Wiring Methods and Materials
Wiring Methods and Materials
Wiring Methods and Materials
Conductors
Conductors
Wires
Cables
o are those larger than wires
Conductors
Stranded Wires
Cable: Type MC
Copper
2.0(1.6)
8.0(3.2)
30
38
50
Aluminum ore
Copper- Clad
Aluminum
3.5(2.0)
8.0(3.2)
30
38
50
Marking
All conductors
o
o
o
o
o
o
o
Cabinets
Elbows
Couplings
Fittings
Support
Support hardware
Cable sheathing
listed
EXEPTION:
stainless steel shall not be required to have
protective coatings
or Outdoor
Exposed to Sunlight
shall be listed as sunlight resistant
Chemical Exposure
shall either be inherently resistant to
chemicals
corrosion
Raceways
-------are channels or wiring accessories so
designed for holding
wires, cables, or
busbars that are either made of metal,
plastic, or any insulating mediums.
Common Types of Raceways
o Conduits
o Connectors and Other Accessories
Raceway Installations
oComplete Runs
exposed raceways having hinged or removable
covers, shall be installed complete between
outlet,
Junction
Splicing points
Raceway Installations
oWelding
Metal Raceways shall not be
supported,
terminated, or
connected by welding
to
the raceway unless specifically designed to be
or otherwise permitted to be in this code.
Underground Installations
oMinimum Cover Requirements
shall meet the minimum cover
of
table 3.0.1.5
requirements
Column 1
Column 2
Column 3
Column 4
Column 5
600
150
450
300
150
450
150
300
150
150
Under a building
0 (In
0 (In
0 (In
raceway
only)
raceway
only)
150
150
raceway
only)
450
100
100
(direct
burial)
100
(In
raceway)
Column 1
Column 2
Column 3
Column 4
Column 5
600
600
600
600
600
450
450
450
300
450
450
450
450
450
450
Underground Installations
oListing
Cables and Insulated Conductors installed in
enclosures or raceways shall be listed for use in wet
locations.
o Underground Cables
Under Buildings
beyond the
Underground Installations
oConductors Entering Buildings
shall be protected to the point of entrance
oService Conductors
shall have their location identified by a warning
ribbon that is placed in the trench at least 300mm above
the underground
installation
Underground Installations
Underground Installations
oBackfill
that contains large rocks, paving materials, cinders,
large or sharply angular substances, or corrosive material
shall not be placed in an
excavation
where
materials may damage raceways,
cables,
or
other substructures.
Underground Installations
oRaceway Seals
Conduits or Raceways through which
moisture
may contact live parts shall be sealed or plugged at either
or both ends.
oBushing
shall be used at the end of the conduit
Underground Installations
o Conductors of the Same Circuit
shall be installed in the same raceway
oGround Movement
shall be arranged to prevent damage to the
enclosed conductors or to the equipment connected to
the raceways.
SCOPE
Construction
Specification
USE
Installation
Bending Radius
5 times the external diameter of metallic
sheath for cable not more than 19mm
Equipment Grounding
copper, shall provide an adequate path for grounding
steel, an equipment grounding conductor shall provided
Insulation
The overall covering shall be flame retardant
and moisture resistant
Article 3.36
Power and Control Tray Cable : Type
TC
Conductors
shall be sizes 0.75 mm^2 through 500 mm^2 copper
3.5 mm^2 through 500 mm^2 aluminum and copper-clad
aluminum
Type SE
Service entrance cable having a flame
retardant, moisture-resistant covered
Construction
cabled single conductor, type USE construction
recognized for underground use shall permitted to have a
bare copper conductor cabled with the assembly.
use underground
single conductor cables
For wiring in wet, dry or corrosive locations
For solar photovoltaic locations
As single conductor cables
Supported by cable trays
Ampacity
60C (140F) conductors
Sheath
flame retardant; moisture, fungus, and
corrosion resistant
Insulation
moisture-resistant types
the conductor insulation shall be rated 90C
(194F).
Article 3.42
Intermediate Metal Conduit : Type IMC
Intermediate Metal Conduit : Type
IMC
- A steel threadable raceway of circular
cross section designed for physical
protection and routing of conductors and
cables and for use as an equipment
grounding conductor when installed with
its integral couplings
Article 3.42
Intermediate Metal Conduit : Type IMC
Uses Permitted
All atmospheric Conditions and
Occupancies
Corrosion Environments
Cinder fill
Wet locations
Dissimilar metals
Size
Minimum-IMC 15 mm
Maximum- IMC larger than raceway size
100 mm shall not be used
3.44.2 Installation
Uses Permitted
All atmospheric Condition and
Occupancies
Corrosion
Wet location
Size
Minimum- RMC smaller than15mm
shall not be used
Maximum- RMC smaller than
raceway size 150 mm shall not be
used.
