Acti 9 Itl - A9c30212
Acti 9 Itl - A9c30212
Acti 9 Itl - A9c30212
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Acti 9
Product name Acti 9 iTL
Product or component type Impulse relay
Device short name ITL
Device application Standard
Poles 2P
Pole contact composition 2 NO
[In] rated current 16 A
Network type AC
[Uc] control circuit voltage 24 V DC
48 V AC 50/60 Hz
Complementary
Network frequency 50/60 Hz
[Ue] rated operational voltage 250 V AC 50/60 Hz
Control type Coil deconnection
Remote and manual control
Control signal type Impulse
Switching frequency 5 switching operations/minute
100 switching operations/day
Impulse duration 50 ms...1 s
Remote control type Illuminated push-button 3 mA
Local signalling ON/OFF indication
Mounting mode Fixed
Mounting support DIN rail
9 mm pitches 2
Height 84 mm
Width 18 mm
Environment
Standards EN 669-1
EN 669-2-2
Product certifications CCC
GOST
Quality labels CEBEC
IMQ
KEMA
NF
VDE
Noise level 60 dB
IP degree of protection IP20 on opening conforming to IEC 60529
IP40 in enclosure conforming to IEC 60529
Pollution degree 3
Tropicalisation 2
Relative humidity 95 % ( 55 °C )
Ambient air temperature for operation -20...50 °C
Ambient air temperature for storage -40...70 °C
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1825 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product Environmental Profile
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months 18 months