Point No. 1
Discription
Ok noted and spares are considered 33 KV Incomer. (Input -Cable No. of Core/Pair has been indicated as 12C with 2 Core Spare. But here all the tag DI-28) 12C has been used to transmit the signals, there is no Spare Core available. But Spare has been indicated in the schedule. Please check and clarify.
Whether all the Analog Signals from the field Instruments individually going to PLC? Whether there is any JB, from where the signals will go to the PLC.