Module Types
Pump (by sensor types & pump leads)
A
RESET POWER TEST B - Bi-Metal (21 & 22) or Thermistor (10 & 11)
& Float Switch (3 & 4)
Monitoring Module
(Bi-Metal & Moisture Probe) D - Bearing RTD (15 & 16) & Float Switch (3 & 4)
O/A Size 3.75”H x 2.62”W x 2.25” D
Overview: KSB submersible pump motors have varying combinations of over-temperature and
moisture intrusion protection. The alternatives employed by the KSB factory are motor specific. The
alternatives include bi-metal or thermistors for winding thermal protection, an RTD for bearing
temperature monitoring and either a conductivity probe, a float switch or on some motors both sensor
types. The appropriate module(s) should be specified accordingly.
PumpSafeTM Module ‘A’: Monitors either thermal winding sensor (bi-metal or thermistor) and the
conductivity probe to detect moisture intrusion. This sensor combination is typical for low
horsepower motors. Each type module monitors one thermal and one moisture function input (see
above listing). Each module type likewise has one set of form C output contacts per alarm function to
provide remote pump monitoring or to directly control the pump’s operation.
Installation: The PumpSafeTM Module can be installed locally or in a MCC on the supplied 12 pin
socket. Modules can be combined in a single Nema 4X local control panel for monitoring multiple
pump installations.
Operation: Integrally the module indicates using bi-colored LEDs, one each for each fault type;
GREEN being OK, RED a failure "ALARM" condition. In addition a power ON LED and a "TEST"
and a "RESET" button are provided. A self correcting fault, either moisture or thermal, causes the
respective LED to change from a steady (alarm) to a flashing signal. This LED continues to flash
until locally cleared, providing the plant operator annunciation of a potential intermittent fault
condition. Rev 1.6 8/22/02
2.25”
2.9” 1.687
3.5”
2.62”
.875”
1.75”
2.375
24 1 1 46 1 1
34 1 1 66 1 1
54 1 1 96 1 1
74 1 1 126 1 1
114 1 1 206 1 1
164 1 1 266 1 1
a)
234 1 1 326 1 1 1 or 2
a)
294 1 1 406 1 1 1 or 2
a) a)
354 1 1 1 or 2 506 1 1 1 or 2
a) b)
504 1 1 1 or 2 606N 1 1 3 or 5
a) c)
654 1 1 1 or 2 806 1 1 3, 4, or 5
a) b)
784 1 1 3, 4, or 5 806N 1 1 3
b) b)
804N 1 1 3 or 5 1006N 1 1 3 or 5
b) c)
954N 1 1 3 or 5 1026 1 1 3, 4, or 5
Notes:
a) Optional Monitoring – Float switch in leakage chamber. Monitoring is not required to maintain warranty.
b) Optional Monitoring – Float switch in leakage chamber and PT-100 RTD on lower pump-side bearing. Monitoring is
not required to maintain warranty, but is recommended.
c) Optional Monitoring – Float switch in leakage chamber. PT-100 RTD on lower pump-side bearing available as an
adder. Monitoring is not required to maintain warranty, but is recommended.
Notes:
a) Optional Monitoring – Float switch in leakage chamber. Monitoring is not required to maintain warranty.
b) Optional Monitoring – Float switch in leakage chamber and PT-100 RTD on lower pump-side bearing. Monitoring is
not required to maintain warranty, but is recommended.
c) Optional Monitoring – Float switch in leakage chamber. PT-100 RTD on lower pump-side bearing available as an
adder. Monitoring is not required to maintain warranty, but is recommended.
184 1 1 6 156 1 1 6
224 1 1 6 186 2 1 7
a)
304 2 1 7 186 w/ optional RTD 1 1 1 8
a)
304 w/ optional RTD 1 1 1 8 226 2 1 7
a)
374 2 1 7 226 w/ optional RTD 1 1 1 8
a)
374 w/ optional RTD 1 1 1 8 306 2 1 7
a)
454 2 1 7 306 w/ optional RTD 1 1 1 8
a)
454 w/ optional RTD 1 1 1 8 456 2 1 7
a)
554 2 1 9 456 w/ optional RTD 1 1 1 8
a)
544 w/ optional RTD 1 1 1 10 556 2 1 9
a)
754 2 1 9 556 w/ optional RTD 1 1 1 10
a)
754 w/ optional RTD 1 1 1 10 756 2 1 9
a)
904 2 1 9 756 w/ optional RTD 1 1 1 10
a)
904 w/ optional RTD 1 1 1 10 906 2 1 9
a)
1104 2 1 9 906 w/ optional RTD 1 1 1 10
a) a)
1104 w/ optional RTD 1 1 1 10 1106 1 1 1 10
a)
1324 2 1 9 1326 1 1 1 10
a) a)
1324 w/ optional RTD 1 1 1 10 1606 1 1 1 10
a) a)
1604 1 1 1 10 2506 1 1 1 10
a) a)
2004 1 1 1 10 3006 1 1 1 10
a)
2504 1 1 1 10
Notes:
a) Optional Monitoring – Float switch in leakage chamber. PT-100 RTD on lower pump-side bearing available as an
adder. Monitoring is not required to maintain warranty, but is recommended.
