M E D IU M VO LTAG E P R O D U C TS

OVB-VBF outdoor vacuum circuit breakers


Safe and reliable protection for your distribution networks
and industrial applications

ABB offers its complete range of three


phase, live tank outdoor vacuum circuit
breakers for distribution substations up to
40.5kV system voltage in accordance to
IEC 62271-100.

State of the art vacuum interrupters and


most reliable operating mechanisms
makes it idle for protection of your
distribution networks, industrial
substations and wind/solar generating
stations.

Reliable also in extreme conditions Safe, easy to install, operate & maintain

· Hermetically sealed poles to avoid moisture · Completely covered live electrical contacts and
ingress moving parts (mechanism) inside control cabinet
to ensure safety of operating personnel
· State of the art vacuum interrupters with silicone
encapsulation ensures switching performance over · Integrated closing spring charging lever for easy
life time even in extreme weather conditions and safe operation even in emergency situation.

· Continuous rated coil with inbuilt self-protection · Compact and robust operating mechanism with
feature to prevent coil failure and thus limit down optimized components and low energy required
time for operation

· Operating mechanism with inbuilt mechanical anti- · Easy plug and play accessories to ensure reduced
pumping feature and simple maintenance

· Suitable even for 0.6 g seismic acceleration · Standing pedestal available as option to carry out
maintenance in control cabinet
· Option for -40 oC ambient temperature available
OVB-VBF OVB-VBF
Technical parameters Unit
36kV 40kV
Standards IEC 62271-100
Rated voltage kV 24 / 36 40.5
Rated frequency Hz 50 / 60 50 / 60
Rated continuous normal current A 2000 / 2500 2500 / 3150
Rated short time current withstand capacity kA 31.5 for 3 sec 31.5 for 3 sec
Rated peak withstand current kAp 82 82
Rated lightning impulse withstand voltage (BIL) kVp 170 195
Rated power frequency withstand voltage (1 min dry) kV 70 95
Rated symmetrical interrupting current kA 31.5 31.5
Rated line charging current (LC) A 10 10
Rated cable charging current (CC) A 50 50
Single capacitor bank switching current A 400 --
Back to back capacitor bank switching current A -- 750
Operating sequence O-0.3s-CO-15s-CO O-0.3s-CO-3min-CO
Minimum operation (CO cycles) at rated continuous current Operations 10000
Interrupting media Vacuum Interrupter
Ambient temperature range °C -25 to +50 1
Minimum external creepage distance mm/kV 25 / 31 25 / 31
Weight of circuit breaker (without structure) Kg 380 650
1
Circuit breakers for lower temperatures available on request
Optional provision to mount CT/PT and SS material for fabrication available on request.


01 OVB-VBF 36 kV


02 OVB-VBF 40 kV

Doc ID: 2REA045621P0001 © September 2017 ABB. All rights reserved


01 02


ABB India Limited The data and illustrations are not
Plot 79, Street 17 binding. We reserve the right to
MIDC Estate, Satpur, Nashik, India 422007 modify the contents of this
Phone: +91 253-2201-200 document without prior notice
Fax: +91 253-2351-260 following technical and product
developments.
Email: ppmvsupport@in.abb.com