CW SYSTEM

STAGE-1
PARTIAL
LOAD

ALL UNIT
I/S

one unit
under O/H
ONE UNIT
OUT OF
service

O/H

FULL LOAD
SUMMER

WINTER

Two pumps
are stopped
6

CW SYSTEM
STAGE-2
PARTIAL
LOAD

ONE UNIT
I/S

BOTH UNIT
IN I/S

O/H

FULL LOAD
SUMMER

WINTER

DRAFT SYSTEMS
STAGE-1
BTL

LIGHT UP

JUST BEFORE
SYNC

DRAFT/O2

(FORCE
COOLING)

ID FAN

-10

FD FAN

3-3.5 %

After boiler cooling, Fans along with its LOP is stopped.


All APH are stopped when APH inlet flue gas temp <
100deg

DRAFT SYSTEMS
STAGE-2
BTL

LIGHT UP

JUST BEFORE
SYNC

DRAFT/O2

(FORCE
COOLING)

ID FAN

-5

FD FAN

3-3.5 %

After boiler cooling, Fans along with its LOP is stopped.


All APH are stopped when APH inlet flue gas temp <
100deg

CONDENSATE & FEED WATER


SYSTEM
STAGE-1
STARTUP

JUST
BEFORE
SYNC

>70%
LOAD

HYDROTE
ST

MDBFP

TDBFP

N/A

N/A

N/A

N/A

BCW

N/A

N/A

N/A

N/A

CEP

2
(before LP
B/P charging)

BOILER
FILLING

BTL
FORCE
COOLING
1

BOILER
FILL PUMP

N/A

After unit shut down, all CEP is stopped after LPT exhaust hood
temp. reaches normal running temperature after temp. rise .
BFP is run as per Boiler cooling requirement.

CONDENSATE & FEED WATER


SYSTEM
STAGE-2
STARTUP

JUST
BEFORE
SYNC

>70%
LOAD

HYDROTE
ST

MDBFP

TDBFP

BCW

CEP

2
(before LP
B/P charging)

BOILER
FILLING

BTL
FORCE
COOLING
1

BOILER
FILL PUMP

After unit shut down, all BCW pumps are stopped when drum metal temp. reaches 100
deg
After unit shut down, all CEP is stopped after LPT exhaust hood temp. reaches normal
running temperature after temp. rise .

MILLING SYSTEMS
STAGE-1
DURING
START UP
WHEN APH
AIR OUTLET
FULL LOAD
TEMP>180
0
& HP/LP
BYPASS I/S

MILL

PA FAN

4
2

BLENDED COAL

PARTIAL
LOAD

60 TO 80 % 80-100%
LOAD
LOAD

After unit shut down, LOP of PA fans and mills stop after 30min. as per logic
During cold startup , Mill is taken i/s after Synchronization

MILLING SYSTEMS
STAGE-2
DURING
START UP
WHEN APH
AIR OUTLET
FULL LOAD
TEMP>180
0
& HP/LP
BYPASS I/S

MILL

PA FAN

6 or 7
2
(AFTER 3 MILLS
I/S)

BLENDED COAL

PARTIAL
LOAD

60 TO 80 % 80-100%
LOAD
LOAD

After unit shut down, LOP of PA fans and mills are stopped
after sometime

ESP SYSTEMS
STAGE-1
HOPPER HEATER

OFF AFTER HOPPER ASH EMPTY

FIELDS

OFF AFTER 01 hour of UNIT S/D

RAPPING MOTORS

OFF AFTER 04 HR CONT. RUN

ESP SYSTEMS
STAGE-2
HOPPER HEATER

OFF AFTER HOPPER ASH EMPTY

FIELDS

OFF AFTER UNIT S/D

RAPPING MOTORS

OFF AFTER 04 HR CONT. RUN

AHU

1 OUT OF 2 AHU IS STOPPED

LDO/HFO SYSTEMS
STAGE-1
LDO PUMP

DISCHARGE PR MAINTAINED AT
16 KSC

HFO

PR MAINTAINED 10-11 KSC AT F/F


with long recirculation in open
condition

LDO/HFO SYSTEMS
STAGE-2
LDO PUMP

DISCHARGE PR MAINTAINED AT 9
KSC

HFO

PR MAINTAINED 6 KSC AT F/F


AFTER CV (SET POINT CHANGE
TO 9 KSC IN AUTO WHEN ANY
HONV OPEN)

ECW SYSTEMS
STAGE-1
Two(out of three) ECW are i/s during
normal Unit running.
One ECW is kept i/s during unit under shut
down till cooling water requirement in the
unit.

ACW/ECW SYSTEMS
STAGE-2
ONLY ONE ACW I/S IN WINTER AT FULL
LOAD
ALL ACW ARE STOPPED AFTER UNIT
SHUT DOWN KEEPING SUCTION &
DISCHARGE V/V OPEN
ONE TGECW IS STOPPED AFTER UNIT
SHUT DOWN
SGECW IS STOPPED AFTER BOILER
COOLING.

AIR COMPRESSORS
STAGE-1
When any unit is stopped for short
shut down, one compressor is
stopped after isolating service air of
that unit.

APC REDUCTION STRATEGY AFTER UNIT


SHUT DOWN
STAGE-1

Only following equipments are in


service during unit short shut down :
1.
2.
3.
4.
5.
6.
7.

Aux. OIL P/P


One JOP
Seal Oil Pump
01 ECW P/P
Stator Water P/P
Scanner fan as per furnace cooling requirement
APH motor till flue gas temp. <100 deg.

APC REDUCTION STRATEGY AFTER UNIT


SHUT DOWN
STAGE-2

Only following equipments are in


service during unit short shut down :
1.
2.
3.
4.
5.
6.
7.
8.
9.

TG LUB OIL P/P


TG JOP
AIR SIDE SOP
H2 SIDE SOP
01 TGECW P/P
PW P/P
CF P/P
TDBFP LUB OIL P/P
LP BY PASS OIL P/P

AIR CONDITIONING & AIR WASHER SYSTEM


STAGE-1

In winter season, all Air Washer Units are stopped.


In winter season, main a/c compressors and VAM are
stopped and condensate water is circulated in chilled water
circuit.
In summer season, VAM is kept in service for unit # 3
&4(Unit #1&2 VAM not provided).

AIR CONDITIONING & AIR WASHER SYSTEM


STAGE-2

1 Set of air washer is stopped in AB bay and BC bay after


unit shut down.
In winter season, all Air Washer Units are stopped.
In winter season, AHU and screw chiller are regulated as
per temperature requirement.
In summer season, VAM is kept in service instead of screw
chiller