b) Optional Monitoring – Float switch in leakage chamber and PT-100 RTD on lower pump-side bearing. Monitoring is
not required to maintain warranty, but is recommended.
158 1 1 6 3010 2 1 7
a)
228 2 1 7 3010 w/ optional RTD 1 1 1 8
a)
228 w/ optional RTD 1 1 1 8 3710 2 1 7
a)
308 2 1 7 3710 w/ optional RTD 1 1 1 8
a)
308 w/ optional RTD 1 1 1 8 4510 2 1 7
a)
378 2 1 7 4510 w/ optional RTD 1 1 1 8
a)
378 w/ optional RTD 1 1 1 8 5510 2 1 9
a)
458 2 1 7 5510 w/ optional RTD 1 1 1 10
a)
458 w/ optional RTD 1 1 1 8 7510 2 1 9
a)
558 2 1 7 7510 w/ optional RTD 1 1 1 10
a)
558 w/ optional RTD 1 1 1 8 9010 2 1 9
a)
758 2 1 7 9010 w/ optional RTD 1 1 1 10
a)
758 w/ optional RTD 1 1 1 8 11010 2 1 9
a)
908 2 1 9 11010 w/ optional 3 1 10
a)
RTD
908 w/ optional RTD 1 1 1 10
13210 2 1 9
1108 2 1 9 a)
13210 w/ optional 1 1 1 10
a)
1108 w/ optional RTD 1 1 1 10 RTD
a)
16010 1 1 1 10
1328 2 1 9
a)
a) 20010 1 1 1 10
1328 w/ optional RTD 1 1 1 10
a)
25010 1 1 1 10
2008 2 1 9
a)
2008 w/ optional RTD 3 1 10
Notes:
a) Optional Monitoring – Float switch in leakage chamber. PT-100 RTD on lower pump-side bearing available as an
adder. Monitoring is not required to maintain warranty, but is recommended.
b) Optional Monitoring – Float switch in leakage chamber and PT-100 RTD on lower pump-side bearing. Monitoring is
not required to maintain warranty, but is recommended.
Pump Type Motor code PumpSafe Module(s) QTY Required Wiring Diagram
A B D Drawing #
Notes:
a) Optional Monitoring – Float switch in leakage chamber and PT-100 RTD on lower pump-side bearing. Monitoring is
not required to maintain warranty, but is recommended.
b) Optional Monitoring – Float switch in leakage chamber, PT-100 RTD on lower pump-side bearing, and PT-100 on
upper pump-side bearing. Monitoring is not required to maintain warranty, but is recommended.
JAB 8/05
Power
24-240 VAC
COM 8 5 N
9 4 GRD Moisture
NO Thermal Fail (alarm)
10 3 9 Moisture
NC Seal Fail (motor interlock)
11 2 22 Winding Bi-metallic
COM
12 1 21 Winding Bi-metallic
NO Seal Fail (alarm)
PUMPSAFE A
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should be used with timers. PumpSafeTM relays
have built in reset button.
PumpSafeTM Wiring Diagram
KRT Submersible Pumps - Drawing # 2
JAB 8/05
Power
24-240 VAC
not used 7 6 L1
COM 8 5 N
10 3 4 Float switch
NC Seal Fail (motor interlock optional)
11 2 15 not used
COM
12 1 16 not used
NO Seal Fail (alarm)
COM 8 5 N
9 4 GRD Moisture
NO Thermal Fail (alarm)
10 3 9 Moisture
NC Seal Fail (motor interlock)
11 2 22 Winding Bi-Metallic
COM
12 1 21 Winding Bi-Metallic
NO Seal Fail (alarm)
PUMPSAFE A
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button.
PumpSafeTM Wiring Diagram
KRT Submersible Pumps - Drawing # 3
JAB 8/05
Power
24-240 VAC
COM 8 5 N
9 4 GRD Moisture
NO Thermal Fail (alarm)
10 3 9 Moisture
NC Seal Fail (motor interlock)
11 2 11 Winding Thermistor
COM
12 1 10 Winding Thermistor
NO Seal Fail (alarm)
PUMPSAFE A
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button.
