Nothing Special   »   [go: up one dir, main page]

CERN Accelerating science

Article
Title SRF Performance of CEBAF After Thermal Cycle to Ambient Temperature
Author(s) Rimmer, Robert ; Benesch, Jay ; Preble, Joseph P ; Reece, Charles E
Affiliation (Jefferson Lab, Newport News, Virginia)
Publication 2005
In: 21st IEEE Particle Accelerator Conference, Knoxville, TN, USA, 16 - 20 May 2005, pp.665
Subject category Accelerators and Storage Rings
Abstract In September 2003, in the wake of Hurricane Isabel, JLab was without power for four days after a tree fell on the main power lines feeding the site. This was long enough to lose insulating vacuum in the cryomodules and cryogenic systems resulting in the whole accelerator warming up and the total loss of the liquid helium inventory. This thermal cycle stressed many of the cryomodule components causing several cavities to become inoperable due to helium to vacuum leaks. At the same time the thermal cycle released years of adsorbed gas from the cold surfaces. Over the next days and weeks this gas was pumped away, the insulating vacuum was restored and the machine was cooled back down and re-commissioned. In a testament to the robustness of SRF technology, only a small loss in energy capability was apparent, although individual cavities had quite different field-emission characteristics compared to before the event. In Summer 2004 a section of the machine was again cycled to room temperature during the long maintenance shutdown. We report on the overall SRF performance of the machine after these major disturbances and on efforts to characterize and optimize the new behavior for high-energy running.



 Record created 2006-02-09, last modified 2024-02-23