3.52.2 Installation
Uses not permitted
Hazardous locations
Support of luminaires
Physical damage
Ambient temperature
Insulation temperature Limitation
Theaters and Similar Locations
15-25
900
32-50
1500
65-80
1800
90-125
2100
150
2400
Permitted
In discrete lengths from reels
In location subject to severe
corrosive influence
In cinder fill
In direct burial installation on earth
or concrete
Where exposed
Within a building
In hazardous location
Where subject to ambient temperature
Article 3.53
High Density Polyethylene Conduit:
Type HDPE Conduit
3.53.2 Installation
Size
Minimum- HDPE conduit smaller
than raceway 15 mm shall not be
used
Maximum- HPDE conduit larger
than raceway size 100 mm shall not
be used.
Bends
-shall be manually made so that the conduit will not
damage
Size
Minimum: LFNC smaller than
raceway size 15 shall not be used
Maximum: larger than raceway size
100 mm shall not be used
Bends
Bends in conduit shall be so made that the conduit is not
damae and internal diameter of the conduit is not effectively
reduced
3.56.3 Construction Specification
Construction
shall be provided in continuous length capable of being
shipped in a coil, reel, or carton without damage.
Marking
-shall be marked at least every 600 mm
Article 3.58
Electrical Metallic Tubing:Type EMT
Electrical Metallic Tubing (EMT)
- An unthreaded thin wall raceway of
circular cross section designed for he
physical protection and routing of
conductors and cables and for use as
an equipment grounding conductors
when installed utilizing appropriate
fittings.
Article 3.58
Electrical Metallic Tubing:Type EMT
3.58.2 Installation
Uses Permitted
Exposed and concealed
Corrosion Protection
Wet Locatiions
Article 3.58
Electrical Metallic Tubing:Type EMT
Size
Minimum-EMT smaller than raceway size
15mm shall not be used
Maximum-shall be raceway size 100mm
3.58.3 Construction Specification
Construction
factory threaded integral couplings shall be
permitted, theads should be factory made
Marking
-EMT shall be clearly and durably marked at least
every 3000mm
Article 3.60
Flexible Metallic Tubing: Type FMT
Flexible Metallic Tubing (FMT)
- A raceway that is circular in cross section,
flexible, metallic and liquid tight without a
nonmetallic jacket.
Uses Permitted
In dry location
Where concealed
In accessible location
For system voltage of 1000 volts
maximum
Article 3.60
Flexible Metallic Tubing: Type FMT
Uses not permitted
In hoistways
Storage battery rooms
Hazardous location
Underground for direct earth burial
Where subject to physical damage
In lengths over 1800 mm
Size
Minimum-smaller than raceway size 15 mm
shall not be used
Maximum-shall be raceway size 20mm
Article 3.62
Electrical Non metallic Tubing:Type ENT
Electrical Non metallic Tubing: Type
ENT
-a non metallic or associated couplings,
connectors, annd fittings for the
installation of electric conductors.
Uses Permitted
In any building not exceeding above grade
as follows
For exposed work
Concealed within walls,floors, ceilings.
Article 3.62
Electrical Non metallic Tubing:Type ENT
Uses permitted
In location subject to corrosive influence and where subject
to chemicals.
In concealed dry and damp locations
Above suspended ceilings
Uses not permitted
Hazardous locations
For the support of luminaires and other equipment
Where subject to ambient temperature
For direct earth burial
Article 3.62
Electrical Non metallic Tubing:Type ENT
Uses not permitted
Where the voltage is over 600 volts
In theaters
Exposed to the direct rays of the sun
Size
Minimum
-ENT smaller than raceway size 15 mm shall not be used
Maximum
-ENT larger than raceway size 50mm shall not be used.
Article 3.62
Electrical Non metallic Tubing:Type ENT
3.62.3 Construction Specification
Construction
-ENT shall be made of material that does not exceed the
ignitibility, flammability, smoke generation, and toxicity
characteristic of rigid polyvinyl chloride
Markings
-shall be clearly and durably marked at least every 3000 mm.
-The type of material shall also be included in the marking
-type, printed, quantity are identified by printed tag
Use
-permitted at any voltage or current for
which spaced conductors are rated and
shall installed only for exposed work
Types of Conductors
insulation rating of 75C (167F) or higher
ARTICLE 3.72
CELLULAR CONCRETE
FLOOR RACEWAYS
3.72.1.2 Definitions
Cell
- A single, enclosed tubular space in a floor made of
precast cellular concrete slabs, the direction of the cell
being parallel to the direction of the floor member.