PumpSafeTM Wiring Diagram
KRT Submersible Pumps - Drawing # 4
JAB 8/05
Power
24-240 VAC
not used 7 6 L1
COM 8 5 N
10 3 4 Float switch
NC Seal Fail (motor interlock optional)
11 2 15 not used
COM
12 1 16 not used
NO Seal Fail (alarm)
COM 8 5 N
9 4 GRD Moisture
NO Thermal Fail (alarm)
10 3 9 Moisture
NC Seal Fail (motor interlock)
11 2 11 Winding thermistor
COM
12 1 10 Winding thermistor
NO Seal Fail (alarm)
PUMPSAFE A
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button.
PumpSafeTM Wiring Diagram
KRT Submersible Pumps - Drawing # 5
JAB 8/05
Power
24-240 VAC
COM 8 5 N
9 4 3 Float switch
NO Thermal Fail (alarm)
10 3 4 Float switch
NC Seal Fail (motor interlock optional)
12 1 16 PT-100 Common
NO Seal Fail (alarm)
COM 8 5 N
9 4 GRD Moisture
NO Thermal Fail (alarm)
10 3 9 Moisture
NC Seal Fail (motor interlock)
11 2 11 Winding thermistor
COM
12 1 10 Winding thermistor
NO Seal Fail (alarm)
PUMPSAFE A
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button. If no PT-100 is used, a jumper must be installed on the D module between
terminals 1 and 2 to prevent a false alarm.
PumpSafeTM Wiring Diagram
KRTB Drywell Submersible Pumps - Drawing # 6
JAB 10/05
Power
24-240 VAC
7 6 L1
NC not used
8 5 N
COM
9 4 22 Bimetallic switches (M)
NO Fan Control
10 3 21 Bimetallic switches (M)
NC not used
11 2 11-1 Winding thermistors (E1)
COM
12 1 10-1 Winding thermistors (E1)
NO not used
COM 8 5 N
10 3 9 Moisture (M)
NC Seal Fail (M) (motor interlock)
PUMPSAFE A
E1 = fan motor
M = pump motor
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button.
PumpSafeTM Wiring Diagram
KRTB Drywell Submersible Pumps - Drawing # 7
JAB 6/05
Power
24-240 VAC
COM 8 5 N
NC not used 10 3
PUMPSAFE A
NC not used 7 6 L1
8 5 N
COM
COM 8 5 N
PUMPSAFE A
E1
E1 = fan motor
M = pump motor
DKN 225
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button.
PumpSafeTM Wiring Diagram
KRTB Drywell Submersible Pumps - Drawing # 8
JAB 10/05
Power
24-240 VAC
NC not used 7 6 L1
COM 8 5 N
PUMPSAFE B
8 5 N
COM
10 3 9 Moisture (M)
NC Seal Fail (M) (motor interlock)
PUMPSAFE A
E1 = fan motor
M = pump motor
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button. If no PT-100 is used, a jumper must be installed on the D module between
terminals 1 and 2 to prevent a false alarm.
PumpSafeTM Wiring Diagram
KRTB Drywell Submersible Pumps - Drawing # 9
JAB 6/05
Power
24-240 VAC
COM 8 5 N
NC not used 10 3
PUMPSAFE A
NC not used 7 6 L1
COM 8 5 N
COM 8 5 N
10 3 9 Moisture (M)
NC Seal Fail (M) (motor interlock)
PUMPSAFE A
E1
E1 = fan motor
M = pump motor
DKN 280
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button. If no PT-100 is used, a jumper must be installed on the D module between
terminals 1 and 2 to prevent a false alarm.
PumpSafeTM Wiring Diagram
KRTB Drywell Submersible Pumps - Drawing # 10
JAB 10/05
TM
PumpSafe Relays Required:
(1) Module A, (1) Moduel B, and (1) Module D with form C outputs rated 5A @ 120VAC
Power
24-240 VAC
NC not used 7 6 L1
COM 8 5 N
PUMPSAFE B
8 5 N
COM
10 3 9 Moisture (M)
NC Seal Fail (M) (motor interlock)
PUMPSAFE A
E1 = fan motor
M = pump motor
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button. If no PT-100 is used, a jumper must be installed on the D module between
terminals 1 and 2 to prevent a false alarm.
