is available to drive the tool / appliance.
RE-MARK:
The user manual is subject to change without notice.
19