23.

26 %
40 MVA
+12 % to -16 %
110 kV
123.20 kV
92.40 kV
12.5 kV
1847.52 A
22 TAPS
10 TAP
1.27 %
2 STEPS
2.55 %
500 A
12500V / 100V = 125
300A / 1A = 300
I
C
=
V |Z|
112.20 kV
CORRESPONDING SECONDARY VOLTAGE: 12.75 kV
250 V
11.72
2.73
I
C
= 91.72 A
= 90 A
Current carrying capacity of OLTC as per manufacturer = 500 A
Corresponding current on Secondary side = 4400 A
Set over current Blocking at = 80% OF 4400A
= 3520.00 A
Relay current = 11.7333 A
PRIMARY VOLTAGE ON LOWER TAP:
RESULTANT VOLTAGE:
BASE IMPEDANCE (IN OHMS):
TRAFO IMPEDNACE (IN OHMS):
RECOMMENDED SETTING
NUMBER OF TAPS:
NOMINAL TAP IS NO.:
LOWER THAN OTHER PARALLELED TRANSFORMER(S).
STEP VOLTAGE:
VOLTAGE REGULATION AFTER:
REGULATION SETTING:
TRANSFORMER REGULATION:
PRIMARY SIDE RATED VOLTAGE (NOMINAL TAP):
PRIMARY SIDE RATED VOLTAGE (MAXIMUM TAP):
OVERCURRENT BLOCKING
RATED SECONDARY SIDE CURRENT:
CALCULATION OF CIRCULATING CURRENT
FOR CALCULATION PURPOSES, ASSUME TRANSFORMER IS TWO TAPS
PRIMARY SIDE RATED VOLTAGE (MINIMUM TAP):
SECONDARY SIDE RATED VOLTAGE (AT NOMINAL PRIMARY TAP):
OLTC RATED CURRENT:
CT & VT DATA
VT RATIO FACTOR:
CT RATIO FACTOR:
AVR SETTING CALCULATION
BASIC TRANSFORMER DATA
VECTOR GROUP: YNyn0(d5)
TRANSFORMER RATED POWER IN MVA:
PERCENTAGE IMPEDANCE:
Recommended O/C blocking I> = 11.7333 A
Recommended Band width Us = 2.55%
corresponding to two tap to avoid the hunting of the OLTC.
BANDWIDTH SELECTION
It is necessary to keep the band width approximately