PumpSafeTM Wiring Diagram
Amamix & Amaprop Submersible Mixers - Drawing # 11
JAB 8/05
Power
24-240 VAC
COM 8 5 N
9 4 GRD Moisture
NO Thermal Fail (alarm)
10 3 9 Moisture
NC Seal Fail (motor interlock)
11 2 11 Winding Thermistor
COM
12 1 10 Winding Thermistor
NO Seal Fail (alarm)
PUMPSAFE A
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button.
PumpSafeTM Wiring Diagram
Amacan Submersible Pumps - Drawing # 12
JAB 6/05
Power
24-240 VAC
COM 8 5 N
9 4 GRD Moisture
NO Thermal Fail (alarm)
10 3 9 Moisture
NC Seal Fail (motor interlock)
11 2 11 Winding thermistor
COM
12 1 10 Winding thermistor
NO Seal Fail (alarm)
PUMPSAFE A
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button.
PumpSafeTM Wiring Diagram
Amacan Submersible Pumps - Drawing # 13
JAB 8/05
Power
24-240 VAC
COM 8 5 N
9 4 3 Float switch
NO Thermal Fail (alarm)
10 3 4 Float switch
NC Seal Fail (motor interlock optional)
12 1 16 PT-100 Common
NO Seal Fail (alarm)
COM 8 5 N
9 4 GRD Moisture
NO Thermal Fail (alarm)
10 3 9 Moisture
NC Seal Fail (motor interlock)
11 2 11 Winding thermistor
COM
12 1 10 Winding thermistor
NO Seal Fail (alarm)
PUMPSAFE A
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button. If no PT-100 is used, a jumper must be installed on the D module between
terminals 1 and 2 to prevent a false alarm.
PumpSafeTM Wiring Diagram
Amacan Submersible Pumps - Drawing # 14
JAB 8/05
Power
24-240 VAC
8 5 N
COM
9 4 3 Float switch
NO Thermal Fail (alarm)
10 3 4 Float switch
NC Seal Fail (motor interlock optional)
12 1 16 PT-100 Common
NO Seal Fail (alarm)
PUMPSAFE D
jumper together
8 5 N
COM
NO (not used) 12 1
COM 8 5 N
9 4 GRD Moisture
NO Thermal Fail (alarm)
10 3 9 Moisture
NC Seal Fail (motor interlock)
11 2 11 Winding thermistor
COM
12 1 10 Winding thermistor
NO Seal Fail (alarm)
PUMPSAFE A
Note: Relays are fail safe. Relays shown in the energized state. Contacts change state at loss of power.
Therefore, pushbutton resets on the front of control panel should only be used with timers. PumpSafeTM
relays have built in reset button. If no PT-100 is used, a jumper must be installed on the D module between
terminals 1 and 2 to prevent a false alarm.
TM
PumpSafe Technical Specification
Modules A, B & D
Furnish and install ____ pump monitoring module(s) and socket(s), model(s)
___________________ for KSB submersible pump model ________________.
Each pump monitor shall provide dual function monitoring for both Over-
Temperature via Bi-Metal, Thermistor or RTD sensor and Seal Failure via
Moisture sensor or Float switch. Each module shall provide dual color
(Red/Green) LED’s for ALARM status (one for each fault indication), Power LED
and a Test/Reset push button. Module shall provide independent 5A, 120 VAC
rated Form C outputs for over-temperature and seal failure. Module must have a
24 - 240 VAC input power range, a 2.8 watt power consumption and must be UL
approved.
8/14/01
KSB Spare Parts Quote/Order Form
Date: 18-Feb-06 Buyer assumes responsibility for selection of correct
KSB Representative: parts if order is submitted without the following
Prepared by: Shawn Stevenson information.
Purcahse Order NO.: Pump Type:
Model:
KSB Quote No.: Serial Number:
Rep Net Multiplier: 0.75 Impeller Size:
Source of Ident Numbers:
Source of Costs:
Power Cable: How was
type/size determined:
QTY Part No. Indent No. Description List Each Net Each Ext. Net
1 PumpSafe A Pump Monitoring Control Module $220 165.00 165.00
1 PumpSafe B Pump Monitoring Control Module $220 165.00 165.00
1 PumpSafe D Pump Monitoring Control Module $220 165.00 165.00
1. F.O.B. Richmond, VA – Prepay and Add 5. Shipment: 5 Days after receipt of order (subject to availability).
2. Terms: Net 30 days, pending credit approval 6. Minimum order is $100.
3. Prices are valid for 90 days. 7. Pricing is based on KSB Standard Terms & Conditions of Sale.
4. 10% expediting fee for order processing and shipment within 48 hours. ($25 minimum fee, $100 maximum fee).
KSB, Inc. building a reputation…Not resting on one!!!!