Header
- Transverse metal raceways for electric conductors,
providing access to predetermined cells of a precast
cellular concrete floor.
ARTICLE 3.72
CELLULAR CONCRETE
FLOOR RACEWAYS
Uses Not Permitted
Where subject to corrosive vapor
In any hazardous (classified) 5.1.2.1(b)(3)
In commercial garages, othe r than for supplying
ceiling outlets or extensions to the area below the floor
but not above
Not Permitted
or assembly of units or
sections and associated fittings
forming a structural system used
to securely fasten or support
cables and raceways.
H
V
D
C
The voltage in the rectifier end of the line can be controlled by adding a proportional
amount of the line voltage drop, Rd *Id to the measured inverter end voltage.
Normally used to keep the firing angle as close as possible to the rated value which
normally chosen to 15 degrees.
The control characteristics must include a dead band also here and step of 1.25%
from rated value corresponds to a region from 12 to
17.5 in .
Udio *cos a in the expression constant, at varying rectifier AC voltage,
the current control system responds to it by changing .
The (TCC) system in the rectifier compares an a response signal to
a reference value and at a significant deviation it orders the tap changer to step and
change Udio.
(TC @ Inv Sta) Tap changer control maintains the DC voltage equal to reference voltage.
Normally, gamma is kept as constant for proper commutation.
Any increase or decrease in the DC voltage will be controlled by tap changer
Since tap changers would take more time to control the converter voltage than current
or voltage controller, dynamic interaction between both controllers can be avoided.
The tap changers in the inverter in the extinction angle control are normally used to
control the voltage on the DC line.
The voltage response measured by a voltage divider is compared to an order, Udi0.
For a significant difference between the two signals, the tap changer control system
(TCC) orders increase or decrease of the valve side voltage.
Because of the stepwise character of the tap changer, the control than characteristic harmonics
system must be provided with dead band. To bring the voltage
back to the reference value and thus avoid hunting, the dead band These are due to:
should have a width of at least one tap changer step
1. Inbalance in the operation s)of two bridges
firing a 12 pulse converter (residual harmonics)
When the inverter takes over the current control, the DC voltage
tap
changer
control
must
be
locked
(generation of
2. firing angle errors
triplen and eve
Harmonics
harmonics and
3. unbalance and distortion of AC Voltages
their analysis is
Harmonics are electric voltages and currents that appear on the
4.unequal transformer leakage impedances
complex)
electric power system as a result of non-linear electric loads.
Harmonic instability may occur in high-voltage dc (HVDC) links
due to dynamic interactions between HVDC terminals and the
impedance of the dc lines or cables.
The harmonics that come from the HVDC will not only increase
loss, thermal stress of equipment, reduce equipment life,
interference with communications, metering, protection and
control devices to work properly and in some cases, it can even
lead to the collapse of the system.
The above circuit diagram consists of a three- phase generator shunt and series. But these filters also have hybrid configuration
source of 345Kv at frequency of 50Hz which is connected to the of passive filters to improve the power handling capacity of
converter transformer for stepping down voltage to 211KV for semiconductor devices.
transmission over long distance. Further a 12-pulse thyristor
bridge converter is connected, which is called as rectifier forharmonic analysis in a basic HVDC transmission system and the
converting AC to DC while the converter at the other end isimportance of using filters for the reduction of the harmonic
referred as inverter for vice-versa conversion. The rectifier-enddistortions in the system to improve the efficiency and reduce
has firing angle () control for ignition of the thyristor while thevarious ill effects due to the harmonics.
inverter-end contains the extinction/gamma control ().
On observing the various waveforms with and without the
insertion of filters, we may conclude that on connecting the
harmonic filters the voltage values is increased and optimized
while the high current values are reduced.
A. Three Phase Converter - The converter transformers are
constructed by three phase three winding on same core
material by connecting primary and secondary windings as
either wyes or deltas.
B. Pulse Generator - a discrete twelve pulse generator is used to
fire the thyristors of HVDC rectifier built with two six pulse
bridges. The four inputs of a pulse generator are alpha firing
angle (in degrees), other three inputs are phase to ground
synchronizing voltages. There are two outputs of a pulse
generator, one connected to wye secondary winding of
transformer and other connected to delta winding of secondary
transformer. Similarly for gamma angle control at the inverterside, a twelve-pulse firing control and discrete gamma
measurement subsystem is used for the two extinction/gamma
angle triggering for the inverter.
C. Filters - Both the ends have AC filters for reducing the
harmonic distortion in the AC-side of the system and DC filters
or smoothening reactors on the DC line for reducing the ripple
content in the current. The AC filters comprises of both passive
and active components for efficient performance and economy.
Generally the passive filters used are of damped (high-pass) and
tuned (single, double or triple) types while active filters are of