MTU 12V4000 DS1500: Diesel Generator Set
MTU 12V4000 DS1500: Diesel Generator Set
MTU 12V4000 DS1500: Diesel Generator Set
SYSTEM RATINGS
Standby
Voltage (L-L) 380V 480V** 600V** 4160V
Phase 3 3 3 3
PF 0.8 0.8 0.8 0.8
Hz 60 60 60 60
kW 1500 1500 1500 1500
kVA 1875 1875 1875 1875
Amps 2849 2255 1804 260
skVA@30%
Voltage Dip 3350 3500 4800 3900
Generator Model* 744RSL4054 742RSL4050 743RSS4290 743FSM4368
Temp Rise 130 °C/40 °C 130 °C/40 °C 130 °C/40 °C 130 °C/40 °C
Connection 4 LEAD WYE 4 LEAD WYE 4 LEAD WYE 6 LEAD WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
STANDARD FEATURES*
// MTU Onsite Energy is a single source supplier // Generator
// Global Product Support - Brushless, Rotating Field Generator
// 2 Year Standard Warranty - 2/3 Pitch Windings
// 12V 4000 Diesel Engine - PMG (Permanent Magnet Generator) supply to regulator
- 57.2 Liter Displacement - 300% Short Circuit Capability
- Common Rail Fuel Injection // Digital Control Panel(s)
- 4-Cycle - UL Recognized, CSA Certified, NFPA 110
// Complete Range of Accessories - Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine-Driven Fan
STANDARD EQUIPMENT*
// Engine
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
3 / // / MTU 12V4000 DS1500 (1500 kWe) - Standby
APPLICATION DATA
Fuel Supply Connection Size #16 JIC 37° Female // Exhaust System
1” NPT Adapter Provided
Fuel Return Connection Size #16 JIC 37° Female Gas Temp. (Stack): °C (°F) 435 (815)
1” NPT Adapter Provided Gas Volume at Stack
Max. Fuel Lift: m (ft) 1 (3) Temp: m3/min (CFM) 342 (12,078)
Recommended Fuel Diesel #2 Max. Allowable
Total Fuel Flow: L/hr (gal/hr) 960 (254) Back Pressure: kPa (in. H20) 8.5 (34.1)
4 / // / MTU 12V4000 DS1500 (1500 kWe) - Standby
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website
for unit specific template drawings.
SOUND DATA
© MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 1088 (77 11E) 2019-02
Unit Type Standby Full Load
Level 0: Open Power Unit dB(A) 92.2
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
www.mtuonsiteenergy.com